Batteries & storage calculator

Size your battery bank: capacity, amp-hours and series/parallel wiring

Shows the kWh and amp-hours a battery bank must supply once margins for discharge depth, temperature, ageing and efficiency are added, then lays out the series and parallel wiring for your chosen cells.

Editable share link Branded PDF report Free · no sign-up

Results

Required: ≈ 13.8 kWh nominal, i.e. 288 Ah at 48 V. Built from 12.8 V, 100 Ah units that means 4 in series and 3 in parallel, 12 units in total, storing 15.36 kWh.
Configuration
4S3P
12 × 12.8 V 100 Ah
Required capacity
13.8kWh
288 Ah at 48 V
Installed bank
15.36kWh
300 Ah at 51.2 V
Usable energy (new)
11.2kWh
80% DoD, temp. 94%
Real autonomy at end of life
1.7days
target 1.5 days
Peak discharge current
63A
0.21C · bank limit 300 A
Units in series
4
12.8 V × 4 = 51.2 V
Parallel strings
3
fuse each string
How the required capacity is built up
Number of units against days of autonomy

The same requirement at other system voltages

SystemLayoutUnitskWhAh neededPeak AStatus
12 V1S11P1114.081,152252OK
24 V2S6P1215.36576126OK
48 V4S3P1215.3628863OK

Sizing steps

StepWh
Daily energy measured at the battery terminals5,376
× days of autonomy8,065
÷ discharge efficiency8,314
÷ depth of discharge10,392
÷ temperature factor11,056
÷ end-of-life capacity13,820
  • In series, voltages add and Ah stay unchanged. In parallel, Ah add and voltage stays unchanged. Use identical units of the same age, wire parallel strings with cables of equal length (diagonal or busbar connection), and fuse every string.
  • Each series string of a lithium bank needs its own BMS. DIY cell packs also need a balancer and fuses at cell level.

Why the bank ends up bigger than the load

Your loads give a starting energy figure, but the capacity on the label must sit well above it, for four reasons: a battery must not be emptied, cold weakens it, heat takes a share, and age wears the cells down. Each reason is applied in turn (the bar chart shows the need rising), and the result becomes a wiring plan for the battery or cell you selected.

  1. For AC loads, divide daily energy by inverter efficiency to get the energy needed at the battery.
  2. Multiply by the days of autonomy the bank must deliver with no recharge.
  3. Allow for discharge losses inside the battery: about 3% with LFP, 10% with lead-acid.
  4. Respect depth of discharge. LFP can give 80–90% of its capacity, lead-acid about 50%.
  5. Correct for cold: roughly 1% lost per °C under 25 °C for lead-acid, 0.4% for lithium.
  6. Add the end-of-life margin (the IEEE 485 ageing factor), so the bank still copes when worn.

Amp-hours follow from dividing by system voltage. The tool builds the string in series to reach that voltage, parallels strings to reach the capacity, and finally compares the bank’s current rating with your peak load.

Equations

E_req = (E_day ÷ η_inv) × days ÷ η_batt ÷ DoD ÷ k_temp ÷ k_EOL Ah_req = E_req ÷ V_system N_series = V_system ÷ V_unit N_parallel = ⌈ E_req ÷ (V_bank × Ah_unit) ⌉ I_peak = P_peak ÷ η_inv ÷ V_bank ≤ N_parallel × I_max,unit

Example: 48 V off-grid home

In the preset, the battery supplies 5 kWh a day via an inverter that is 93% efficient. It must last 1.5 days, the LFP cells may go to 80% DoD, the lowest temperature is 10 °C, and the end-of-life design point sits at 80%.

Follow the chain. The terminals must deliver 5.38 kWh/day; over 1.5 days that is 8.06 kWh; discharge losses lift it to 8.31 kWh, the 80% DoD limit to 10.4 kWh and the 10 °C cold to 11.1 kWh. Dividing by the end-of-life factor gives 13.8 kWh nominal, or 288 Ah at 48 V. With 12.8 V 100 Ah LFP batteries the layout is 4S3P: 51.2 V from four in series, 300 Ah from three parallel strings, so twelve batteries and 15.36 kWh. A 3 kW peak draws just 63 A, nowhere near the 300 A the strings can supply, and 1.7 days of autonomy remain even at end of life.

At 12 V the same job would take eleven batteries in parallel and 252 A at peak, which is a strong case for 48 V.

Reading the results

  • Configuration such as 4S3P describes the wiring: series units per string × parallel strings.
  • Installed bank is generally slightly above the requirement, because batteries come whole.
  • Actual autonomy (end of life) is the real reserve once the bank has been rounded up to whole units.
  • Peak discharge current and C-rate: lead-acid prefers staying under about 0.2C, LFP under 0.5–1C (confirm with the BMS rating).

Bank sizes by use

  • Van or small boat: 1–2 kWh a day, 1 day of autonomy. LFP bank 12 V 100–200 Ah, lead-acid 12 V 200–400 Ah.
  • Weekend cabin: 1.5–3 kWh a day, 1.5–2 days. LFP 24 V 150–300 Ah, lead-acid 24 V 300–600 Ah.
  • Off-grid home: 4–10 kWh a day, 1.5–3 days. LFP 48 V 200–600 Ah, lead-acid 48 V 500–1,500 Ah.
  • Home backup for essentials: 3–6 kWh a day, 0.5–1 day. 5–10 kWh at 48 V in LFP; lead-acid is rarely used for this now.

Build advice

  • Match the batteries: one model, one capacity, one age, and one chemistry only.
  • Wire strings symmetrically with the positive lead from one end and the negative from the opposite end, or with busbars, so that every string sees the same cable resistance.
  • Put a fuse on every parallel string, close to the battery. Without one, all the other strings feed a short in a single string.
  • Choose a higher voltage rather than more strings. You save fuses, balance better and use thinner cable (see the cable size calculator).
  • Check runtime at real loads with the battery backup time calculator, and the charging side with the off-grid solar calculator.

Boundaries of the model

Daily energy is treated as an average. When short, very high loads dominate, check the battery’s power rating and Peukert losses on their own. Temperature factors are simple linear approximations, and lithium charging limits below 0 °C are not modelled. Settings of the battery-management system, cell balancing and the manufacturer’s own parallel limits always override these general rules.

Method & assumptions

Nominal energy to install = daily energy ÷ inverter efficiency × days of autonomy ÷ battery discharge efficiency ÷ depth of discharge ÷ temperature factor ÷ end-of-life capacity, which is an ageing allowance in the spirit of IEEE 485. Ah to install = Wh ÷ system voltage.

The number of units in series is system voltage ÷ single-unit voltage, and the number of parallel strings is ⌈ required Wh ÷ (bank voltage × unit Ah) ⌉. For the peak current, divide peak load by inverter efficiency and by bank voltage, then compare it with parallel strings × the continuous current limit of one unit.

Frequently asked questions

Method for calculating the battery bank I need?
Begin with kWh per day taken from the battery, then correct for the inverter's efficiency. Multiply by how many days you want to ride through without charging. Finally inflate the figure for depth of discharge, cold and end-of-life wear. One case: 5 kWh/day, 1.5 days, LFP at 80% DoD, 10 °C and an 80% end-of-life design point need about 13.8 kWh nominal, i.e. 288 Ah at 48 V.
How many batteries make up a 48 V bank?
One 48 V string needs 48 divided by the voltage of each unit: that is four 12 V (12.8 V LFP) batteries, eight 6 V ones, sixteen 3.2 V LFP cells, or twenty-four 2 V cells. Capacity comes from paralleling more identical strings until the amp-hours are met. Reading 4S3P: four in series, three strings side by side, twelve batteries in all.
Series or parallel: what changes?
Wiring in series adds the voltages and leaves capacity alone, so two 12 V 100 Ah batteries become 24 V 100 Ah. Wiring in parallel adds amp-hours at constant voltage, so the same pair becomes 12 V 200 Ah. Stored energy is 2.4 kWh either way, but the higher-voltage layout halves the current for a given power.
What is the limit on parallel battery strings?
Unequal cable resistance and uneven ageing make parallel strings share current badly, so makers of lead-acid batteries mostly limit a bank to three or four strings. Lithium units with a built-in BMS tolerate more. Beyond about eight strings, a single larger battery or a rack system is easier to protect and balance.
Which voltage should the bank use, 12 V, 24 V or 48 V?
The load power decides. 12 V works up to about 1–1.5 kW, 24 V suits 1.5–3 kW, and 48 V takes over beyond that. Compare a 3 kW inverter: about 270 A at 12 V against only 68 A at 48 V. Higher voltage means thinner cables, smaller fuses and lower losses.
What does the ageing factor do in battery sizing?
For stationary batteries, IEEE 485 applies a factor of 1.25, which keeps the bank adequate when its capacity has dropped to 80% at end of life. Leave it out and a battery that is barely big enough when new will fall short after a few years.

Sources & references

  1. IEEE Std 485: Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications
  2. IEEE Std 1562: Guide for Array and Battery Sizing in Stand-Alone PV Systems
  3. Battery University: BU-302 Series and parallel battery configurations
  4. Sandia National Laboratories: Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices