With 20% growth allowed for, a 630 kVA unit handles the 560 kVA requirement. It is loaded to 74% of its rating at peak and 37% at average load. Expect roughly 10,258 kWh of losses per year (1,539 €) and a secondary full-load current of 909 A.
Recommended rating
630kVA
560 kVA needed once margin is added
Loading at peak
74%
Secondary full-load current
909A
at 400 V
Primary full-load current
33.1A
at 11 kV
No-load loss
540W
iron loss, 24/7
Load loss at rated current
4,600W
copper loss ∝ load²
Efficiency at mean load
99.45%
Peak efficiency
99.45%
at 34% load
Annual losses
10,258kWh
Annual cost of losses
€1,539
Secondary short-circuit current
22.7kA
uk 4%, infinite source
Candidate ratings
| Rating (kVA) | Peak loading | No-load loss (W) | Load loss (W) | Annual losses (kWh) | Loss cost (€/yr) |
|---|---|---|---|---|---|
| 500 | 93% | 459 | 3,900 | 11,461 | 1,719 |
| 630 | 74% | 540 | 4,600 | 10,258 | 1,539 |
| 800 | 58% | 585 | 6,000 | 9,596 | 1,439 |
| 1,000 | 47% | 693 | 7,600 | 9,695 | 1,454 |
| 1,250 | 37% | 855 | 9,500 | 10,390 | 1,558 |
- The default losses are the EU Ecodesign Tier 2 ceilings for liquid-immersed transformers (Regulation 548/2014, amended 2019/1783). Type in the datasheet figures for your own unit. Dry-type units typically show 50–100% more no-load loss.
- The yearly loss figure holds the mean load constant. Load losses rise with the square of current, so a spiky profile will lose a little more than shown.