After the upgrade, yearly consumption drops from 182,566 to 85,454 kWh (53% lower). That saves about 14,567 € and 44.5 t CO₂ annually, repays the investment in 0.7 years and returns around 209,001 € across a motor life of 15 years.
Annual saving
€14,567
97,111 kWh per year
Simple payback
0.7years
Existing motor efficiency
91.2%
IE1 at 37 kW
New motor efficiency
95.2%
IE4 at 37 kW
Electrical input now
30.4kW
Electrical input after
14.2kW
Saving from the motor swap only
€1,151
7,671 kWh
Saving from the drive
€13,416
89,441 kWh
CO₂ avoided per year
44.5t
Running cost now
€27,385
every year returns 2.9× the upgrade cost
Efficiency classes for a 37 kW motor
| Class | Efficiency | Input power (kW) | kWh/yr | Cost (€/yr) |
|---|---|---|---|---|
| IE1 | 91.2% | 30.43 | 182,566 | 27,385 |
| IE2 | 92.7% | 29.94 | 179,612 | 26,942 |
| IE3 | 93.9% | 29.55 | 177,316 | 26,597 |
| IE4 | 95.2% | 29.15 | 174,895 | 26,234 |
| IE5 | 96.2% | 28.86 | 173,149 | 25,972 |
- IE1–IE4 figures are the IEC 60034-30-1 limits for 4-pole, 50 Hz motors (interpolated); IE5 is assumed to have 20% lower losses than IE4. Many real motors beat the minimum, and efficiency also drops below roughly 50% load.
- The calculation treats the flow as throttled today by a valve or damper (shaft power ≈ 55% + 45% × flow). A drive removes that loss following the affinity laws, with 3% lost in the drive itself. If static head is large, the gain is smaller.