What is at stake in a fault
Once phases touch, only the impedance between source and fault limits the current, and beside a big transformer that can mean tens of kiloamps. A breaker or fuse that cannot interrupt the worst case it may face can burst instead of clearing the fault. Mechanical strength matters too, since busbars and cleats take the peak magnetic force of the first half-cycle. For that reason fault current ranks with load current and voltage drop among the first figures in an LV design.
The calculator applies the IEC 60909 impedance method to a radial LV layout: an MV network, a distribution transformer, then a cable to a sub-board. Outputs: peak and maximum three-phase currents at the transformer and at the sub-board, the phase-to-phase fault current, and the lowest standard breaker rating that is adequate.
Equations
I″k3 = c·U ÷ (√3 · |Z_Q + Z_T + Z_C|) i_p = κ·√2·I″k3 κ = 1.02 + 0.98·e^(−3R/X) I″k2 = (√3 ÷ 2)·I″k3
Symbols: U is the LV line voltage; ρ = 0.0178 Ω·mm²/m for copper, 0.0286 for aluminium; both values are taken at 20 °C, the IEC 60909 choice for maximum currents; A is cross-section; n counts parallel cables in each phase; x′ is the cable reactance, near 0.08 mΩ/m for multicore types.
Example with the defaults
Default case: a 1,000 kVA, 6% transformer with 7.6 kW load losses, supplied by a 250 MVA MV network. From its 400 V secondary, two parallel 240 mm² copper cables, 60 m long, run to a sub-board.
Impedances at 400 V: the network gives 1.05 × 400² ÷ 250 MVA = 0.67 mΩ, and the transformer 0.06 × 400² ÷ 1,000 kVA = 9.6 mΩ (R = 1.22 mΩ, X = 9.52 mΩ). At the LV terminals |Z| ≈ 10.3 mΩ, so I″k3 = 1.05 × 400 ÷ (1.732 × 10.3 mΩ) ≈ 23.6 kA. With X/R ≈ 7.8 the factor κ is 1.69 and the peak current reaches 56.5 kA.
Then 2.2 mΩ of resistance and 2.4 mΩ of reactance come from the cable, leaving 18.6 kA at the sub-board. So specify 25 kA as the least breaking capacity for the main LV breaker and 20 kA for sub-board devices.
The rule of thumb I_n ÷ u_k returns 24.1 kA (25.3 kA with c = 1.05). That lands close to the full calculation since a 250 MVA network barely sags against a 1 MVA transformer.
Table of values at 400 V transformer terminals
| Transformer | u_k | Full-load current | I″k3 (infinite source, c = 1.05) |
|---|---|---|---|
| 250 kVA | 4% | 361 A | ≈ 9.5 kA |
| 400 kVA | 4% | 577 A | ≈ 15 kA |
| 630 kVA | 4% | 909 A | ≈ 24 kA |
| 1,000 kVA | 6% | 1,443 A | ≈ 25 kA |
| 1,600 kVA | 6% | 2,309 A | ≈ 40 kA |
| 2,500 kVA | 6% | 3,608 A | ≈ 63 kA |
Two transformers feeding one busbar in parallel roughly double the fault level, which often forces a switchgear upgrade.
Using the output
- Ik3 at the transformer: sets the breaker rating for the main LV board.
- Peak ip: compare with the rated peak withstand current (Ipk) of the busbar system.
- Ik3 at the cable end: fixes the rating for downstream boards; the chart shows how quickly the current drops with distance.
- Ik2, line to line: a lower value, occasionally used to confirm protection still trips fast enough.
Limitations
The tool reports the largest symmetrical three-phase current only. Not included: motors feeding the fault, generators, the transformer correction factor K_T (about 1 for ordinary units) and the heating of conductors while the fault lasts. Earth faults depend on the earthing arrangement (TN, TT, IT) and on zero-sequence impedance; calculate them separately, above all when verifying disconnection times. For a final design, use specialist software or carry out a complete IEC 60909 or IEEE 551 study. The cable size calculator handles sizing for load and voltage drop.
Method & assumptions
Impedances are built up from three parts. The upstream source gives ZQ = c U² ÷ S″kQ, assuming X/R = 10. The transformer adds ZT = uk U² ÷ Sn and RT = Pk U² ÷ Sn². The cable adds R = ρ L ÷ (A × n) and X = x′ L ÷ n. From the combined |Z|, the symmetrical three-phase current is I″k3 = c U ÷ (√3 |Z|). Multiply by κ √2, with κ = 1.02 + 0.98 e−3R/X, for the peak ip. A fault between two conductors yields I″k2 = (√3/2) I″k3.
Frequently asked questions
How can I estimate a transformer's short-circuit current?
Ik versus ip: which is which?
Does a long cable reduce the fault current?
How do I pick the breaking capacity of a breaker?
What does the voltage factor c mean in IEC 60909?
Should motors be counted in the fault current?
Sources & references
- IEC 60909-0 — Short-circuit currents in three-phase AC systems: Calculation of currents
- IEEE Std 551 (Violet Book) — Calculating Short-Circuit Currents in Industrial and Commercial Power Systems
- Schneider Electric — Electrical Installation Guide, chapter G: Short-circuit current
- IEC 60947-2 — Low-voltage switchgear: Circuit-breakers