Results

Power factor 0.8 on 100 kVA means 80 kW. Install a 33.7 kVAr capacitor bank and the power factor climbs to 0.95; current falls from 144 A to 122 A, cable losses shrink by 29% and 15.8 kVA of capacity is freed.
Real power
80kW
power factor 0.8
Apparent power
100kVA
Reactive power
60kVAr
Line current (per phase)
144.3A
I = S ÷ (√3 × 400 V)
Phase angle φ
36.9°
Power in horsepower
107.3hp
Capacitor bank for PF 0.95
33.7kVAr
Current after correction
121.5A
−16% current
kVA after correction
84.21kVA
Power triangle (before and after correction)
Current against power factor (kW unchanged)

The same apparent power at different power factors

Power factorkWkVArCurrent (A)
11000144.3
0.959531.22144.3
0.99043.59144.3
0.858552.68144.3
0.88060144.3
0.757566.14144.3
0.77071.41144.3

Common generator and transformer sizes at PF 0.8

kVAkWAmps @ 400 V 3-ph
10814
201629
302443
504072
635091
10080144
160128231
250200361
400320577
630504909
1,0008001,443
1,6001,2802,309
2,5002,0003,608
  • Cables, transformers and generators must be sized for kVA. Only the kW part does useful work, and the ratio of kW to kVA is the power factor.
  • Generator ratings are normally given in kVA at 0.8 PF, which means a 100 kVA genset can supply no more than 80 kW of real power.
  • The capacitor sizing presumes a sinusoidal supply. If you have lots of drives or inverters producing harmonics, go for detuned banks or active filters, and get an engineer to rule out resonance.

Free calculator by Energy.com.info