In London, UK you can expect roughly 1,844 heating degree days per year (base 15.5 °C) alongside 21 cooling degree days (base 22 °C). For a building that loses 180 W per kelvin, that means about 7,968 kWh of annual heat demand and a cold-day peak of up to 4.6 kW.
Heating degree days
1,844K·day/yr
base 15.5 °C · 3,320 °F·day
Cooling degree days
21K·day/yr
base 22 °C
Annual heat demand
7,968kWh
66 kWh/m²
Peak heating load (design day)
4.6kW
at -4.8 °C outside, 21 °C inside
Fuel or electricity used for heating
8,853kWh
Heating cost per year
€885
Heat loss coefficient
180W/K
4.32 kWh per degree day
Mean annual temperature
11.4°C
climate normals
Month by month
| Month | Mean °C | HDD | CDD | Heat kWh | Cost (€) |
|---|---|---|---|---|---|
| Jan | 5.2 | 319 | 0 | 1,379 | 153 |
| Feb | 5.3 | 286 | 0 | 1,234 | 137 |
| Mar | 7.6 | 245 | 0 | 1,059 | 118 |
| Apr | 9.9 | 170 | 0 | 734 | 82 |
| May | 13.3 | 85 | 0 | 368 | 41 |
| Jun | 16.5 | 28 | 2 | 122 | 14 |
| Jul | 18.7 | 10 | 9 | 43 | 5 |
| Aug | 18.5 | 11 | 8 | 49 | 5 |
| Sep | 15.7 | 38 | 1 | 164 | 18 |
| Oct | 12 | 116 | 0 | 503 | 56 |
| Nov | 8 | 225 | 0 | 973 | 108 |
| Dec | 5.5 | 310 | 0 | 1,339 | 149 |
- Each month's mean temperature is spread statistically into daily values to estimate degree days, in the manner of CIBSE TM41 / Hitchin. If you used actual daily records from one year, results could be 5–15% higher or lower.
- The base temperature is the outdoor temperature above which a building needs no heating, since sun, occupants and appliances make up for the losses. Well-insulated buildings have lower bases, so their heat demand drops faster than U-values alone would suggest.
- Selecting “My location” loads NASA POWER satellite climate data, so any spot on the map can be analysed.