Design around the darkest month
An off-grid plant has nothing to lean on, so it is dimensioned for the harshest stretch rather than the yearly average. This calculator follows the stand-alone method of IEEE 1562 and the Sandia handbook, using climate data for your location.
- Loads. Pick appliances or type a daily total. The tool sums watt-hours per day and estimates both the peak load and the surge of motors (pumps, fridge compressors).
- Energy path. AC demand is divided by inverter efficiency, with 24 hours of idle consumption added on top. Evening and night energy passes through the battery and pays the round-trip loss.
- Sun. Monthly NASA POWER irradiance, temperature and wind for your site are tilted to your panel angle and turned into kWh per kWp per day reaching the battery, after cell-temperature and controller losses.
- Design month. The array follows the darkest month plus a margin. You can instead pick the fourth-darkest (generator covers deep winter) or the darkest summer month (seasonal cabin).
- Battery, inverter, controller. The bank must hold your autonomy days without breaching the chemistry’s depth-of-discharge limit, and must allow for capacity lost at the coldest battery temperature. It is then divided into series and parallel units.
Formulas
Example: all-year cabin by Bucharest
Default loads add up to 3.18 kWh/day: eight LED lamps, a low-consumption fridge, TV, laptop, router, a 750 W water pump for one hour a day, and two laundry cycles weekly. A 92% inverter with 15 W idle raises the battery-bus demand to 3.81 kWh/day. With 60% of it passing through a 95%-efficient LFP battery, the panels must supply 3.94 kWh/day.
At a 55° tilt, December gets 2.12 kWh/m²/day, and after temperature, soiling, wiring and controller losses a kWp delivers just 1.76 kWh/day. Adding 10% margin gives 2.46 kWp, covered by six 450 W panels (2.70 kWp). In August the array gives 10.7 kWh/day, so about 1,670 kWh a year goes unused.
The battery for two days at 80% DoD and 10 °C is about 10.4 kWh nominal. On a 48 V bus the build is four 12.8 V 100 Ah batteries in series, three strings in parallel, i.e. 15.4 kWh (300 Ah) and nearly three real days of autonomy. When pump, fridge and washing-machine heater run together, the peak calls for a 4 kW inverter (surge at least 4.4 kW) and an 80 A MPPT controller. Rough cost with installation: about €10,900.
Using the results
- The sun-hours of the design month explain the array. If the array size by month chart shows one or two months driving it, a generator or a seasonal tilt change can beat buying panels.
- Real autonomy often exceeds the target, since batteries come in whole units.
- Months needing backup is zero when you design for the darkest month; with the generator option it gives the kWh the generator must deliver.
- Battery life mixes rated cycles and calendar ageing. Off-grid LFP rarely wears out from cycling; lead-acid tends to die of winter undercharge.
Typical results by site
| Location | Dec. sun on 55° panels | kWh/kWp/day (Dec.) | kWp for ≈ 3 kWh/day of loads |
|---|---|---|---|
| Helsinki, Finland | 0.3–0.6 kWh/m² | 0.3–0.5 | 10+ (generator usually cheaper) |
| Berlin, Germany | 0.9–1.2 kWh/m² | 0.7–1.0 | 4.5–6 |
| Bucharest, Romania | 2.0–2.3 kWh/m² | 1.6–1.9 | 2.3–2.7 |
| Madrid, Spain | 3.5–4.2 kWh/m² | 2.8–3.3 | 1.3–1.6 |
Values assume the default loads, 12% PV losses, MPPT and a 10% margin.
Advice for dependable systems
- Trim loads before buying panels. At mid-latitudes each kWh/day removed saves about 0.5–0.8 kWp and 2–3 kWh of battery in winter. Efficient fridges, LED lighting, no electric heating; cook and heat water with gas, wood or a solar thermal collector.
- Steep tilt. 55–65° in Europe lifts December yield and clears snow. Run the tilt angle calculator in winter mode.
- LFP over lead-acid for capacity, efficiency and cycle life, but never charge it below 0 °C.
- 48 V for anything bigger than a small cabin; check cable losses with the cable size calculator.
- Controller limits. Cold-weather open-circuit array voltage must stay under the MPPT input maximum, which the string sizing calculator tests.
- A small generator for the darkest weeks can halve array and battery costs in northern climates when you design for the fourth-darkest month.
Limits
Monthly means hide strings of cloudy days and year-to-year swings, so keep the autonomy and margin inputs. Loads are constant through the year; for seasonal loads such as heating fans or summer cooling, enter the values of your design month. Shading, snow cover and battery self-discharge are not modelled separately, and costs are rough and vary by country and installer.
Method & assumptions
Design proceeds in four steps.
1. Load. Add power × hours for every AC load to get daily energy E. Reflected to the battery bus, E_dc = E ÷ η_inverter + idle × 24 h. After accounting for the share f that is drawn from the battery overnight, the solar side supplies E_pv = E_dc × [(1 − f) + f ÷ RTE].
2. Battery. Multiply E_dc by the days of autonomy, then divide by √RTE, by DoD and by the temperature factor to obtain nominal Wh. Ah = Wh ÷ system voltage. The series count is V_system ÷ V_unit and the parallel strings are ⌈Ah ÷ Ah_unit⌉.
3. Array. Required size = E_pv ÷ (Y_design) × (1 + margin). Y_design is the design month's kWh/kWp/day, from NASA monthly irradiance transposed to your tilt, after cell temperature and losses, times controller efficiency (MPPT 97%, PWM ≈ 80%).
4. Electronics. Choose an inverter ≥ 1.25 × peak load whose surge covers the largest motor start, and a controller with current = array W ÷ V_system × 1.25.
Frequently asked questions
What solar array size does an off-grid home need?
How do I size the battery bank for an off-grid system?
Which system voltage should I pick: 12 V, 24 V or 48 V?
What are days of autonomy?
MPPT or PWM controller for off-grid solar?
Why is my winter-sized array so much bigger than summer demands?
Sources & references
- IEEE Std 1562 — Guide for Array and Battery Sizing in Stand-Alone Photovoltaic (PV) Systems
- IEC TS 62257 — Recommendations for renewable energy and hybrid systems for rural electrification
- NASA POWER — long-term monthly solar and meteorological climatology
- Sandia National Laboratories — Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices (SAND87-7023)
Embed this calculator
Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.