Batteries & storage calculator

Design an off-grid solar system: panels, batteries, inverter and charge controller

Designs a complete stand-alone solar installation from what you plug in. The design month is the darkest one at your location, based on NASA satellite climate data, days of autonomy and realistic battery chemistry limits.

Editable share link Branded PDF report Free · no sign-up

Results

A load of 3.18 kWh/day calls for about 2.7 kWp of panels (6 × 450 W), a LiFePO₄ (LFP) battery bank of 15.4 kWh at 48 V, and an inverter of 4 kW. The month that sets the design is December; in it, every kWp produces only 1.76 kWh/day.
Solar array
2.7kWp
6 × 450 W panels at 55°
Battery bank
15.4kWh
300 Ah @ 48 V · usable 11.6 kWh
Battery configuration
4S × 3P
12 × 12.8 V 100 Ah units
Inverter
4kW
continuous; surge ≥ 4.4 kW
Charge controller
80 A
MPPT · 70 A needed at 48 V
Daily load
3.18kWh/day
3.81 kWh/day drawn from the battery bus, inverter losses included
Design month
Dec
2.12 kWh/m²/day reaching the panels (sun-hours)
Real autonomy
3days
temperature factor 94%
Months needing backup
0/ 12
none
Summer surplus (unused)
1,666kWh/yr
typical for winter-sized arrays
Battery life
15years
about 68 cycles a year · the pack is rated at 6,000 cycles or a 15 yr calendar life
Rough system cost
€10,937
estimate covering hardware and installation
Solar yield per day against daily demand, by month
Array size required if sized for each month
Where the energy goes

Energy balance by month (★ = sizing month)

MonthSun on panels (kWh/m²/day)Solar (kWh/day)Need (kWh/day)Coverage
Jan2.455.513.94140%
Feb3.397.483.94190%
Mar4.239.053.94230%
Apr4.8310.033.94255%
May510.143.94258%
Jun5.029.993.94254%
Jul5.2810.373.94264%
Aug5.4510.73.94272%
Sep4.889.873.94251%
Oct48.43.94214%
Nov2.575.633.94143%
Dec2.124.763.94121% ★

Load list

LoadWh/dayShare
Lighting32010%
Refrigeration80025%
TV / entertainment2408%
Computers3009%
Always-on devices2408%
Water pump75024%
Washing machine2297%
Other3009%

Component checklist

ComponentSpecification
PV array6 × 450 W = 2.7 kWp, 55° tilt, azimuth 180°
Battery bank15.4 kWh of LiFePO₄ (LFP): 12 units of 12.8 V 100 Ah, wired 4 in series and 3 in parallel
Charge controllerMPPT rated 70 A or more at 48 V (keep the PV string Voc below the controller maximum input voltage)
Inverter4 kW pure-sine continuous output from a 48 V DC input, with surge capacity of 4.4 kW or more
Battery cable & fuserated for roughly 81 A continuous
  • Solar resource: NASA POWER monthly climate averages for 44.43, 26.1 (default-site data built in for pre-rendering), panels at 55° tilt and 180° azimuth, with cell temperature and 12% PV losses.
  • Energy path: AC loads ÷ 92% inverter efficiency, plus 15 W standby draw, gives the demand on the battery bus. Of that, 60% cycles through the battery at 95% round-trip efficiency, and the controller runs at 97%.
  • Autonomy days cover consecutive overcast days. NASA monthly averages hide multi-day storms, so remote critical systems often plan for 3–5 days plus a generator.

Design around the darkest month

An off-grid plant has nothing to lean on, so it is dimensioned for the harshest stretch rather than the yearly average. This calculator follows the stand-alone method of IEEE 1562 and the Sandia handbook, using climate data for your location.

  1. Loads. Pick appliances or type a daily total. The tool sums watt-hours per day and estimates both the peak load and the surge of motors (pumps, fridge compressors).
  2. Energy path. AC demand is divided by inverter efficiency, with 24 hours of idle consumption added on top. Evening and night energy passes through the battery and pays the round-trip loss.
  3. Sun. Monthly NASA POWER irradiance, temperature and wind for your site are tilted to your panel angle and turned into kWh per kWp per day reaching the battery, after cell-temperature and controller losses.
  4. Design month. The array follows the darkest month plus a margin. You can instead pick the fourth-darkest (generator covers deep winter) or the darkest summer month (seasonal cabin).
  5. Battery, inverter, controller. The bank must hold your autonomy days without breaching the chemistry’s depth-of-discharge limit, and must allow for capacity lost at the coldest battery temperature. It is then divided into series and parallel units.

Formulas

E_dc = E_ac ÷ η_inv + P_idle × 24 h E_pv = E_dc × [(1 − f) + f ÷ RTE] f = share used via battery Array kWp = E_pv ÷ Y_design × (1 + margin) Y = kWh/kWp/day in design month Battery Wh = E_dc × days ÷ √RTE ÷ DoD ÷ k_temp Ah = Wh ÷ V_sys series = V_sys ÷ V_unit parallel = ⌈Ah ÷ Ah_unit⌉ Inverter ≥ 1.25 × peak load Controller A = array W ÷ V_sys × 1.25

Example: all-year cabin by Bucharest

Default loads add up to 3.18 kWh/day: eight LED lamps, a low-consumption fridge, TV, laptop, router, a 750 W water pump for one hour a day, and two laundry cycles weekly. A 92% inverter with 15 W idle raises the battery-bus demand to 3.81 kWh/day. With 60% of it passing through a 95%-efficient LFP battery, the panels must supply 3.94 kWh/day.

At a 55° tilt, December gets 2.12 kWh/m²/day, and after temperature, soiling, wiring and controller losses a kWp delivers just 1.76 kWh/day. Adding 10% margin gives 2.46 kWp, covered by six 450 W panels (2.70 kWp). In August the array gives 10.7 kWh/day, so about 1,670 kWh a year goes unused.

The battery for two days at 80% DoD and 10 °C is about 10.4 kWh nominal. On a 48 V bus the build is four 12.8 V 100 Ah batteries in series, three strings in parallel, i.e. 15.4 kWh (300 Ah) and nearly three real days of autonomy. When pump, fridge and washing-machine heater run together, the peak calls for a 4 kW inverter (surge at least 4.4 kW) and an 80 A MPPT controller. Rough cost with installation: about €10,900.

Using the results

  • The sun-hours of the design month explain the array. If the array size by month chart shows one or two months driving it, a generator or a seasonal tilt change can beat buying panels.
  • Real autonomy often exceeds the target, since batteries come in whole units.
  • Months needing backup is zero when you design for the darkest month; with the generator option it gives the kWh the generator must deliver.
  • Battery life mixes rated cycles and calendar ageing. Off-grid LFP rarely wears out from cycling; lead-acid tends to die of winter undercharge.

Typical results by site

Location Dec. sun on 55° panels kWh/kWp/day (Dec.) kWp for ≈ 3 kWh/day of loads
Helsinki, Finland 0.3–0.6 kWh/m² 0.3–0.5 10+ (generator usually cheaper)
Berlin, Germany 0.9–1.2 kWh/m² 0.7–1.0 4.5–6
Bucharest, Romania 2.0–2.3 kWh/m² 1.6–1.9 2.3–2.7
Madrid, Spain 3.5–4.2 kWh/m² 2.8–3.3 1.3–1.6

Values assume the default loads, 12% PV losses, MPPT and a 10% margin.

Advice for dependable systems

  • Trim loads before buying panels. At mid-latitudes each kWh/day removed saves about 0.5–0.8 kWp and 2–3 kWh of battery in winter. Efficient fridges, LED lighting, no electric heating; cook and heat water with gas, wood or a solar thermal collector.
  • Steep tilt. 55–65° in Europe lifts December yield and clears snow. Run the tilt angle calculator in winter mode.
  • LFP over lead-acid for capacity, efficiency and cycle life, but never charge it below 0 °C.
  • 48 V for anything bigger than a small cabin; check cable losses with the cable size calculator.
  • Controller limits. Cold-weather open-circuit array voltage must stay under the MPPT input maximum, which the string sizing calculator tests.
  • A small generator for the darkest weeks can halve array and battery costs in northern climates when you design for the fourth-darkest month.

Limits

Monthly means hide strings of cloudy days and year-to-year swings, so keep the autonomy and margin inputs. Loads are constant through the year; for seasonal loads such as heating fans or summer cooling, enter the values of your design month. Shading, snow cover and battery self-discharge are not modelled separately, and costs are rough and vary by country and installer.

Method & assumptions

Design proceeds in four steps.

1. Load. Add power × hours for every AC load to get daily energy E. Reflected to the battery bus, E_dc = E ÷ η_inverter + idle × 24 h. After accounting for the share f that is drawn from the battery overnight, the solar side supplies E_pv = E_dc × [(1 − f) + f ÷ RTE].

2. Battery. Multiply E_dc by the days of autonomy, then divide by √RTE, by DoD and by the temperature factor to obtain nominal Wh. Ah = Wh ÷ system voltage. The series count is V_system ÷ V_unit and the parallel strings are ⌈Ah ÷ Ah_unit⌉.

3. Array. Required size = E_pv ÷ (Y_design) × (1 + margin). Y_design is the design month's kWh/kWp/day, from NASA monthly irradiance transposed to your tilt, after cell temperature and losses, times controller efficiency (MPPT 97%, PWM ≈ 80%).

4. Electronics. Choose an inverter ≥ 1.25 × peak load whose surge covers the largest motor start, and a controller with current = array W ÷ V_system × 1.25.

Frequently asked questions

What solar array size does an off-grid home need?
Work from the winter. Divide daily consumption (with inverter losses) by the kWh one kWp delivers per day in December. South-eastern Europe gets about 1.6–1.9 kWh/kWp/day on a winter tilt and Germany only 0.7–1.0. So 3 kWh/day of loads means around 2.5 kWp in the former, 5 kWp or more in the latter, and about 1.5 kWp in Spain. That is a multiple of what summer alone would demand.
How do I size the battery bank for an off-grid system?
Daily energy times autonomy days, divided by allowed depth of discharge, and by a temperature factor in cold sites. With 3.8 kWh/day, 2 days and LFP at 80% DoD the answer is about 10–11 kWh nominal: four 12.8 V 100 Ah units in series make a 48 V, 5.1 kWh string, and two or three strings go in parallel. Lead-acid cannot be drained below 50%, so plan about 60% extra nominal capacity.
Which system voltage should I pick: 12 V, 24 V or 48 V?
Twelve volts suits vans, boats and cabins drawing under about 1 kW. Use 24 V for 1–2.5 kW and 48 V above. The reason is current: a 3 kW inverter needs about 270 A at 12 V and about 68 A at 48 V. Lower current allows thinner cable, smaller fuses and less loss.
What are days of autonomy?
They count how long the battery can carry the load with the sun contributing nothing. Two days is a common pick for holiday homes backed by a generator. Homes lived in all year under cloudy skies, or loads that must never stop such as telecom and medical equipment, call for three to five. Each added day means one more full day of stored energy.
MPPT or PWM controller for off-grid solar?
MPPT converts surplus panel voltage into extra charging current and harvests about 15–30% more than PWM, which just links panels to battery. PWM only makes sense on very small 12 V systems whose panels are built for 12 V charging. With today's 400–600 W panels, MPPT is required.
Why is my winter-sized array so much bigger than summer demands?
Because the darkest month decides. At mid-latitudes December offers a quarter to a third of the solar energy of July, so a winter-proof array produces plenty of surplus later in the year. Some owners heat water with it; others plan around the fourth-darkest month and use a small generator for the worst weeks.

Sources & references

  1. IEEE Std 1562 — Guide for Array and Battery Sizing in Stand-Alone Photovoltaic (PV) Systems
  2. IEC TS 62257 — Recommendations for renewable energy and hybrid systems for rural electrification
  3. NASA POWER — long-term monthly solar and meteorological climatology
  4. Sandia National Laboratories — Stand-Alone Photovoltaic Systems, A Handbook of Recommended Design Practices (SAND87-7023)

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.