Frequency response
The automatic shift in generation or demand that halts and then corrects a frequency drift following a sudden mismatch on the grid.
Restoring grid frequency after a disturbance, say a large generator or an interconnector tripping, involves automatic and manual steps in sequence, together called frequency response:
- Inertial response (instantly, lasting a few seconds): spinning machines hand back stored kinetic energy, which holds down how fast frequency changes (see inertia).
- Primary response (seconds up to 30 s): governors on generators, and fast resources, lift output according to how large the deviation is. For Continental Europe this means Frequency Containment Reserve (FCR), about 3,000 MW, dimensioned to cover two large nuclear units tripping.
- Secondary response (30 s to 15 min): automatic generation control pulls frequency back to nominal and restores scheduled flows (aFRR).
- Tertiary reserves then replace what the secondary reserves used up.
Droop sets the primary response. A 4% droop means a unit swings from nothing to full output while frequency moves by 4% (2 Hz at 50 Hz).
North America's NERC quantifies the response in MW per 0.1 Hz; the Eastern Interconnection must provide roughly 1,000 MW/0.1 Hz. Falling inertia has pushed system operators toward quicker services. Great Britain's Dynamic Containment responds in 1 second, with batteries supplying almost all of it, and ERCOT's Fast Frequency Response takes 0.5 s.
Related terms
All terms →- Grid frequency
How many times per second alternating current reverses on a power system, 50 Hz or 60 Hz; it mirrors the moment-to-moment balance between supply and demand.
- Inertia (grid)
Kinetic energy held in synchronously spinning generators and motors, which resists abrupt shifts in grid frequency.
- Ancillary services
Products other than bulk energy that grid operators buy to keep the system stable and secure: frequency reserves, voltage support, black start and the like.
- BESS (Battery Energy Storage System)
A full grid-connected or on-site battery plant: cells, battery management, power electronics, thermal management and control systems.
- Grid-forming inverter
An inverter that defines its own voltage and frequency, behaving like a voltage source; it can hold weak grids steady and provides synthetic inertia.
- Reserve margin
How far available or accredited capacity sits above forecast peak demand, given as a percentage of that peak.