Results

A capacity factor of 32% lies inside the usual 20–45% for Onshore wind. It is the same as running at full power for 2,800 of 8,760 hours.
Capacity factor
32%
0.32 as a fraction
Full-load hours
2,800h
in the 8,760-hour period
Average power
15.98MW
vs 50 MW nameplate
Energy
140GWh
Capacity
50MW
Typical for Onshore wind
20–45%
Specific yield
2,800kWh/kW·yr
yearly energy per kW, annualised
Your capacity factor next to typical values

Usual capacity factors for each technology

TechnologyTypical rangeFull-load hours/yrWhy
Nuclear80–93%7,008–8,147baseload plant, shut for refuelling every 18–24 months
Geothermal70–90%6,132–7,884constant heat source
Biomass / biogas50–85%4,380–7,446fuel-limited, dispatchable
Gas combined cycle45–65%3,942–5,694runs according to price; mid-merit
Coal35–65%3,066–5,694declining use in many grids
Offshore wind38–55%3,329–4,818winds at sea are stronger and steadier
Hydropower30–60%2,628–5,256depends on water supply, dispatch and storage
Onshore wind ◀20–45%1,752–3,942local wind resource and the turbine's specific power
Concentrating solar power with storage30–55%2,628–4,818storage hours extend output
Utility-scale PV with tracking20–32%1,752–2,803trackers follow the sun
Utility solar PV, fixed12–25%1,051–2,190night & clouds; latitude
Rooftop solar PV9–20%788–1,752sub-optimal tilt, shade and heat
Gas / oil peaker2–15%175–1,314runs only at demand peaks
Battery storage (discharge)8–20%701–1,752daily cycles × duration
  • These ranges are drawn from US fleet statistics (EIA Electric Power Monthly, Table 6.07) and global averages for new plants (IRENA). Individual stations and years can differ widely.
  • Capacity factor and efficiency are different things. A solar capacity factor of 25% reflects night and weather rather than lost energy, while for dispatchable plants it shows how often the grid asks them to run.
  • When comparing solar with other technologies, base it on AC nameplate capacity; figures on a DC basis appear lower.