Three-phase power calculator: kW to amps and back, star or delta

Get real, reactive and apparent power in a three-phase circuit from the current, or the current from the power. Line and phase voltages and currents are shown for star (Y) and delta (Δ), along with motor efficiency and a list of standard voltages.

Editable share link Branded PDF report Free · no sign-up

Results

Three-phase at 400 V with 32 A per line and PF 0.9 gives 19.95 kW real power and 22.17 kVA apparent power. Every star winding carries 231 V and 32 A.
Real power
19.95kW
32 A at 400 V, PF 0.9
Line current
32A
Apparent power
22.17kVA
Reactive power
9.66kVAr
Phase voltage
230.9V
V_ph = V_L ÷ √3
Phase (winding) current
32A
I_ph = I_L
Impedance per phase
7.22Ω
Motor shaft output
18.36kW
24.6 hp at 92% efficiency
Suggested breaker (≥125%)
40 A
rule of thumb for continuous loads; check local code
Single-phase equivalent
96A at 230 V
why big loads use three phases
Momentary phase voltages across one cycle
Current needed for the same 20 kW at common voltages

Standard three-phase voltages

Line-to-line (V)Phase, star (V)Typical useAmps for 20 kWkW per 100 A
208120US commercial61.532.4
230133old IEC / Japan55.735.9
400231Europe, IEC3262.4
415240UK, Australia30.864.7
480277US industrial26.774.8
600346Canada21.393.5
690398industrial / wind18.6107.6
3,3001,905MV motors3.9514.4
6,6003,811MV1.91,028.8
11,0006,351MV distribution1.21,714.7
20,00011,547MV distribution0.63,117.7
33,00019,053MV / wind farm collector0.45,144.2
  • The calculation assumes a balanced load, with equal current in each of the three lines. If the load is unbalanced, calculate every phase on its own: P = Σ V_ph · I_ph · cos φ.
  • Star wiring: each line carries the phase current, and the voltage between lines is √3 times the phase voltage. Delta wiring flips this, with the line current √3 times the phase current. Power uses one formula in both cases.
  • Treat the breaker rating as a rough guide only (125% of the continuous current). The final protection depends on cable size and length, how it is installed and your local regulations.

Line against phase

Wherever the load is big, three-phase wiring is probably behind it: factories, large buildings, EV wallboxes and fast chargers, heat pumps over a few kW, and all generating stations. Two pairs of quantities cause most confusion. Line voltage and current are the ones you measure between conductors and within each conductor. Phase voltage and current belong to one winding or one element of the load.

Start by choosing the direction: current to power, or power to current. Then give the line-to-line voltage and power factor, and say whether the load is star (wye) or delta. If the load is a motor, give shaft power and efficiency, and the electrical input is derived. You receive real, apparent and reactive power, values per line and per phase, impedance per phase and a breaker suggestion. Also shown: how much current one phase would carry for the same power, and currents at all standard voltages between 208 V and 33 kV.

Equations

P = √3 × V_L × I_L × cos φ S = √3 × V_L × I_L Q = √(S² − P²) Star (Y): V_ph = V_L ÷ √3 I_ph = I_L Delta (Δ): V_ph = V_L I_ph = I_L ÷ √3 Motor: P_electrical = P_shaft ÷ η I_L = P ÷ (√3 × V_L × cos φ)

Sample case: 400 V, 32 A

Defaults: 400 V European supply, 32 A per line, power factor 0.9, star load.

  • P = 1.732 × 400 × 32 × 0.9, giving 19.95 kW.
  • S is 22.17 kVA, Q is 9.66 kVAr.
  • A winding gets 400 ÷ 1.732 = 231 V at 32 A, so its impedance is 7.2 Ω per phase.
  • A 92%-efficient motor on this supply yields 18.4 kW (24.6 hp) at the shaft.
  • On one 230 V phase, 20 kW would draw about 96 A, which is triple.

Understanding what you see

  • Cables, breakers and contactors are chosen from the line current.
  • Phase figures describe the load: winding insulation, heater elements, motor nameplate ratings like “230 V Δ / 400 V Y”.
  • On the waveform chart the three voltages sit 120° apart and cancel to zero at each instant, which means a balanced load puts no current in the neutral.
  • On the bar chart, the same power appears at each standard voltage. Higher voltage, lower current, thinner cable.

Standard three-phase voltages

Line-to-line Phase (star) Where
208 V 120 V US commercial buildings
400 V 230 V Europe and most IEC countries
415 V 240 V UK, Australia (nominal 400 V ±)
480 V 277 V US industry
600 V 347 V Canada
690 V 400 V Large motors, wind turbines
11–33 kV 6.4–19 kV Medium-voltage distribution, wind and solar parks

Current for common loads at 400 V

Load Power PF Line current
11 kW EV wallbox 11 kW 0.99 16 A
22 kW EV wallbox 22 kW 0.99 32 A
15 kW heat pump 5 kW electrical 0.95 7.6 A
7.5 kW motor (IE3, η 90%) 8.3 kW input 0.82 14.7 A
55 kW motor (η 94%) 58.5 kW input 0.86 98 A

Practical points

  1. Share single-phase loads out across L1, L2 and L3; lopsided loading leads to neutral current and voltage imbalance.
  2. Check how the motor nameplate says to connect it. A “230/400 V” motor goes in star on 400 V and in delta on 230 V.
  3. Starting in star and then switching to delta (star–delta starting) brings the starting current down to about a third.
  4. For power factor see the kVA to kW calculator; for single elements, Ohm’s law applies.
  5. Treat the displayed breaker size as a rough guide. Local code, cable size, length and grouping override it.

What is not covered

A balanced, sinusoidal system is assumed. For unbalance, drive and rectifier harmonics, voltage drop in long cables or motor inrush, a separate study is required. Because motor efficiency and power factor depend on loading, an oversized motor should be entered with its part-load figures.

Method & assumptions

In a balanced three-phase load, P = 3 · Vph · Iph · cos φ, or equivalently P = √3 · VL · IL · cos φ. Take S = √3 · VL · IL for the apparent power; reactive power then follows as Q = √(S² − P²). For motors, divide the shaft power by efficiency to find the electrical input.

Frequently asked questions

How do I calculate power in a three-phase circuit?
Multiply √3 by the line-to-line voltage, the line current and the power factor. In symbols P (W) = √3 × V_L × I_L × PF, valid when the load is balanced. Leave out PF and the product is apparent power S in VA.
Convert 32 A on three phases into kW.
A 400 V supply and a power factor of 0.9 give √3 × 400 × 32 × 0.9 = 19.95 kW, or 22.2 kVA. Were the power factor 1, the figure would be 22.2 kW. That is why one 32 A three-phase socket is enough for a 22 kW EV charger.
What is the line current for 22 kW on three phases?
Rearrange to I = P ÷ (√3 × V × PF). Take 400 V and PF 0.99: the charger pulls 32 A in every phase. Take 480 V and PF 0.9: the same 22 kW needs 29 A.
Star or delta: what changes?
In a star connection each winding runs from a line to the neutral point, so the winding voltage is V_L ÷ √3 (230 V on a 400 V network) while its current equals the line current. In delta each winding spans two lines: it takes the entire line voltage, and its current is I_L ÷ √3. Overall power does not change.
Phase voltage is 230 V, so why is the line voltage 400 V?
Because the phases are offset by 120°, the voltage measured between two lines is √3 ≈ 1.732 times a single phase voltage. 230 × 1.732 = 398 V, rounded to 400 V. The same logic gives 208 V from 120 V phases and 480 V from 277 V phases in North America.
Why do grids and factories use three phases?
Compared with single-phase at equal power and conductor size, three-phase carries √3 times more while needing only 1.5 times the conductors. Delivered power is constant instead of pulsing, and motors start and run without capacitors.

Sources & references

  1. IEC 60038 — IEC standard voltages
  2. Schneider Electric — Electrical Installation Guide (three-phase systems, power and current)
  3. IEC 60034-30-1 — Efficiency classes of line-operated AC motors (IE code)