Electrical engineering calculator

Short-circuit fault level: transformer terminals and cable end

Starting from the upstream fault level, the transformer's kVA and impedance, and the cable's size, length and material, the tool returns the three-phase prospective short-circuit current (kA) and peak current. Results apply at the transformer's LV terminals and at the cable end, using IEC 60909.

Editable share link Branded PDF report Free · no sign-up

Results

A short circuit would push 23.6 kA (peak 56.5 kA) through the transformer's low-voltage side and 18.6 kA through the far end of the cable, in a three-phase fault. Select protection rated to interrupt 25 kA or more on the main board, and 20 kA or more where the cable terminates.
Ik3 at the transformer terminals
23.6kA
25.3 kA from an infinite source
Peak current ip (at terminals)
56.5kA
κ = 1.69
Ik3 at cable end
18.6kA
Peak current ip (at cable end)
37.9kA
Phase-to-phase fault Ik2 (cable end)
16.1kA
Transformer full-load current
1,443A
Required breaking capacity, main board
25kA
next standard Icu/Icn
Required breaking capacity, cable end
20kA
Fault current by cable length

Per-phase impedance (referred to LV)

ElementR (mΩ)X (mΩ)Z (mΩ)
Upstream network0.070.670.67
Transformer1.229.529.6
Cable2.232.43.27
Total to cable end3.5112.5913.07
  • This is the maximum symmetrical three-phase fault current from IEC 60909-0, using voltage factor c with conductors at 20 °C. Neither the motor contribution nor the transformer correction factor KT enters the result (KT is about 1 when uk ≤ 6%).
  • Earth-fault current on a single phase depends on the earthing system and zero-sequence impedance. A Dyn transformer gives about the same value as Ik3 at its terminals, but it declines more steeply along the cable.

What is at stake in a fault

Once phases touch, only the impedance between source and fault limits the current, and beside a big transformer that can mean tens of kiloamps. A breaker or fuse that cannot interrupt the worst case it may face can burst instead of clearing the fault. Mechanical strength matters too, since busbars and cleats take the peak magnetic force of the first half-cycle. For that reason fault current ranks with load current and voltage drop among the first figures in an LV design.

The calculator applies the IEC 60909 impedance method to a radial LV layout: an MV network, a distribution transformer, then a cable to a sub-board. Outputs: peak and maximum three-phase currents at the transformer and at the sub-board, the phase-to-phase fault current, and the lowest standard breaker rating that is adequate.

Equations

Network: Z_Q = c·U² ÷ S″kQ (X/R ≈ 10) Transformer: Z_T = u_k·U² ÷ S_n R_T = P_k·U² ÷ S_n² X_T = √(Z_T² − R_T²) Cable: R_C = ρ·L ÷ (A·n) X_C = x′·L ÷ n

I″k3 = c·U ÷ (√3 · |Z_Q + Z_T + Z_C|) i_p = κ·√2·I″k3 κ = 1.02 + 0.98·e^(−3R/X) I″k2 = (√3 ÷ 2)·I″k3

Symbols: U is the LV line voltage; ρ = 0.0178 Ω·mm²/m for copper, 0.0286 for aluminium; both values are taken at 20 °C, the IEC 60909 choice for maximum currents; A is cross-section; n counts parallel cables in each phase; x′ is the cable reactance, near 0.08 mΩ/m for multicore types.

Example with the defaults

Default case: a 1,000 kVA, 6% transformer with 7.6 kW load losses, supplied by a 250 MVA MV network. From its 400 V secondary, two parallel 240 mm² copper cables, 60 m long, run to a sub-board.

Impedances at 400 V: the network gives 1.05 × 400² ÷ 250 MVA = 0.67 mΩ, and the transformer 0.06 × 400² ÷ 1,000 kVA = 9.6 mΩ (R = 1.22 mΩ, X = 9.52 mΩ). At the LV terminals |Z| ≈ 10.3 mΩ, so I″k3 = 1.05 × 400 ÷ (1.732 × 10.3 mΩ) ≈ 23.6 kA. With X/R ≈ 7.8 the factor κ is 1.69 and the peak current reaches 56.5 kA.

Then 2.2 mΩ of resistance and 2.4 mΩ of reactance come from the cable, leaving 18.6 kA at the sub-board. So specify 25 kA as the least breaking capacity for the main LV breaker and 20 kA for sub-board devices.

The rule of thumb I_n ÷ u_k returns 24.1 kA (25.3 kA with c = 1.05). That lands close to the full calculation since a 250 MVA network barely sags against a 1 MVA transformer.

Table of values at 400 V transformer terminals

Transformer u_k Full-load current I″k3 (infinite source, c = 1.05)
250 kVA 4% 361 A ≈ 9.5 kA
400 kVA 4% 577 A ≈ 15 kA
630 kVA 4% 909 A ≈ 24 kA
1,000 kVA 6% 1,443 A ≈ 25 kA
1,600 kVA 6% 2,309 A ≈ 40 kA
2,500 kVA 6% 3,608 A ≈ 63 kA

Two transformers feeding one busbar in parallel roughly double the fault level, which often forces a switchgear upgrade.

Using the output

  • Ik3 at the transformer: sets the breaker rating for the main LV board.
  • Peak ip: compare with the rated peak withstand current (Ipk) of the busbar system.
  • Ik3 at the cable end: fixes the rating for downstream boards; the chart shows how quickly the current drops with distance.
  • Ik2, line to line: a lower value, occasionally used to confirm protection still trips fast enough.

Limitations

The tool reports the largest symmetrical three-phase current only. Not included: motors feeding the fault, generators, the transformer correction factor K_T (about 1 for ordinary units) and the heating of conductors while the fault lasts. Earth faults depend on the earthing arrangement (TN, TT, IT) and on zero-sequence impedance; calculate them separately, above all when verifying disconnection times. For a final design, use specialist software or carry out a complete IEC 60909 or IEEE 551 study. The cable size calculator handles sizing for load and voltage drop.

Method & assumptions

Impedances are built up from three parts. The upstream source gives ZQ = c U² ÷ S″kQ, assuming X/R = 10. The transformer adds ZT = uk U² ÷ Sn and RT = Pk U² ÷ Sn². The cable adds R = ρ L ÷ (A × n) and X = x′ L ÷ n. From the combined |Z|, the symmetrical three-phase current is I″k3 = c U ÷ (√3 |Z|). Multiply by κ √2, with κ = 1.02 + 0.98 e−3R/X, for the peak ip. A fault between two conductors yields I″k2 = (√3/2) I″k3.

Frequently asked questions

How can I estimate a transformer's short-circuit current?
A fast approximation is the rated current divided by the impedance voltage: Ik ≈ In ÷ uk. Take a 1,000 kVA, 400 V transformer with In = 1,443 A and uk = 6%. Result: close to 24 kA, rising to roughly 25 kA when the IEC voltage factor c = 1.05 is included. Impedance in the upstream network trims it slightly.
Ik versus ip: which is which?
Ik (I″k) denotes the RMS symmetrical short-circuit current, which is what a breaker must clear. ip is the top instantaneous value reached in the first half-cycle, with the DC offset added. It governs magnetic forces on busbars and how much current switchgear must be able to close onto. The relation is ip = κ × √2 × Ik, with κ from 1.02 to 2 depending on X/R.
Does a long cable reduce the fault current?
Yes: the cable's resistance is added to the loop impedance. Take a sub-board 150 m away, fed by one 95 mm² aluminium cable: it may see only 4–5 kA when the main board sees 15 kA. Breaker ratings benefit, though the current still has to be high enough for protection to trip fast.
How do I pick the breaking capacity of a breaker?
Look at the rated ultimate breaking capacity: Icu on IEC 60947-2 breakers, Icn on IEC 60898 MCBs. It must not be lower than the prospective short-circuit current at the spot where the device is fitted. Standard ratings include 6, 10, 15, 25, 36, 50, 70 and 100 kA.
What does the voltage factor c mean in IEC 60909?
It reflects that networks can operate above nominal voltage. For maximum fault currents in low-voltage systems, IEC 60909-0 sets c = 1.05 with a ±6% voltage tolerance and 1.10 with ±10%. For minimum currents, used when checking that protection trips, c = 0.95.
Should motors be counted in the fault current?
They do contribute. Induction motors that are running push current into a fault for a few cycles, about their locked-rotor level, typically 4–6 times rated. IEC 60909 asks you to add them once they pass roughly 5% of the motor-free fault current. This calculator does not.

Sources & references

  1. IEC 60909-0 — Short-circuit currents in three-phase AC systems: Calculation of currents
  2. IEEE Std 551 (Violet Book) — Calculating Short-Circuit Currents in Industrial and Commercial Power Systems
  3. Schneider Electric — Electrical Installation Guide, chapter G: Short-circuit current
  4. IEC 60947-2 — Low-voltage switchgear: Circuit-breakers