Heat versus loss
Choosing a conductor means passing two separate tests. One is thermal: the cable must not overheat at the load current, which is its ampacity. The other is electrical: enough voltage has to arrive at the far end. Short circuits are usually thermal-limited. Long ones, low-voltage ones and solar arrays almost always fail on voltage drop first. This tool runs both tests and reports the smallest standard cross-section that clears them.
The loss calculation takes IEC 60228 resistances for stranded copper or aluminium and adjusts them to the temperature the conductor will actually reach. Copper gains about 0.39% resistance per °C, so at 70 °C it carries 20% more than at 20 °C. On AC circuits a typical reactance and the power factor come in as well. The thermal side begins with the IEC 60364-5-52 reference table for PVC-insulated copper clipped direct, then multiplies by factors for the installation method, XLPE insulation, surrounding temperature, bundling with other circuits and aluminium.
You also get the watts lost as heat, annual energy waste, the longest permitted run per size and the AWG equivalent.
Formulas
Case study: a 25 m feed to a 7.4 kW charger
Defaults: a single-phase 230 V charger drawing 32 A, a 25 m cable from the board, copper with PVC insulation clipped to a wall, and a 3% drop budget.
- Thermal capacity alone accepts 4 mm², rated 36 A under method C.
- The drop on that size is 8.8 V, or 3.84%, so it fails the budget.
- 6 mm² brings the drop to 5.9 V (2.56%). Its rating is up to 46 A, and at full power it dissipates about 189 W. That is the pick (≈ 8 AWG), good for runs up to about 29 m at 3%.
- A cable sized exactly for 3% would be 4.96 mm². Stepping up to 10 mm² halves the waste to 112 W.
Making sense of the results
- Recommended cable: the smallest standard size meeting both limits. The two “minimum size” tiles tell you which constraint is binding.
- Power loss: significant wherever current flows for long hours. With solar circuits and heat pumps, going up one size often earns its cost back in saved losses.
- Max length at this size: the quick answer to how far a given cable can reach.
- Comparison table: neighbouring sizes side by side (drop, loss, capacity) for weighing copper price against waste.
Minimum sizes for common loads
Assumptions: copper, 70 °C, 3% drop, single-phase 230 V. The three sizes listed are for 10 m, 25 m and 50 m runs.
- 2.3 kW socket circuit (10 A): 1.5 mm², then 2.5 mm², then 4 mm².
- 3.7 kW at 16 A: 1.5 mm², 4 mm², 6 mm².
- 7.4 kW EV charger at 32 A: 4 mm², 6 mm², 16 mm².
- 11 kW three-phase 400 V at 16 A: 1.5 mm², 1.5 mm², 4 mm².
For the same power three-phase wiring is far lighter, because every conductor carries less current and √3 takes the place of the 2.
Field notes
- Measure the route in one direction only, risers and detours included. The return leg is already inside the formula.
- Prefer a higher voltage to extra copper. Doubling voltage halves current, and the percentage drop in the same cable drops to a quarter.
- Solar DC wiring should stay within 1–2% at the string’s working current; use the string sizing calculator for that.
- Battery cables see the highest currents in a system and must be consistent with the fuse. The battery bank calculator gives the continuous and peak current to size them by.
- Allow for heat. In a roof void or beside a PV array the ambient temperature can reach 50–70 °C, which slashes PVC cable capacity. XLPE or solar cable is the answer there.
Scope and caveats
The ampacities are guideline numbers taken from the IEC 60364-5-52 reference tables with simplified correction factors. What is legally required follows from national rules (BS 7671, NEC Article 310, VDE 0298-4 and others), the protective device and the short-circuit withstand. A typical multicore reactance is assumed; widely spaced single cores have more. Harmonics in the neutral, motor starting and fault-loop impedance are left unchecked. Have a qualified electrician design and verify the installation.
Method & assumptions
Load current for DC and single-phase circuits is I = P ÷ (V × cos φ); for three-phase it is I = P ÷ (√3 × V_LL × cos φ). Conductor resistance per metre is taken from IEC 60228 at 20 °C and corrected to temperature with R_T = R_20 × [1 + α(T − 20)], using α = 0.00393 for Cu and 0.00403 for Al.
The voltage drop is ΔV = k × L × I × (R cos φ + X sin φ), where k = 2 covers the outward and return path of DC and single-phase and k = √3 applies to three-phase. Power loss = n × I² × R × L for n = 2 or 3 conductors. Recommended size means the smallest standard cross-section passing the drop limit and the derated ampacity, taken from the IEC 60364-5-52 method C table and multiplied by factors for installation method, insulation, ambient temperature and grouping (aluminium × 0.78).
Frequently asked questions
Formula for voltage drop along a cable?
What voltage drop limit should I design to?
Which conductor should feed a 32 A EV charger?
How thick must cables be on a 12 V system?
How do metric cable sizes map to AWG?
Does aluminium work as well as copper for cables?
Sources & references
- IEC 60364-5-52: Low-voltage electrical installations: Selection and erection of wiring systems (current-carrying capacity, voltage drop)
- IEC 60228: Conductors of insulated cables (DC resistance values)
- NFPA 70 National Electrical Code: Article 310 (conductor ampacity) and informational notes on voltage drop
- IEC 62548-1: PV arrays design requirements (DC cable sizing)