Industry & business calculator

Savings from premium efficiency electric motors and VFDs

How much would a better motor save? Weigh your present motor against an IE3, IE4 or IE5 unit under the IEC 60034-30-1 classes, optionally with a variable-speed drive on a pump or fan (affinity laws), and get the kWh, money and CO₂ saved plus payback.

Editable share link Branded PDF report Free · no sign-up

Results

After the upgrade, yearly consumption drops from 182,566 to 85,454 kWh (53% lower). That saves about 14,567 € and 44.5 t CO₂ annually, repays the investment in 0.7 years and returns around 209,001 € across a motor life of 15 years.
Annual saving
€14,567
97,111 kWh per year
Simple payback
0.7years
Existing motor efficiency
91.2%
IE1 at 37 kW
New motor efficiency
95.2%
IE4 at 37 kW
Electrical input now
30.4kW
Electrical input after
14.2kW
Saving from the motor swap only
€1,151
7,671 kWh
Saving from the drive
€13,416
89,441 kWh
CO₂ avoided per year
44.5t
Running cost now
€27,385
every year returns 2.9× the upgrade cost
Electricity consumed per year (kWh)
Lowest allowed efficiency per class (4-pole, 50 Hz)

Efficiency classes for a 37 kW motor

ClassEfficiencyInput power (kW)kWh/yrCost (€/yr)
IE191.2%30.43182,56627,385
IE292.7%29.94179,61226,942
IE393.9%29.55177,31626,597
IE495.2%29.15174,89526,234
IE596.2%28.86173,14925,972
  • IE1–IE4 figures are the IEC 60034-30-1 limits for 4-pole, 50 Hz motors (interpolated); IE5 is assumed to have 20% lower losses than IE4. Many real motors beat the minimum, and efficiency also drops below roughly 50% load.
  • The calculation treats the flow as throttled today by a valve or damper (shaft power ≈ 55% + 45% × flow). A drive removes that loss following the affinity laws, with 3% lost in the drive itself. If static head is large, the gain is smaller.

Where the electricity goes

Around 70% of industrial electricity, and about half of all electricity worldwide, ends up in motors. In some sectors the IEA’s motor systems work suggests the share is higher still. A motor on two shifts may use three or four times its purchase price in energy per year. A few points of efficiency, or better control of flow, therefore often repay faster than any other plant upgrade.

You give the tool two motors, the one installed and a better candidate, and it assigns each the minimum efficiency of its IEC 60034-30-1 class. If a valve or damper currently chokes the flow of a fan or pump, a speed drive can be added to the comparison too. Results show yearly kWh, cost and CO₂ per step, and how soon the total spend returns.

How it is calculated

Shaft power P_shaft = rated kW × load Electrical input P_in = P_shaft ÷ η_motor

With a drive (fans, pumps): throttled shaft power ≈ P_design × (0.55 + 0.45 × Q) speed-controlled ≈ P_design × Q^n ÷ η_drive n = 2–3, η_drive = 0.97

Annual kWh = P_in × hours Saving = (kWh_old − kWh_new) × price Payback = installed cost ÷ annual saving

Class efficiencies come from interpolating the IEC 60034-30-1 values (4-pole, 50 Hz) at your rated power, and losses for IE5 are set 20% under those of IE4. A basic curve models valve or damper throttling; outlet dampers and bypass control deviate from it slightly.

Worked case: pump motor and drive

In the preset, an aging IE1 37 kW pump motor (75% load, 6,000 hours a year) gives way to an IE4 motor plus a drive. The pump seldom needs more than 70% of design flow.

Step Calculation Result
Today shaft 27.75 kW ÷ 0.912 30.4 kW drawn, 182,600 kWh a year, about 27,400 at 0.15/kWh
IE4 motor alone 27.75 ÷ 0.952 29.1 kW, saving about 7,700 kWh (1,150) a year
Add the drive design-point shaft 27.75 ÷ 0.865 = 32.1 kW; at 70% flow and exponent 2.5, 32.1 × 0.41 13.2 kW shaft, 14.2 kW at the meter
Outcome whole year 85,500 kWh, 53% lower, worth about 14,600 a year and 44 t of CO₂ at the world average grid intensity; the 9,500 outlay is back in roughly 8 months

A few percent from the motor, tens of percent from fitting speed to the actual load: that split is common. Load the IE2 → IE3 preset for a conveyor at 4,000 hours with the drive off and payback exceeds 12 years, so that motor should simply be replaced when it fails.

Minimum efficiency by class (4-pole, 50 Hz)

IE4 IE3 IE2 IE1 Rated power
87.2% 84.1% 81.4% 75.0% 1.1 kW
91.1% 88.6% 86.6% 83.1% 4 kW
93.3% 91.4% 89.8% 87.6% 11 kW
95.2% 93.9% 92.7% 91.2% 37 kW
96.1% 95.2% 94.2% 93.0% 90 kW
96.7% 96.0% 95.1% 94.0% 200 kW and above

Motors built for 60 Hz in North America (NEMA Premium ≈ IE3) show somewhat higher values at equal power.

Practical steps

  • Look at the duty before the motor. Throttled pumps and fans, oversized motors idling at 30–40% load, and equipment running with nothing to do waste more than the motor’s internal losses.
  • Replace rather than rewind small and mid-size motors in heavy service. The premium of an IE3/IE4 unit over a rewind normally repays quickly.
  • Check power factor. Part-loaded motors perform poorly on it; try the power factor correction calculator.
  • Hunt compressed-air leaks. Compressed air frequently ranks as the priciest utility a motor can drive. Price your leaks with the compressed air leak calculator.

Limitations

Limit What it means
Class minimums, full load Many real motors do better; efficiency falls steeply below about 50% load
Drive losses A drive adds 2–4% losses plus harmonics, and saves nothing on constant-torque loads at full speed
Generic throttling model A real drive study needs measured flow and pressure
CO₂ Follows the average grid intensity of the country you select

Method & assumptions

The motor draws shaft power ÷ motor efficiency, with shaft power = rated kW × load, and the efficiency is taken from the IEC 60034-30-1 class limits for its rating (log-interpolated). A drive turns a throttled operating point into a speed-controlled one: P ∝ Qn (affinity laws, n = 2–3), with 97% drive efficiency. ΔkWh × price is the saving, installed cost ÷ annual saving is the payback, and CO₂ follows the chosen grid's average intensity.

Frequently asked questions

What does an IE2-to-IE4 upgrade save in kWh?
Expect a gain of 2–4 percentage points for motors rated 1–100 kW, which means 25–40% less waste heat. One example: a 37 kW unit working at 75% load for 6,000 hours a year goes from 92.7% (IE2) to 95.2% (IE4) and avoids about 4,700 kWh annually.
Which efficiency classes exist for electric motors?
IEC 60034-30-1 ranks line-operated motors from IE1 (standard) through IE2 (high) and IE3 (premium) up to IE4 (super premium). Above that, IEC TS 60034-30-2 defines IE5 (ultra premium), whose losses run about 20% below IE4. In the EU, IE3 has been mandatory for most 0.75–1,000 kW motors since July 2021, and IE4 for 75–200 kW motors since July 2023.
What savings do speed drives bring to pumps and fans?
Often 20–50%. Slowing a centrifugal machine cuts its power roughly by the cube of the speed ratio (the affinity laws), so 80% speed draws about half. Systems that now throttle flow with a valve or damper gain most; those with high static head gain least.
Should a healthy old motor be replaced early?
When it runs above about 4,000 hours a year, retiring an IE1 or an old rewound motor commonly pays back in 2–5 years. For a lightly used motor, wait for the failure and buy an IE3 or IE4 unit instead of rewinding.
Why is a motor's power bill larger than its price tag?
Left running most of the year, a motor pays for its own purchase price in electricity several times over annually. Across a 15–20 year life, energy is well over 90% of the total cost of ownership.
Does rewinding reduce motor efficiency?
It can. A careless rewind that overheats the core may lose 1–2 points, but one done to EASA/AEMT guidelines stays within roughly 0.5 points of the original.

Sources & references

  1. IEC 60034-30-1:2014 — Efficiency classes of line-operated AC motors (IE code)
  2. EU Commission Regulation 2019/1781 — Ecodesign requirements for electric motors and variable speed drives
  3. US DOE — Improving Motor and Drive System Performance: A Sourcebook for Industry
  4. IEA 4E Electric Motor Systems Platform (EMSA)