Power factor 0.8 on 100 kVA means 80 kW. Install a 33.7 kVAr capacitor bank and the power factor climbs to 0.95; current falls from 144 A to 122 A, cable losses shrink by 29% and 15.8 kVA of capacity is freed.
Real power
80kW
power factor 0.8
Apparent power
100kVA
Reactive power
60kVAr
Line current (per phase)
144.3A
I = S ÷ (√3 × 400 V)
Phase angle φ
36.9°
Power in horsepower
107.3hp
Capacitor bank for PF 0.95
33.7kVAr
Current after correction
121.5A
−16% current
kVA after correction
84.21kVA
The same apparent power at different power factors
| Power factor | kW | kVAr | Current (A) |
|---|---|---|---|
| 1 | 100 | 0 | 144.3 |
| 0.95 | 95 | 31.22 | 144.3 |
| 0.9 | 90 | 43.59 | 144.3 |
| 0.85 | 85 | 52.68 | 144.3 |
| 0.8 | 80 | 60 | 144.3 |
| 0.75 | 75 | 66.14 | 144.3 |
| 0.7 | 70 | 71.41 | 144.3 |
Common generator and transformer sizes at PF 0.8
| kVA | kW | Amps @ 400 V 3-ph |
|---|---|---|
| 10 | 8 | 14 |
| 20 | 16 | 29 |
| 30 | 24 | 43 |
| 50 | 40 | 72 |
| 63 | 50 | 91 |
| 100 | 80 | 144 |
| 160 | 128 | 231 |
| 250 | 200 | 361 |
| 400 | 320 | 577 |
| 630 | 504 | 909 |
| 1,000 | 800 | 1,443 |
| 1,600 | 1,280 | 2,309 |
| 2,500 | 2,000 | 3,608 |
- Cables, transformers and generators must be sized for kVA. Only the kW part does useful work, and the ratio of kW to kVA is the power factor.
- Generator ratings are normally given in kVA at 0.8 PF, which means a 100 kVA genset can supply no more than 80 kW of real power.
- The capacitor sizing presumes a sinusoidal supply. If you have lots of drives or inverters producing harmonics, go for detuned banks or active filters, and get an engineer to rule out resonance.