Converters & physics calculator

Choose the right cable: voltage drop, power loss and cross-section

Picks the smallest cable that keeps voltage drop within your limit while carrying the current. Handles DC, single-phase and three-phase, copper or aluminium, with sizes in mm² and AWG, power loss and temperature derating.

Editable share link Branded PDF report Free · no sign-up

Results

Copper at 6 mm² (≈ 8 AWG) can take 32 A across 25 m. The drop is 2.56% (5.9 V) and the loss is 189 W.
Recommended cable
6 mm²
≈ 8 AWG · copper
Voltage drop
2.56%
5.9 V of 230 V · limit 3%
Power loss in cable
189W
2.56% of 7.36 kW
Current
32A
cos φ 1
Smallest size meeting the voltage drop
6 mm²
exact 4.96 mm²
Min. size for current
4 mm²
Clipped straight onto a wall or tray, 30 °C
Current rating of the selected size
46A
ambient factor 1
Max length at this size
29m
for a 3% drop
Energy lost per year
189kWh
at 1,000 full-load hours
Voltage drop for each cross-section (25 m, 32 A)

Cable size comparison

SizeAWG ≈Drop %Drop VLoss WCapacity AMax length mOK?
1 mm²16 AWG15.07%34.651,109165✗ current
1.5 mm²14 AWG10.07%23.16741207✗ current
2.5 mm²12 AWG6.17%14.194542712✗ current
4 mm²10 AWG3.84%8.832823620✗ drop
6 mm² ◀8 AWG2.56%5.91894629✓
10 mm²6 AWG1.52%3.51126349✓
16 mm²4 AWG0.96%2.2708578✓
25 mm²3 AWG0.61%1.3945112124✓
35 mm²1 AWG0.44%132138172✓
50 mm²1/0 AWG0.32%0.7424168233✓
70 mm²3/0 AWG0.22%0.5116213336✓
95 mm²4/0 AWG0.16%0.3712258467✓
  • Drop is calculated as ΔV = 2 × L × I × (R·cos φ + X·sin φ). Conductor resistance is taken from IEC 60228 and adjusted for 70 °C; reactance is fixed at 0.08 mΩ/m.
  • Treat the current capacity as a guide only. It comes from IEC 60364-5-52 tables (PVC/XLPE, method factors, ambient temperature and grouping corrections). Final sizing is decided by your national wiring regulations (BS 7671, NEC 310, VDE 0298-4 and others) together with the protective device rating.
  • Motor starting currents of 5–7 times nominal create short extra voltage drops, so check start-up conditions on long motor feeders.

Heat versus loss

Choosing a conductor means passing two separate tests. One is thermal: the cable must not overheat at the load current, which is its ampacity. The other is electrical: enough voltage has to arrive at the far end. Short circuits are usually thermal-limited. Long ones, low-voltage ones and solar arrays almost always fail on voltage drop first. This tool runs both tests and reports the smallest standard cross-section that clears them.

The loss calculation takes IEC 60228 resistances for stranded copper or aluminium and adjusts them to the temperature the conductor will actually reach. Copper gains about 0.39% resistance per °C, so at 70 °C it carries 20% more than at 20 °C. On AC circuits a typical reactance and the power factor come in as well. The thermal side begins with the IEC 60364-5-52 reference table for PVC-insulated copper clipped direct, then multiplies by factors for the installation method, XLPE insulation, surrounding temperature, bundling with other circuits and aluminium.

You also get the watts lost as heat, annual energy waste, the longest permitted run per size and the AWG equivalent.

Formulas

I = P ÷ (V × cos φ) (DC, single-phase) I = P ÷ (√3 × V_LL × cos φ) (three-phase) R_T = R_20 × [1 + α × (T − 20 °C)] α_Cu = 0.00393, α_Al = 0.00403 ΔV = k × L × I × (R_T × cos φ + X × sin φ) k = 2 (DC, 1-ph), √3 (3-ph) ΔV% = ΔV ÷ V × 100 P_loss = n × I² × R_T × L (n = 2 or 3) I_z = I_table × k_method × k_insulation × k_ambient × k_group × (0.78 if Al)

Case study: a 25 m feed to a 7.4 kW charger

Defaults: a single-phase 230 V charger drawing 32 A, a 25 m cable from the board, copper with PVC insulation clipped to a wall, and a 3% drop budget.

  • Thermal capacity alone accepts 4 mm², rated 36 A under method C.
  • The drop on that size is 8.8 V, or 3.84%, so it fails the budget.
  • 6 mm² brings the drop to 5.9 V (2.56%). Its rating is up to 46 A, and at full power it dissipates about 189 W. That is the pick (≈ 8 AWG), good for runs up to about 29 m at 3%.
  • A cable sized exactly for 3% would be 4.96 mm². Stepping up to 10 mm² halves the waste to 112 W.

Making sense of the results

  • Recommended cable: the smallest standard size meeting both limits. The two “minimum size” tiles tell you which constraint is binding.
  • Power loss: significant wherever current flows for long hours. With solar circuits and heat pumps, going up one size often earns its cost back in saved losses.
  • Max length at this size: the quick answer to how far a given cable can reach.
  • Comparison table: neighbouring sizes side by side (drop, loss, capacity) for weighing copper price against waste.

Minimum sizes for common loads

Assumptions: copper, 70 °C, 3% drop, single-phase 230 V. The three sizes listed are for 10 m, 25 m and 50 m runs.

  • 2.3 kW socket circuit (10 A): 1.5 mm², then 2.5 mm², then 4 mm².
  • 3.7 kW at 16 A: 1.5 mm², 4 mm², 6 mm².
  • 7.4 kW EV charger at 32 A: 4 mm², 6 mm², 16 mm².
  • 11 kW three-phase 400 V at 16 A: 1.5 mm², 1.5 mm², 4 mm².

For the same power three-phase wiring is far lighter, because every conductor carries less current and √3 takes the place of the 2.

Field notes

  • Measure the route in one direction only, risers and detours included. The return leg is already inside the formula.
  • Prefer a higher voltage to extra copper. Doubling voltage halves current, and the percentage drop in the same cable drops to a quarter.
  • Solar DC wiring should stay within 1–2% at the string’s working current; use the string sizing calculator for that.
  • Battery cables see the highest currents in a system and must be consistent with the fuse. The battery bank calculator gives the continuous and peak current to size them by.
  • Allow for heat. In a roof void or beside a PV array the ambient temperature can reach 50–70 °C, which slashes PVC cable capacity. XLPE or solar cable is the answer there.

Scope and caveats

The ampacities are guideline numbers taken from the IEC 60364-5-52 reference tables with simplified correction factors. What is legally required follows from national rules (BS 7671, NEC Article 310, VDE 0298-4 and others), the protective device and the short-circuit withstand. A typical multicore reactance is assumed; widely spaced single cores have more. Harmonics in the neutral, motor starting and fault-loop impedance are left unchecked. Have a qualified electrician design and verify the installation.

Method & assumptions

Load current for DC and single-phase circuits is I = P ÷ (V × cos φ); for three-phase it is I = P ÷ (√3 × V_LL × cos φ). Conductor resistance per metre is taken from IEC 60228 at 20 °C and corrected to temperature with R_T = R_20 × [1 + α(T − 20)], using α = 0.00393 for Cu and 0.00403 for Al.

The voltage drop is ΔV = k × L × I × (R cos φ + X sin φ), where k = 2 covers the outward and return path of DC and single-phase and k = √3 applies to three-phase. Power loss = n × I² × R × L for n = 2 or 3 conductors. Recommended size means the smallest standard cross-section passing the drop limit and the derated ampacity, taken from the IEC 60364-5-52 method C table and multiplied by factors for installation method, insulation, ambient temperature and grouping (aluminium × 0.78).

Frequently asked questions

Formula for voltage drop along a cable?
For DC or single-phase AC, take length × current × resistance per metre and double it, because the current travels out and back. A three-phase circuit instead takes ΔV = √3 × length × current × (R·cos φ + X·sin φ). A 25 m run of 6 mm² copper at 70 °C (3.68 mΩ/m) carrying 32 A loses 2 × 25 × 32 × 0.00368 = 5.9 V, which is 2.6% of 230 V.
What voltage drop limit should I design to?
IEC 60364-5-52 sets 3% as the recommended ceiling for lighting and 5% for everything else, measured from where a public low-voltage supply enters the installation. The US NEC advises 3% for a branch circuit and 5% for feeder plus branch together. Solar designers go tighter, 1–2% on DC wiring and 1% from inverter to grid connection point, as every percent lost is energy not sold.
Which conductor should feed a 32 A EV charger?
Heat limits would permit 4–6 mm² copper for 32 A under most installation methods, but the drop over distance tends to be the deciding factor. With 4 mm², the drop stays under 3% for runs of up to about 20 m. Go to 6 mm² between roughly 20 and 29 m, and to 10 mm² for lengths up to about 49 m. Your local code and the breaker rating fix the lowest permitted size.
How thick must cables be on a 12 V system?
Because power at low voltage means large current, the wire has to be heavy. 1 kW at 12 V pulls 83 A. To keep the loss under 3% across 4 m one way, you would need around 50 mm² of copper. Run the load at 48 V and the current falls to 21 A, so 4 mm² is enough. That explains why larger off-grid installations choose 24 V or 48 V.
How do metric cable sizes map to AWG?
Using the next larger AWG: 1.5 mm² ≈ 14 AWG, 2.5 mm² ≈ 12 AWG, 4 mm² ≈ 10 AWG, 6 mm² ≈ 8 AWG, 10 mm² ≈ 6 AWG, 16 mm² ≈ 4 AWG, 25 mm² ≈ 3 AWG, 35 mm² ≈ 1 AWG, 50 mm² ≈ 1/0, 70 mm² ≈ 3/0, 95 mm² ≈ 4/0. The two systems do not line up exactly, so go up to the next size, never down.
Does aluminium work as well as copper for cables?
Per unit of cross-section it conducts only about 61% as well, so matching copper's voltage drop takes roughly 1.6 times the area, commonly one or two standard sizes bigger. At an equal size it carries about 78% of copper's current. Its low weight and price make it the usual choice for large feeders and utility lines, but it requires suitable terminals and is generally avoided below 16 mm².

Sources & references

  1. IEC 60364-5-52: Low-voltage electrical installations: Selection and erection of wiring systems (current-carrying capacity, voltage drop)
  2. IEC 60228: Conductors of insulated cables (DC resistance values)
  3. NFPA 70 National Electrical Code: Article 310 (conductor ampacity) and informational notes on voltage drop
  4. IEC 62548-1: PV arrays design requirements (DC cable sizing)