Heating & gas calculator

Degree days: estimate heating and cooling demand anywhere

Choose a city or any point on Earth and receive heating and cooling degree days by month from NASA satellite data. They are converted into building heat demand, peak load, fuel use and cost, with base temperatures set by you in °C.

Editable share link Branded PDF report Free · no sign-up

Results

In London, UK you can expect roughly 1,844 heating degree days per year (base 15.5 °C) alongside 21 cooling degree days (base 22 °C). For a building that loses 180 W per kelvin, that means about 7,968 kWh of annual heat demand and a cold-day peak of up to 4.6 kW.
Heating degree days
1,844K·day/yr
base 15.5 °C · 3,320 °F·day
Cooling degree days
21K·day/yr
base 22 °C
Annual heat demand
7,968kWh
66 kWh/m²
Peak heating load (design day)
4.6kW
at -4.8 °C outside, 21 °C inside
Fuel or electricity used for heating
8,853kWh
Heating cost per year
€885
Heat loss coefficient
180W/K
4.32 kWh per degree day
Mean annual temperature
11.4°C
climate normals
Degree days by month, London, UK
Heat demand by month (kWh)

Month by month

MonthMean °CHDDCDDHeat kWhCost (€)
Jan5.231901,379153
Feb5.328601,234137
Mar7.624501,059118
Apr9.9170073482
May13.385036841
Jun16.528212214
Jul18.7109435
Aug18.5118495
Sep15.738116418
Oct12116050356
Nov82250973108
Dec5.531001,339149
  • Each month's mean temperature is spread statistically into daily values to estimate degree days, in the manner of CIBSE TM41 / Hitchin. If you used actual daily records from one year, results could be 5–15% higher or lower.
  • The base temperature is the outdoor temperature above which a building needs no heating, since sun, occupants and appliances make up for the losses. Well-insulated buildings have lower bases, so their heat demand drops faster than U-values alone would suggest.
  • Selecting “My location” loads NASA POWER satellite climate data, so any spot on the map can be analysed.

What this tool does

A building loses heat in proportion to the indoor-outdoor temperature gap and to how long it lasts. Degree days turn that into one number per climate. Multiply by the building’s loss per degree and you have yearly demand.

Weather data is either 1991–2020 monthly normals (listed cities) or NASA POWER satellite climatology (any map point). A monthly mean smooths over cold snaps, so the tool scatters daily temperatures around it with a normal distribution (σ = 3.5 K), much as the Hitchin method in CIBSE TM41 does. Even a month averaging 10 °C then scores on its chilly days against a 10 °C base.

For the house, enter floor area and an insulation level, or paste a heat loss coefficient from a certificate or survey. The tool returns monthly and annual demand, the cold-day peak, fuel and cost.

Formulas

HDD (month) = Σ days max(0, base − daily mean temperature) CDD (month) = Σ days max(0, daily mean − cooling base)

H (W/K) = floor area × specific loss (3.0 uninsulated … 0.25 passive house W/m²K) Heat demand (kWh) = H × HDD × 24 ÷ 1000 Peak load (kW) = H × (indoor − design temperature) ÷ 1000 Design temperature = coldest monthly mean − 10 °C

Fuel = heat demand ÷ efficiency; Cost = fuel × price

Default example

Take the defaults: a 120 m² home in London with average insulation (1.5 W/m²K), so H = 180 W/K; bases 15.5 °C for heating and 22 °C for cooling; gas boiler 90% efficient, gas €0.10/kWh.

  • Climate: January averages 5.2 °C, July 18.7 °C, the year 11.4 °C. That yields about 1,844 HDD (3,320 °F·days) and only 21 CDD.
  • Per degree day: 180 × 24 ÷ 1000 = 4.32 kWh.
  • Per year: 4.32 × 1,844 ≈ 7,970 kWh, or 66 kWh per m².
  • Design temperature 5.2 − 10 = −4.8 °C, so peak = 180 × (21 + 4.8) ÷ 1000 ≈ 4.6 kW.
  • Gas: 7,970 ÷ 0.90 ≈ 8,850 kWh, costing roughly €885 a year.

Monthly, January takes about 1,380 kWh and July about 43 kWh.

Results explained

  • Degree days grade how severe the winter is for your base; only compare cities that use the same one.
  • Annual demand counts heat delivered into rooms, ahead of boiler or heat pump losses.
  • Peak load is the cold-day output for sizing a boiler or heat pump. More than that costs extra and makes heat pumps cycle.
  • kWh per degree day characterises the building itself, so you can follow bills over several years.

Benchmarks

Approximate yearly figures, heating base 15.5 °C and cooling base 22 °C:

  • Madrid: HDD 1,200–1,500; CDD 250–400.
  • London: HDD 1,800–2,000; CDD under 50.
  • Berlin: HDD 2,300–2,500; CDD under 50.
  • Chicago: HDD 2,700–3,100; CDD 150–250.
  • Stockholm: HDD 3,000–3,300; CDD under 30.
  • Kuala Lumpur: HDD 0; CDD over 2,000.

Specific heat loss per m² of floor, by insulation level:

  • Passive house: 0.25 W/m²K.
  • Good, post-2000 code: 1.0 W/m²K.
  • Some upgrades, average: 1.5 W/m²K.
  • Uninsulated, pre-1950: 3.0 W/m²K.

Using it well

  • A tight home full of appliances may need no heat above 12–14 °C outdoors, so a 15.5 °C base would overstate it.
  • Test the model: last winter’s heating energy divided by that period’s degree days should resemble the tool’s kWh per degree day.
  • Choose equipment by the peak figure. Running costs can then be checked with the heat pump calculator or the heating cost comparison.
  • Raise the insulation level and watch demand and peak drop; for the cost of the work, go to insulation savings.

Accuracy

Monthly-mean estimates typically land within 5–15% of daily-record values, and one year can differ from the normal by a similar margin. The model leaves out thermal mass, ventilation habits and any solar gain beyond what the base temperature implies. Cooling is sensible heat only, with no solar, internal gains or humidity, so actual air-conditioning loads run higher. NASA’s grid is about 50 km, which can miss cities, valleys and coasts.

Method & assumptions

To get a month's HDD, add up max(0, base − daily mean) for every day. Only the monthly mean is known, so daily means are modelled as normally distributed (σ = 3.5 K). Yearly demand = H × HDD × 24 ÷ 1000, where H (W/K) is the building's heat loss coefficient: floor area × specific loss by insulation level (3.0 W/m²K uninsulated … 0.25 passive house). Peak load = H × (indoor − design temperature), with the design temperature set at the coldest monthly mean − 10 °C. Fuel = heat ÷ efficiency.

Frequently asked questions

What is a heating degree day?
It is a daily score for cold: the number of degrees by which the day's average temperature sits below a chosen base. Against 15.5 °C, a day averaging 5 °C scores 10.5. A year's total follows the heat a building needs, so it lets you set one winter or one property against another.
Which base temperature is right?
Standard practice differs by region: 15.5 °C in Britain and most of Europe, 65 °F (18.3 °C) in the US. Your own building has a truer base, the outdoor reading at which the heating can be switched off. Tight, well-insulated homes with heat from people and appliances come in at 12–14 °C, while old leaky ones or warm thermostat settings push it up.
How do degree days become kWh of heat?
Multiply W/K of heat loss by the degree days and by 24, then divide by 1,000. For 180 W/K and 1,844 degree days that is 180 × 1,844 × 24 ÷ 1,000 ≈ 7,970 kWh of heat each year.
London: how many HDD per year?
Somewhere between 1,800 and 2,000 at a 15.5 °C base, depending on the period. This tool, using 1991–2020 normals, returns about 1,840. Same base elsewhere: Berlin roughly 2,400, Stockholm above 3,000.
Why do cooling degree days matter?
CDD is the warm-weather twin, counting degrees above a cooling base such as 18.3 °C or 22 °C, and it points to air-conditioning demand. In humid Kuala Lumpur the 22 °C total tops 2,000, while winter-style heating scores almost nothing.
Mild winter versus cold winter: how do I compare my bills?
Divide the kWh you burned by the degree days of the same months. That ratio ignores the weather, so a lower value after insulation work is a saving you can trust.

Sources & references

  1. CIBSE TM41: Degree-days, theory and application
  2. Degree Days.net: Degree days, handle with care
  3. NASA POWER: Prediction of Worldwide Energy Resources (climate data)

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.