Results

Suggested size: 125 kVA, standby-rated duty (100 kW at PF 0.8). Running load calls for 85 kVA with margin. Starting the 15 kW motor pulls about 125 kVA and gives a 13% voltage dip on this generator, so engine load during the start sets the size.
Recommended generator
125kVA
100 kW at PF 0.8, standby
Running load
71kVA
60 kW at PF 0.85
Needed for the running load
85kVA
includes margin, non-linear loads and duty
Motor starting kVA
125kVA
6.5 × 19.2 kVA running
Needed to limit the voltage dip
75kVA
dip limit 20%
Voltage dip on this set
13%
Engine loading while starting
89kW
needs at least 101 kVA
Running load on the set
56%
Diesel burnt at running load
23L/h
Voltage dip at motor start for each generator size
What sets the size (kVA)

Ways of starting this motor

MethodStarting currentStarting kVAGenerator size to stay within the dip limit (kVA)
Direct-on-line (DOL)6.5 × FLC125100
Star-delta2.2 × FLC42100
Soft starter3.5 × FLC67100
Variable-speed drive (VFD)1.2 × FLC23100
  • Use this as a screening check only. The voltage-dip formula is built on the alternator subtransient reactance and takes no account of the voltage regulator's response or engine speed dip. Verify with the manufacturer's sizing software (motor starting curves, transient response class from ISO 8528-5).
  • When several motors might start together, enter their combined kW as the largest motor. Staggering the starts, or using soft starters or drives, often lets you pick a much smaller generator.

Free calculator by Energy.com.info