Results

A load of 3.18 kWh/day calls for about 2.7 kWp of panels (6 × 450 W), a LiFePO₄ (LFP) battery bank of 15.4 kWh at 48 V, and an inverter of 4 kW. The month that sets the design is December; in it, every kWp produces only 1.76 kWh/day.
Solar array
2.7kWp
6 × 450 W panels at 55°
Battery bank
15.4kWh
300 Ah @ 48 V · usable 11.6 kWh
Battery configuration
4S × 3P
12 × 12.8 V 100 Ah units
Inverter
4kW
continuous; surge ≥ 4.4 kW
Charge controller
80 A
MPPT · 70 A needed at 48 V
Daily load
3.18kWh/day
3.81 kWh/day drawn from the battery bus, inverter losses included
Design month
Dec
2.12 kWh/m²/day reaching the panels (sun-hours)
Real autonomy
3days
temperature factor 94%
Months needing backup
0/ 12
none
Summer surplus (unused)
1,666kWh/yr
typical for winter-sized arrays
Battery life
15years
about 68 cycles a year · the pack is rated at 6,000 cycles or a 15 yr calendar life
Rough system cost
€10,937
estimate covering hardware and installation
Solar yield per day against daily demand, by month
Array size required if sized for each month
Where the energy goes

Energy balance by month (★ = sizing month)

MonthSun on panels (kWh/m²/day)Solar (kWh/day)Need (kWh/day)Coverage
Jan2.455.513.94140%
Feb3.397.483.94190%
Mar4.239.053.94230%
Apr4.8310.033.94255%
May510.143.94258%
Jun5.029.993.94254%
Jul5.2810.373.94264%
Aug5.4510.73.94272%
Sep4.889.873.94251%
Oct48.43.94214%
Nov2.575.633.94143%
Dec2.124.763.94121% ★

Load list

LoadWh/dayShare
Lighting32010%
Refrigeration80025%
TV / entertainment2408%
Computers3009%
Always-on devices2408%
Water pump75024%
Washing machine2297%
Other3009%

Component checklist

ComponentSpecification
PV array6 × 450 W = 2.7 kWp, 55° tilt, azimuth 180°
Battery bank15.4 kWh of LiFePO₄ (LFP): 12 units of 12.8 V 100 Ah, wired 4 in series and 3 in parallel
Charge controllerMPPT rated 70 A or more at 48 V (keep the PV string Voc below the controller maximum input voltage)
Inverter4 kW pure-sine continuous output from a 48 V DC input, with surge capacity of 4.4 kW or more
Battery cable & fuserated for roughly 81 A continuous
  • Solar resource: NASA POWER monthly climate averages for 44.43, 26.1 (default-site data built in for pre-rendering), panels at 55° tilt and 180° azimuth, with cell temperature and 12% PV losses.
  • Energy path: AC loads ÷ 92% inverter efficiency, plus 15 W standby draw, gives the demand on the battery bus. Of that, 60% cycles through the battery at 95% round-trip efficiency, and the controller runs at 97%.
  • Autonomy days cover consecutive overcast days. NASA monthly averages hide multi-day storms, so remote critical systems often plan for 3–5 days plus a generator.