Results

Required: ≈ 13.8 kWh nominal, i.e. 288 Ah at 48 V. Built from 12.8 V, 100 Ah units that means 4 in series and 3 in parallel, 12 units in total, storing 15.36 kWh.
Configuration
4S3P
12 × 12.8 V 100 Ah
Required capacity
13.8kWh
288 Ah at 48 V
Installed bank
15.36kWh
300 Ah at 51.2 V
Usable energy (new)
11.2kWh
80% DoD, temp. 94%
Real autonomy at end of life
1.7days
target 1.5 days
Peak discharge current
63A
0.21C · bank limit 300 A
Units in series
4
12.8 V × 4 = 51.2 V
Parallel strings
3
fuse each string
How the required capacity is built up
Number of units against days of autonomy

The same requirement at other system voltages

SystemLayoutUnitskWhAh neededPeak AStatus
12 V1S11P1114.081,152252OK
24 V2S6P1215.36576126OK
48 V4S3P1215.3628863OK

Sizing steps

StepWh
Daily energy measured at the battery terminals5,376
× days of autonomy8,065
÷ discharge efficiency8,314
÷ depth of discharge10,392
÷ temperature factor11,056
÷ end-of-life capacity13,820
  • In series, voltages add and Ah stay unchanged. In parallel, Ah add and voltage stays unchanged. Use identical units of the same age, wire parallel strings with cables of equal length (diagonal or busbar connection), and fuse every string.
  • Each series string of a lithium bank needs its own BMS. DIY cell packs also need a balancer and fuses at cell level.