Convert kVA to kW and back, with power factor, kVAr and amps

Switch between kVA (apparent), kW (real) and kVAr (reactive power) and read the current for single- or three-phase systems. You also get the power triangle and the capacitor bank sized to fix a poor power factor.

Editable share link Branded PDF report Free · no sign-up

Results

Power factor 0.8 on 100 kVA means 80 kW. Install a 33.7 kVAr capacitor bank and the power factor climbs to 0.95; current falls from 144 A to 122 A, cable losses shrink by 29% and 15.8 kVA of capacity is freed.
Real power
80kW
power factor 0.8
Apparent power
100kVA
Reactive power
60kVAr
Line current (per phase)
144.3A
I = S ÷ (√3 × 400 V)
Phase angle φ
36.9°
Power in horsepower
107.3hp
Capacitor bank for PF 0.95
33.7kVAr
Current after correction
121.5A
−16% current
kVA after correction
84.21kVA
Power triangle (before and after correction)
Current against power factor (kW unchanged)

The same apparent power at different power factors

Power factorkWkVArCurrent (A)
11000144.3
0.959531.22144.3
0.99043.59144.3
0.858552.68144.3
0.88060144.3
0.757566.14144.3
0.77071.41144.3

Common generator and transformer sizes at PF 0.8

kVAkWAmps @ 400 V 3-ph
10814
201629
302443
504072
635091
10080144
160128231
250200361
400320577
630504909
1,0008001,443
1,6001,2802,309
2,5002,0003,608
  • Cables, transformers and generators must be sized for kVA. Only the kW part does useful work, and the ratio of kW to kVA is the power factor.
  • Generator ratings are normally given in kVA at 0.8 PF, which means a 100 kVA genset can supply no more than 80 kW of real power.
  • The capacitor sizing presumes a sinusoidal supply. If you have lots of drives or inverters producing harmonics, go for detuned banks or active filters, and get an engineer to rule out resonance.

Real, reactive and apparent power

An AC circuit carries two kinds of power. Real (active) power, in kW, is the part that does work, such as heat, light or motion. Reactive power, in kVAr, flows back and forth to magnetise motors and transformers and delivers no net work. Combine the two as vectors and you get apparent power, in kVA, which sets the current that cables, switchgear, transformers and generators have to carry. Divide kW by kVA to get the power factor (cos φ).

Type in the quantity you know (kVA, kW or current) plus the power factor, the system type (single-phase, three-phase or DC) and the voltage. You get the rest back, a drawn power triangle, a view of current climbing as power factor drops, and the size of capacitor bank that corrects the power factor to your target.

Formulas

kW = kVA × PF kVA = kW ÷ PF kVAr = kVA × sin φ = √(kVA² − kW²) Three-phase: I = kVA × 1,000 ÷ (√3 × V_LL) Single-phase: I = kVA × 1,000 ÷ V Correction: Qc = kW × (tan φ₁ − tan φ₂), φ = arccos(PF)

Example: sizing up a 100 kVA generator

The preset is a three-phase generator of 100 kVA at 400 V, with the usual rating power factor of 0.8:

  • Real power is 100 × 0.8 = 80 kW.
  • Reactive power is 100 × sin(36.9°) = 60 kVAr.
  • Current is 100,000 ÷ (1.732 × 400) = 144 A per phase.

Suppose the site’s load really sat at PF 0.8. A 33.7 kVAr capacitor bank would raise it to 0.95, and the same 80 kW would need only 84.2 kVA and 122 A. Current falls 16%, cable losses about 29% (they follow current squared), and 16 kVA of generator or transformer capacity is freed.

Interpreting the charts

  • Power triangle: kW along the base, kVAr up the side, kVA as the sloping edge. The dashed line is the corrected kVA, with kW unchanged and a shorter hypotenuse.
  • Current versus power factor: for the same useful power, current climbs sharply below PF 0.8, and that is what utilities penalise.
  • Standard sizes table: kW and amps for common generator and transformer ratings at PF 0.8 and your voltage.

Typical power factors

  • 1.00: resistive heaters, kettles, incandescent lamps.
  • 0.95–1.00: EV chargers, modern power supplies with PFC, PV inverters.
  • 0.90–0.98: LED lighting with quality drivers.
  • Induction motors: 0.80–0.90 at full load, 0.65–0.80 at half load, 0.20–0.40 with no load.
  • 0.50–0.70: welding transformers and arc furnaces.
  • 0.70–0.85: a typical industrial site before correction.

Current at common ratings (three-phase)

Each line gives kVA, then kW at PF 0.8, then amps at 400 V, 480 V and 208 V:

  • 20 kVA: 16 kW; 29 A, 24 A, 56 A.
  • 50 kVA: 40 kW; 72 A, 60 A, 139 A.
  • 100 kVA: 80 kW; 144 A, 120 A, 278 A.
  • 250 kVA: 200 kW; 361 A, 301 A, 694 A.
  • 500 kVA: 400 kW; 722 A, 601 A, 1,388 A.
  • 1,000 kVA: 800 kW; 1,443 A, 1,203 A, 2,776 A.

Practical points

  1. Size generators for kVA and for starting current. A motor can pull 3–7 times its running current at start; soft starters and VFDs cut that.
  2. Correct at the source. Capacitors on large motors reduce current throughout the distribution system, not only at the main board.
  3. Avoid over-correction. At light load a leading power factor can raise voltage; automatic stepped banks prevent this.
  4. Look at harmonics. Variable-speed drives distort current, and plain capacitors may resonate with the network, so use detuned reactors.
  5. For balanced three-phase loads with star/delta detail, go to the three-phase power calculator.

Limits of the calculation

It assumes sinusoidal voltage and current and a balanced three-phase load. Non-linear loads bring harmonic distortion into the “true power factor”, and capacitors do not cure that. Breaker, cable and capacitor sizing must follow local wiring rules and manufacturer data.

Method & assumptions

The power triangle gives S² = P² + Q², with P = S · cos φ and Q = S · sin φ. Line current: I = S ÷ V for single-phase and I = S ÷ (√3 · VLL) for three-phase. A capacitor for correction supplies Qc = P · (tan φ1 − tan φ2). Since cable losses grow with I², lifting the power factor from 0.8 to 0.95 trims them by roughly 29%.

Frequently asked questions

What is the formula to turn kVA into kW?
Multiply by the power factor: kW = kVA × PF. A generator rated at the standard PF of 0.8 gives 80 kW from 100 kVA, while at PF 0.95 the same 100 kVA gives 95 kW. The two units match only when PF is 1, meaning a purely resistive load.
How do I get from kW to kVA?
Divide kW by the power factor: kVA = kW ÷ PF. Take a 7.5 kW motor at PF 0.82: it draws 9.15 kVA, and the cables and supply must be sized for that apparent power.
What current does 100 kVA draw?
For three phase, I = 100,000 ÷ (√3 × V). That means 144 A per phase at 400 V, 139 A at 415 V, 120 A at 480 V and 278 A at 208 V. On a single-phase 230 V supply it is 435 A.
Why do generator labels show kVA and not kW?
Winding heat in the alternator follows current, and current follows apparent power whatever the load's power factor. So makers rate generators in kVA and quote kW at an assumed PF of 0.8, with the engine sized to deliver that kW.
What power factor counts as good?
Anything over 0.95. Utilities often penalise reactive energy when a commercial or industrial customer drops under 0.9–0.95, which explains the capacitor banks at sites full of motors.
How do I size a power factor correction capacitor?
Use Qc = kW × (tan φ1 − tan φ2). Raising an 80 kW load from PF 0.80 to 0.95 takes 80 × (0.750 − 0.329) ≈ 33.7 kVAr. Where many drives or inverters run, choose detuned banks.

Sources & references

  1. IEC 60050-131 / IEV — International Electrotechnical Vocabulary: apparent, active and reactive power
  2. Schneider Electric — Electrical Installation Guide, chapter L: Power factor correction
  3. US DOE — Reducing power factor cost (Motor Systems Tip Sheet)