A short circuit would push 23.6 kA (peak 56.5 kA) through the transformer's low-voltage side and 18.6 kA through the far end of the cable, in a three-phase fault. Select protection rated to interrupt 25 kA or more on the main board, and 20 kA or more where the cable terminates.
Ik3 at the transformer terminals
23.6kA
25.3 kA from an infinite source
Peak current ip (at terminals)
56.5kA
κ = 1.69
Ik3 at cable end
18.6kA
Peak current ip (at cable end)
37.9kA
Phase-to-phase fault Ik2 (cable end)
16.1kA
Transformer full-load current
1,443A
Required breaking capacity, main board
25kA
next standard Icu/Icn
Required breaking capacity, cable end
20kA
Per-phase impedance (referred to LV)
| Element | R (mΩ) | X (mΩ) | Z (mΩ) |
|---|---|---|---|
| Upstream network | 0.07 | 0.67 | 0.67 |
| Transformer | 1.22 | 9.52 | 9.6 |
| Cable | 2.23 | 2.4 | 3.27 |
| Total to cable end | 3.51 | 12.59 | 13.07 |
- This is the maximum symmetrical three-phase fault current from IEC 60909-0, using voltage factor c with conductors at 20 °C. Neither the motor contribution nor the transformer correction factor KT enters the result (KT is about 1 when uk ≤ 6%).
- Earth-fault current on a single phase depends on the earthing system and zero-sequence impedance. A Dyn transformer gives about the same value as Ik3 at its terminals, but it declines more steeply along the cable.