A load of 3.18 kWh/day calls for about 2.7 kWp of panels (6 × 450 W), a LiFePO₄ (LFP) battery bank of 15.4 kWh at 48 V, and an inverter of 4 kW. The month that sets the design is December; in it, every kWp produces only 1.76 kWh/day.
Solar array
2.7kWp
6 × 450 W panels at 55°
Battery bank
15.4kWh
300 Ah @ 48 V · usable 11.6 kWh
Battery configuration
4S × 3P
12 × 12.8 V 100 Ah units
Inverter
4kW
continuous; surge ≥ 4.4 kW
Charge controller
80 A
MPPT · 70 A needed at 48 V
Daily load
3.18kWh/day
3.81 kWh/day drawn from the battery bus, inverter losses included
Design month
Dec
2.12 kWh/m²/day reaching the panels (sun-hours)
Real autonomy
3days
temperature factor 94%
Months needing backup
0/ 12
none
Summer surplus (unused)
1,666kWh/yr
typical for winter-sized arrays
Battery life
15years
about 68 cycles a year · the pack is rated at 6,000 cycles or a 15 yr calendar life
Rough system cost
€10,937
estimate covering hardware and installation
Energy balance by month (★ = sizing month)
| Month | Sun on panels (kWh/m²/day) | Solar (kWh/day) | Need (kWh/day) | Coverage |
|---|---|---|---|---|
| Jan | 2.45 | 5.51 | 3.94 | 140% |
| Feb | 3.39 | 7.48 | 3.94 | 190% |
| Mar | 4.23 | 9.05 | 3.94 | 230% |
| Apr | 4.83 | 10.03 | 3.94 | 255% |
| May | 5 | 10.14 | 3.94 | 258% |
| Jun | 5.02 | 9.99 | 3.94 | 254% |
| Jul | 5.28 | 10.37 | 3.94 | 264% |
| Aug | 5.45 | 10.7 | 3.94 | 272% |
| Sep | 4.88 | 9.87 | 3.94 | 251% |
| Oct | 4 | 8.4 | 3.94 | 214% |
| Nov | 2.57 | 5.63 | 3.94 | 143% |
| Dec | 2.12 | 4.76 | 3.94 | 121% ★ |
Load list
| Load | Wh/day | Share |
|---|---|---|
| Lighting | 320 | 10% |
| Refrigeration | 800 | 25% |
| TV / entertainment | 240 | 8% |
| Computers | 300 | 9% |
| Always-on devices | 240 | 8% |
| Water pump | 750 | 24% |
| Washing machine | 229 | 7% |
| Other | 300 | 9% |
Component checklist
| Component | Specification |
|---|---|
| PV array | 6 × 450 W = 2.7 kWp, 55° tilt, azimuth 180° |
| Battery bank | 15.4 kWh of LiFePO₄ (LFP): 12 units of 12.8 V 100 Ah, wired 4 in series and 3 in parallel |
| Charge controller | MPPT rated 70 A or more at 48 V (keep the PV string Voc below the controller maximum input voltage) |
| Inverter | 4 kW pure-sine continuous output from a 48 V DC input, with surge capacity of 4.4 kW or more |
| Battery cable & fuse | rated for roughly 81 A continuous |
- Solar resource: NASA POWER monthly climate averages for 44.43, 26.1 (default-site data built in for pre-rendering), panels at 55° tilt and 180° azimuth, with cell temperature and 12% PV losses.
- Energy path: AC loads ÷ 92% inverter efficiency, plus 15 W standby draw, gives the demand on the battery bus. Of that, 60% cycles through the battery at 95% round-trip efficiency, and the controller runs at 97%.
- Autonomy days cover consecutive overcast days. NASA monthly averages hide multi-day storms, so remote critical systems often plan for 3–5 days plus a generator.