Glossary · Grid & markets

Inertia (grid)

Kinetic energy held in synchronously spinning generators and motors, which resists abrupt shifts in grid frequency.

Grid inertia comes from the rotating mass of turbines, generators and large motors locked to the grid's speed. Should a big plant trip, they hand back some of that stored energy within milliseconds, which slows the fall in frequency and buys frequency response a few seconds to start.

H = (½ × J × ω²) / Srated

H, the inertia constant, is expressed in seconds: stored kinetic energy per unit of rated power. Steam turbines range from 4 to 9 s, gas turbines from 3 to 7 s and hydro units from 2 to 4 s. For a whole grid, inertia is quoted in GW·s or MW·s.

Inverters sit between wind or solar plants and the network, so these sources contribute no natural inertia. The more they displace synchronous generation, the less inertia remains and the faster frequency moves after a disturbance (higher RoCoF). In Great Britain, NESO keeps a floor of roughly 102 to 120 GW·s and buys stability services to hold it. Ireland restricts non-synchronous penetration (SNSP), which EirGrid raised to 75% in 2023.

Ways to add inertia: synchronous condensers (generators spinning without fuel, occasionally with flywheels), grid-forming inverters on batteries giving virtual or synthetic inertia, fast frequency response from BESS, and protection set to tolerate high RoCoF (often 1 Hz/s).

Related terms

All terms →
  • Grid frequency

    How many times per second alternating current reverses on a power system, 50 Hz or 60 Hz; it mirrors the moment-to-moment balance between supply and demand.

  • Frequency response

    The automatic shift in generation or demand that halts and then corrects a frequency drift following a sudden mismatch on the grid.

  • Grid-forming inverter

    An inverter that defines its own voltage and frequency, behaving like a voltage source; it can hold weak grids steady and provides synthetic inertia.

  • Variable renewable energy (VRE)

    Wind and solar PV power, whose production rises and falls with weather and daylight and cannot be fully scheduled by the operator.

  • Ancillary services

    Products other than bulk energy that grid operators buy to keep the system stable and secure: frequency reserves, voltage support, black start and the like.

  • BESS (Battery Energy Storage System)

    A full grid-connected or on-site battery plant: cells, battery management, power electronics, thermal management and control systems.