Results

Copper at 6 mm² (≈ 8 AWG) can take 32 A across 25 m. The drop is 2.56% (5.9 V) and the loss is 189 W.
Recommended cable
6 mm²
≈ 8 AWG · copper
Voltage drop
2.56%
5.9 V of 230 V · limit 3%
Power loss in cable
189W
2.56% of 7.36 kW
Current
32A
cos φ 1
Smallest size meeting the voltage drop
6 mm²
exact 4.96 mm²
Min. size for current
4 mm²
Clipped straight onto a wall or tray, 30 °C
Current rating of the selected size
46A
ambient factor 1
Max length at this size
29m
for a 3% drop
Energy lost per year
189kWh
at 1,000 full-load hours
Voltage drop for each cross-section (25 m, 32 A)

Cable size comparison

SizeAWG ≈Drop %Drop VLoss WCapacity AMax length mOK?
1 mm²16 AWG15.07%34.651,109165✗ current
1.5 mm²14 AWG10.07%23.16741207✗ current
2.5 mm²12 AWG6.17%14.194542712✗ current
4 mm²10 AWG3.84%8.832823620✗ drop
6 mm² ◀8 AWG2.56%5.91894629✓
10 mm²6 AWG1.52%3.51126349✓
16 mm²4 AWG0.96%2.2708578✓
25 mm²3 AWG0.61%1.3945112124✓
35 mm²1 AWG0.44%132138172✓
50 mm²1/0 AWG0.32%0.7424168233✓
70 mm²3/0 AWG0.22%0.5116213336✓
95 mm²4/0 AWG0.16%0.3712258467✓
  • Drop is calculated as ΔV = 2 × L × I × (R·cos φ + X·sin φ). Conductor resistance is taken from IEC 60228 and adjusted for 70 °C; reactance is fixed at 0.08 mΩ/m.
  • Treat the current capacity as a guide only. It comes from IEC 60364-5-52 tables (PVC/XLPE, method factors, ambient temperature and grouping corrections). Final sizing is decided by your national wiring regulations (BS 7671, NEC 310, VDE 0298-4 and others) together with the protective device rating.
  • Motor starting currents of 5–7 times nominal create short extra voltage drops, so check start-up conditions on long motor feeders.

Free calculator by Energy.com.info