Results

A PUE of 1.48 means every kWh the IT gear consumes comes with a total facility draw of 1.48 kWh. Over a year the site uses 12,970 MWh, and 4,210 MWh of that is overhead worth 505,247 €. If the PUE fell to 1.3, the same IT load would save 189,887 € and 725 t CO₂ annually.
PUE
1.48
DCiE 67.5%
Facility power
1,481kW
Annual energy
12,970MWh
8,760 MWh for IT
Annual electricity cost
1.6million €
Cost of overhead
€505,247
cooling, electrical losses and the building
Yearly cost per kW of IT load
€1,556
Saving at target PUE
€189,887
1,582 MWh per year
CO₂ per year
5,940t
Water per year
15,768m³
WUE 1.8 L/kWh
Where the power goes (kW)
Yearly power cost by PUE (€)

Energy balance

ComponentkWMWh/yrShare
IT equipment1,0008,76067.5%
Cooling375.53,29025.4%
UPS losses65.15704.4%
Transformers & PDUs201751.4%
Lighting & other201751.4%
  • ISO/IEC 30134-2 defines PUE as measured over a whole year at the facility meter, while this tool works with average power. When you know the PUE, the overhead split shown is only illustrative (70% cooling).
  • Water use depends strongly on cooling design and climate, so enter your own WUE (ISO/IEC 30134-9). Emissions rely on the average grid intensity of the chosen country.

Free calculator by Energy.com.info