C-rate
Battery charge or discharge current expressed against capacity: at 1C a full battery empties in an hour, at 0.5C in two.
Expressing current as a multiple of capacity, the C-rate allows batteries of different sizes to be compared. A 100 Ah battery drained at 100 A runs at 1C, at 50 A at 0.5C (C/2), at 200 A at 2C. Storage systems apply it to power relative to energy.
Duration (h) ≈ 1 / C-rate
Example: 100 MW / 400 MWh BESS = 0.25C, a 4-hour system
High C-rates bring more resistive (I²R) heat and polarisation, so usable capacity shrinks and ageing speeds up. This is why datasheets state capacity and cycle life for a defined rate, usually 0.5C or 1C. Common operating points:
- Grid energy-shifting BESS: 0.25–0.5C, i.e. 2–4 hours
- Frequency regulation systems: 1–2C
- Domestic batteries: roughly 0.3–0.5C sustained
- EV fast charging: peaks of 2–4C on modern packs, tapering past about 60–80% SoC
Power-optimised cells trade energy density for thinner electrodes and more conductive additives; energy-optimised cells make the opposite trade. The battery C-rate parallels the power-to-energy ratio covered in power vs energy.
Related terms
All terms →- Power vs energy (kW vs kWh)
Power in kW is the flow of energy at one moment, while energy in kWh is power added up over time. Capacity is stated in power, and output in energy.
- Cycle life
Number of complete charge and discharge rounds a battery completes before retaining only a set fraction, commonly 70–80%, of its rated capacity.
- Depth of discharge (DoD)
Percentage of a battery's capacity already drawn out; also the ceiling on that percentage which the manufacturer permits per cycle.
- BESS (Battery Energy Storage System)
A full grid-connected or on-site battery plant: cells, battery management, power electronics, thermal management and control systems.
- DC fast charging
EV charging at high power where the rectifier sits in the station, not the car, so DC flows straight to the battery; usually 50–400 kW and up.