Results

Expect 18 h 11 min at 210 W. This meets your 12-hour goal.
Backup time
18 h 11 min
210 W load · 0.8 days
Usable energy
4.61kWh
5.12 kWh nominal × 90% DoD
Battery drain
253W
includes 11% inverter loss and 20 W standby
Discharge current
19.8A
0.05C at 12.8 V
Runtime without Peukert
18 h 11 min
lithium: negligible
Energy reaching the loads
3.82kWh
Capacity for 12 h
3.3kWh
256 Ah at 12.8 V nominal
Temperature and ageing factor
100%
25 °C, 100% health
Runtime vs. load
Load breakdown

Runtime at other loads

LoadBattery drain (W)Current (A)RuntimeC-rate
25 W483.796 h 27 min0.01C
50 W765.960 h 59 min0.01C
100 W13110.235 h 09 min0.03C
200 W24218.919 h 01 min0.05C
300 W35327.613 h 02 min0.07C
500 W576458 h 00 min0.11C
750 W85366.75 h 24 min0.17C
1,000 W1,13188.44 h 04 min0.22C
1,500 W1,687131.82 h 41 min0.33C
2,000 W2,242175.22 h 00 min0.44C
3,000 W3,3532621 h 20 min0.65C

Selected loads

DeviceAverage WShare
Refrigerator6029%
Wi-Fi router + modem157%
LED lighting (5 bulbs)4521%
TV 50"9043%
  • What counts is the average draw, not the nameplate. A fridge labelled 150 W switches on and off and averages 40–80 W. Start-up surges influence inverter size, not runtime.
  • Lithium batteries hold almost their full capacity at moderate current, so the Peukert effect is tiny (k ≈ 1.02–1.05).