Batteries & storage calculator

Will my battery last the night? Backup runtime calculator for any load

Which battery, and how many hours? Works for power stations, home batteries, UPS units and 12 V banks. Enter capacity and the tool deducts depth of discharge, inverter losses, temperature and ageing; for lead-acid it applies Peukert’s law.

Editable share link Branded PDF report Free · no sign-up

Results

Expect 18 h 11 min at 210 W. This meets your 12-hour goal.
Backup time
18 h 11 min
210 W load · 0.8 days
Usable energy
4.61kWh
5.12 kWh nominal × 90% DoD
Battery drain
253W
includes 11% inverter loss and 20 W standby
Discharge current
19.8A
0.05C at 12.8 V
Runtime without Peukert
18 h 11 min
lithium: negligible
Energy reaching the loads
3.82kWh
Capacity for 12 h
3.3kWh
256 Ah at 12.8 V nominal
Temperature and ageing factor
100%
25 °C, 100% health
Runtime vs. load
Load breakdown

Runtime at other loads

LoadBattery drain (W)Current (A)RuntimeC-rate
25 W483.796 h 27 min0.01C
50 W765.960 h 59 min0.01C
100 W13110.235 h 09 min0.03C
200 W24218.919 h 01 min0.05C
300 W35327.613 h 02 min0.07C
500 W576458 h 00 min0.11C
750 W85366.75 h 24 min0.17C
1,000 W1,13188.44 h 04 min0.22C
1,500 W1,687131.82 h 41 min0.33C
2,000 W2,242175.22 h 00 min0.44C
3,000 W3,3532621 h 20 min0.65C

Selected loads

DeviceAverage WShare
Refrigerator6029%
Wi-Fi router + modem157%
LED lighting (5 bulbs)4521%
TV 50"9043%
  • What counts is the average draw, not the nameplate. A fridge labelled 150 W switches on and off and averages 40–80 W. Start-up surges influence inverter size, not runtime.
  • Lithium batteries hold almost their full capacity at moderate current, so the Peukert effect is tiny (k ≈ 1.02–1.05).

Why simple division overshoots

Capacity divided by load looks like the whole answer, yet it commonly overstates runtime by 30–50%. The calculator corrects for what really shortens it.

  • How deep you may go. Lithium iron phosphate (LFP) lets you use 80–100% of its capacity, while lead-acid ages quickly if taken below about 50%.
  • What the inverter takes. Converting battery power for AC loads costs 7–15%, and an inverter that stays on also eats idle power every hour.
  • How hard you pull. Lead-acid returns less charge at high current. Peukert’s equation is applied relative to the rated discharge time, 20 hours on most lead-acid ratings.
  • Cold and wear. Capacity falls in the cold (about 1% per °C below 25 °C for lead-acid) and with age; end of life is usually put at 70–80% of the original.

Select the appliances you want running during an outage, or enter a total, and the calculator reports runtime, current and C-rate. It also draws a runtime curve for other loads and sizes the battery for your target backup time.

Equations

E_usable = Ah × V × n × DoD × SoH × k_temp (or kWh × n × …) P_battery = P_load ÷ η_inverter + P_idle (DC loads: P_battery = P_load) Lithium: t ≈ E_usable ÷ P_battery Lead-acid: t = H × [ C ÷ (I × H) ]^k × DoD, I = P_battery ÷ V C-rate = I ÷ C

H is the rated discharge time (20 h), C the effective capacity in Ah, and k the Peukert exponent: 1.1–1.3 for lead-acid, about 1.03 for LFP.

Example: two 200 Ah LFP batteries during a power cut

The preset pairs two 12.8 V 200 Ah LiFePO₄ batteries in parallel, 4.61 kWh usable out of 5.12 kWh nominal at 90% DoD. What they run: a fridge at 60 W average, a 15 W router, 45 W of LED lighting and a 50-inch TV at 90 W, 210 W in total. The inverter is 90% efficient and idles at 20 W, so the battery delivers 253 W, only 0.05C. That lasts about 18 hours 11 minutes, comfortably more than the 12-hour goal.

Switch to two 12 V 200 Ah AGM batteries and half the energy is usable, 2.4 kWh at 50% DoD, so the same load lasts about 9 hours 24 minutes. Raise the load to 1,000 W and the AGM bank holds out for only 1 hour 41 minutes. That is 21% less than plain division suggests, since a 94 A discharge brings the Peukert penalty into play.

Reading the numbers

  • Backup time ends when you reach the DoD limit, not when the battery is flat.
  • Battery drain reveals the inverter’s overhead. If idle power is a large part of a small load, running DC appliances or choosing a smaller inverter gains real hours.
  • C-rate gets a warning above the comfortable limit for the chemistry (about 0.2–0.3C lead-acid, 1C LFP).
  • Capacity for target returns the required bank size with Peukert and temperature built in. To refine the layout, go to the battery bank size calculator.

Sample runtimes

The battery here is 12 V 100 Ah (1.2 kWh nominal) behind an inverter with 90% efficiency and 20 W idle draw, apart from the DC CPAP. Age and temperature will move real results.

  • Router and modem, 15 W: about 30 h on LFP (90% DoD), about 17 h on AGM (50% DoD).
  • CPAP without humidifier, 40 W, DC: about 29 h on LFP, 16 h on AGM.
  • Fridge at 60 W average: about 13 h on LFP, 6.5 h on AGM.
  • Essentials at 200 W: about 4.7 h on LFP, 2 h on AGM.
  • Microwave at 1,000 W: about 1 h on LFP, 20 min on AGM.

Getting more hours

  • Use the real average load. Labels on fridges and freezers state the maximum, whereas the daily average is typically a third to a half of that. Get it with a plug-in meter or the appliance energy cost calculator.
  • Turn the inverter off when no AC device is needed, or power routers, lights and CPAPs straight from 12 V.
  • Keep it warm. A battery at 0 °C in an unheated garage can give up 10–25% of its capacity.
  • Do not oversize the inverter. A 3 kW model idling at 40 W may burn more than the router it is meant to keep alive.
  • Add solar charging. In summer even a few hundred watts of panels can carry you through an outage indefinitely; the off-grid solar calculator shows how.

What the model leaves out

Near empty, voltage sag may trip an inverter’s low-voltage cut-off before the nominal DoD is reached. Peukert’s law is an empirical fit for moderate currents; at very low currents it overpredicts capacity, which is why the gain is capped at 15% for lead-acid. The model ignores battery-management-system limits, cell imbalance and temperature shifts during discharge. For power banks quoted in mAh at 3.6–3.7 V, convert to Wh before using it.

Method & assumptions

Usable energy = nominal capacity (Ah × V × number of batteries, or kWh) × depth of discharge × state of health × temperature factor (about −1% per °C below 25 °C for lead-acid, about −0.4% per °C for lithium). Draw on the battery = load ÷ inverter efficiency, plus the inverter's own idle power when the load is AC.

Runtime follows Peukert's law: t = H × [C ÷ (I × H)]^k × DoD. Here C is the effective capacity in Ah, I is the drain divided by battery voltage, H is the rated discharge time (20 h for lead-acid) and k is the Peukert exponent. With lithium, k is close to 1, so runtime ≈ usable Wh ÷ drain W.

Frequently asked questions

How many hours will a 100Ah battery run a load?
The 1.2 kWh stored in a 12 V 100 Ah battery is mostly usable with lithium (LFP), around 90%. A 100 W appliance on an inverter really costs the battery about 130 W, which gives 8.5–9 hours. If the battery is lead-acid and only half may be used, expect about 4 hours, and less when the load is heavy because of the Peukert effect.
What is the formula for battery runtime?
Hours = usable energy in the battery (Wh) ÷ power the battery has to deliver (W). Build the first from Ah × V × depth of discharge × health × temperature factor, and the second from load ÷ inverter efficiency + inverter idle draw. With lead-acid, add a Peukert correction, because high discharge currents shrink capacity.
How long does a 10 kWh battery keep a house running?
At 95% usable capacity and with an efficient inverter, 10 kWh gives about 9 kWh. Essentials such as the fridge, router, lights and TV (about 200–300 W) last 30–40 hours. A typical house pulling 1 kW lasts about 8–9 hours, and electric heating, ovens or air conditioning empty the battery within a few hours.
What does the Peukert effect mean?
Peukert's law captures a simple fact: the harder you discharge a battery, the less of its rated capacity you get. For lead-acid (exponent 1.1–1.3) it counts. An AGM battery rated 100 Ah over 20 hours may deliver just 70–80 Ah when emptied in two hours. Lithium, with an exponent near 1.02–1.05, is practically unaffected.
Why is my real battery runtime shorter than calculated?
Usual suspects: a nameplate wattage typed in instead of the average (motors and compressors cycle), an inverter idling at 10–50 W through the day and night, low temperatures, an ageing battery (70–80% of capacity left at end of life), and lead-acid pushed at high current. Each one has a field in the advanced options.
What battery capacity gives 24 hours of backup?
Take the average battery drain, multiply by 24 h, and divide by the share of capacity you may use. A 250 W drain makes 6 kWh of usable energy, which means buying about 6.7 kWh of lithium (90% DoD) or 12 kWh of lead-acid (50% DoD). The 'capacity for target' tile runs the same sum with Peukert and temperature included.

Sources & references

  1. Peukert, W. (1897). Über die Abhängigkeit der Kapazität von der Entladestromstärke bei Bleiakkumulatoren. Elektrotechnische Zeitschrift 20
  2. Battery University: BU-503: How to calculate battery runtime; BU-502: Discharging at high and low temperatures
  3. IEEE Std 1188 / IEEE 485: Sizing and maintenance of lead-acid batteries for stationary applications