Depth of discharge (DoD)

Percentage of a battery's capacity already drawn out; also the ceiling on that percentage which the manufacturer permits per cycle.

Depth of discharge mirrors state of charge: at 30% SoC a battery has a DoD of 70%. On a datasheet the term usually denotes the usable fraction of nominal capacity, which fixes the energy you can really draw.

DoD = 1 - SoC
Usable energy (kWh) = nominal capacity (kWh) x allowed DoD
Example: 10 kWh LFP battery at 90% DoD = 9 kWh usable

How deep a battery is cycled strongly shapes its cycle life. Lead-acid is usually kept to 50% DoD, since deeper cycling may leave only a few hundred cycles. Lithium-ion copes with 80–100% DoD, yet shallower use still helps: an NMC cell rated at 1,500 cycles for 100% DoD could manage several thousand at 50%. Total throughput (cycles x DoD x capacity) is a useful common yardstick, and modern LFP home batteries are often warranted for 30–40 MWh per 10 kWh unit.

Flow batteries tolerate 100% DoD with no degradation. To size a solar battery, divide the nightly energy requirement by DoD and by round-trip efficiency to obtain nominal capacity, as the solar battery calculator does.

Related terms

All terms →
  • State of charge (SoC)

    The charge left in a battery, shown as a percentage of its present full capacity.

  • Cycle life

    Number of complete charge and discharge rounds a battery completes before retaining only a set fraction, commonly 70–80%, of its rated capacity.

  • Lithium-ion battery

    A rechargeable cell whose lithium ions travel to and fro across an electrolyte, from a graphite anode to a phosphate or metal-oxide cathode and back; EVs and grid storage mostly use it.

  • Round-trip efficiency

    The portion of the energy fed into a storage system that comes back out on discharge, measured at a stated boundary (cell, DC side or AC grid connection).

  • C-rate

    Battery charge or discharge current expressed against capacity: at 1C a full battery empties in an hour, at 0.5C in two.