Ground-source heat pump
A heat pump whose heat source is the ground, reached by buried loops or boreholes; constant soil temperature keeps its seasonal efficiency high.
A ground-source heat pump (GSHP, also called a geothermal heat pump) uses closed underground loops filled with water-glycol brine. At depths below about 10–15 m the soil holds a near-steady temperature, close to the local average yearly air temperature (8–12 °C across much of Europe). The source therefore stays comparatively warm through winter and cool through summer.
- Vertical boreholes run 50–200 m deep with a 110–150 mm diameter, and each metre yields about 40–60 W in good rock
- Horizontal loops lie 1.2–2 m below the surface and take up land of roughly 1.5–3 times the heated floor area
- Open systems draw groundwater straight from the aquifer, where regulations allow it
Ground extraction = heat output x (1 - 1/COP)
Example: 10 kW at COP 4.5 needs 7.8 kW from ground; at 50 W/m ≈ 156 m of borehole
Seasonal performance typically lands at SCOP 4.5–5.5 for 35 °C flow, better than air-source alternatives, and the unit avoids defrost cycles and an external fan. What hurts is drilling, which often costs 15,000–30,000 EUR for one house. So GSHPs make most sense for larger buildings, new builds and shared-loop networks. In summer, passive cooling can put heat back into the ground. The ground-source heat pump calculator helps you size a system.
Related terms
All terms →- Heat pump
Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.
- Air-source heat pump
A heat pump that pulls warm energy out of the outside air to heat rooms and water (air-to-water) or to blow warm air (air-to-air); the leading installed technology.
- COP (Coefficient of Performance)
How much useful heat (or cooling) a heat pump delivers per unit of electricity it uses, at one stated operating point.
- SCOP (Seasonal COP)
Seasonal coefficient of performance (SCOP): a heat pump's average COP over a standard heating season, built from test points weighted by how often each outdoor temperature occurs.
- Geothermal gradient
Away from plate boundaries, rock gets hotter by roughly 25 to 30 °C with every kilometre of depth; this is the geothermal gradient.