Results

After the upgrade, yearly consumption drops from 182,566 to 85,454 kWh (53% lower). That saves about 14,567 € and 44.5 t CO₂ annually, repays the investment in 0.7 years and returns around 209,001 € across a motor life of 15 years.
Annual saving
€14,567
97,111 kWh per year
Simple payback
0.7years
Existing motor efficiency
91.2%
IE1 at 37 kW
New motor efficiency
95.2%
IE4 at 37 kW
Electrical input now
30.4kW
Electrical input after
14.2kW
Saving from the motor swap only
€1,151
7,671 kWh
Saving from the drive
€13,416
89,441 kWh
CO₂ avoided per year
44.5t
Running cost now
€27,385
every year returns 2.9× the upgrade cost
Electricity consumed per year (kWh)
Lowest allowed efficiency per class (4-pole, 50 Hz)

Efficiency classes for a 37 kW motor

ClassEfficiencyInput power (kW)kWh/yrCost (€/yr)
IE191.2%30.43182,56627,385
IE292.7%29.94179,61226,942
IE393.9%29.55177,31626,597
IE495.2%29.15174,89526,234
IE596.2%28.86173,14925,972
  • IE1–IE4 figures are the IEC 60034-30-1 limits for 4-pole, 50 Hz motors (interpolated); IE5 is assumed to have 20% lower losses than IE4. Many real motors beat the minimum, and efficiency also drops below roughly 50% load.
  • The calculation treats the flow as throttled today by a valve or damper (shaft power ≈ 55% + 45% × flow). A drive removes that loss following the affinity laws, with 3% lost in the drive itself. If static head is large, the gain is smaller.

Free calculator by Energy.com.info