Glossary · Grid & markets

Grid-forming inverter

An inverter that defines its own voltage and frequency, behaving like a voltage source; it can hold weak grids steady and provides synthetic inertia.

The typical solar, wind or battery inverter today is grid-following. It locks onto the grid's voltage with a phase-locked loop and pushes current out in step, relying on synchronous machines to supply a clean voltage waveform in the first place. By contrast, a grid-forming (GFM) inverter is a controlled voltage source behind an impedance. It decides voltage magnitude and phase angle by itself, in the manner of a synchronous generator.

Control schemes include droop control, virtual synchronous machine (VSM) emulation and dispatchable virtual oscillator control. What GFM inverters can do:

  • React immediately to phase jumps and frequency shifts, supplying synthetic inertia.
  • Stay stable in weak grids where short-circuit ratio (SCR) is under 3.
  • Run microgrids as islands and, potentially, perform black start.
  • Damp oscillations and support voltage when faults occur.

Limited current is the catch. In a fault, power semiconductors normally cannot exceed 1.1 to 1.5 times rated current, whereas synchronous machines can deliver 5 to 7 times. That is why batteries with spare headroom are the favoured hardware. Examples: the 2022 Hornsdale Power Reserve upgrade in South Australia (virtual machine mode), Kapolei in Hawaii, and various Australian BESS projects. NESO in Great Britain has issued a GB Grid Forming specification and run stability pathfinder tenders, while AEMO, ERCOT and NERC are working on GFM performance requirements.

Related terms

All terms →
  • Inertia (grid)

    Kinetic energy held in synchronously spinning generators and motors, which resists abrupt shifts in grid frequency.

  • Grid frequency

    How many times per second alternating current reverses on a power system, 50 Hz or 60 Hz; it mirrors the moment-to-moment balance between supply and demand.

  • BESS (Battery Energy Storage System)

    A full grid-connected or on-site battery plant: cells, battery management, power electronics, thermal management and control systems.

  • Microgrid

    A defined cluster of generators, storage and loads that can run tied to the main grid or on its own in island mode.

  • Black start

    Rebuilding a power system after a full or partial blackout, beginning with units able to start without any power from the grid.

  • Variable renewable energy (VRE)

    Wind and solar PV power, whose production rises and falls with weather and daylight and cannot be fully scheduled by the operator.