Why simulate rather than guess
Of all the parts in a PV plant, the inverter is the one you deliberately buy smaller than the array. Nameplate output is a rarity, and an inverter sized exactly to the panels sits partly idle for years. The useful question is therefore how much energy a smaller unit would cut off, and whether the cheaper purchase makes up for it. Climate, orientation and module temperature all feed into that answer, which is why this page calculates it instead of quoting a rule.
For your location the tool retrieves one year of hourly NASA POWER weather and works out the array’s DC output hour after hour, covering sun position, the Hay–Davies sky model, incidence-angle losses, cell temperature and the DC losses you set. Each hourly value is pushed through every standard inverter size from a DC/AC ratio of 2.0 down to 0.8. Conversion efficiency is applied and output is limited to the rating. Whatever the cap removes is the clipping loss. The energy lost across the inverter’s lifetime is priced and weighed against what a smaller inverter saves at purchase.
Equations
Example: 8 kWp near Bucharest
The default setup is 8 kWp of TOPCon panels pointing south with a 30° tilt, 12% DC losses and a 97.5% efficient inverter. During 2024 the best single hour reaches about 6.5 kW, only 81% of nameplate, and 99% of the hours with production stay below 5.9 kW.
Fit a 6 kW inverter (DC/AC 1.33) and clipping is just 6 kWh a year (0.1%), leaving about 10,020 kWh, or 1,253 kWh per kWp. Go down to 5 kW (ratio 1.60) and 2.1% disappears, roughly 210 kWh yearly; at 4 kW the loss is 9.2%. Price the inverter at €120 per marginal kW, value energy at €0.15/kWh and assume a 12-year life, and 6 kW comes out as both the smallest low-loss choice and the best economic one. One caution: at 230 V single-phase that inverter carries 26 A, over the 16 A cap for single-phase generation in many grid codes. You may therefore need three-phase.
Interpreting the tool’s output
- Recommended inverter: the smallest standard rating with clipping of at most 0.5% of hourly energy, or the economic optimum when its clipping is 2% or less, subject to any grid limit entered.
- Clipping against DC/AC ratio: the curve is flat to about 1.3–1.4, then rises steeply; the bend is your site’s own.
- Hours at each loading: inverters rarely work near full power, and most of their hours are under 50% load.
- Lost value (NPV) next to inverter saving: the size table puts a price on the advice.
Typical ratios
| Situation | Typical DC/AC ratio | Expected clipping |
|---|---|---|
| South-facing, sunny, hot climate | 1.1–1.25 | < 1% |
| South-facing, central/northern Europe | 1.2–1.35 | < 1% |
| East–west roof, 10–15° tilt | 1.3–1.5 | < 1% |
| Utility single-axis tracking | 1.2–1.35 | 1–3% |
| Grid-capped home (e.g. 3.68 kW limit) | 1.3–1.7 | 0.5–5% |
| Battery-coupled hybrid (DC-coupled storage) | 1.4–2.0 | captured by battery |
Pointers
- Do not go below 1.0. It adds cost and pushes efficiency down at the light loads where an inverter spends most hours.
- East–west and steep roofs accept more. The two faces peak at different times, so neither gets full sun at once.
- Mind any grid cap. With export or inverter limits from the utility, extra DC is the cheapest way to harvest more under the cap, and a DC-coupled battery can store the portion that would be clipped.
- Check MPPT current. A large array on a small inverter may exceed a tracker’s input current. Use the string sizing calculator to confirm.
- Choose AC cable for peak inverter current, not average output, with the help of the cable size calculator.
Limitations
Averaging by the hour hides short spikes at cloud edges that can briefly push an array past its hourly peak. With one-minute data, studies find roughly 1.5–2× more clipping than hourly models at high DC/AC ratios. Efficiency is treated as constant, inverter derating in hot enclosures is absent, and the export-limit setting presumes a steady daytime house load. Only one weather year is used at a time; the weather-year option lets you test others.
Method & assumptions
A NASA weather year drives an hourly DC simulation of the array: sun position, Hay–Davies transposition, incidence and temperature losses, and your own DC losses. For each inverter size S being tested, the AC output of an hour is min(DC × η, S) and the excess over S is clipped. If you set an export limit, output is held to limit + house load.
For the economics, the energy lost with each smaller standard size is valued across the inverter's life (NPV at your discount rate) and set against the purchase saving per kW. The tool recommends the smallest standard size with clipping of 0.5% or less (hourly), or the economic optimum if that clips at most 2%, never exceeding a grid limit you enter.
Frequently asked questions
What inverter size suits my solar array?
What DC/AC ratio is reasonable?
What is clipping in a solar inverter?
How come panels rarely hit their nameplate power?
Do I want a single-phase or three-phase inverter?
Is a DC array bigger than the inverter acceptable?
Sources & references
- Good, J. & Johnson, J.X. (2016). Impact of inverter loading ratio on solar photovoltaic system performance. Applied Energy 177
- NREL — PVWatts Version 5 Manual (DC/AC ratio and inverter model), NREL/TP-6A20-62641
- Lawrence Berkeley National Laboratory — Utility-Scale Solar (inverter loading ratio trends)
- NASA POWER — hourly solar and meteorological data
Embed this calculator
Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.