Round-trip efficiency
The portion of the energy fed into a storage system that comes back out on discharge, measured at a stated boundary (cell, DC side or AC grid connection).
Round-trip efficiency (RTE) is energy out on discharge divided by energy in on charge for one complete cycle. The boundary you pick changes the answer. A lithium-ion cell can manage 95–98% DC-to-DC, yet measured AC-to-AC at the grid connection, with inverter, transformer, cooling and standby loads included, it usually lands at 85–90%.
RTE ≈ η_charge x η_discharge
Example: 1 MWh charged at 88% RTE returns 0.88 MWh
Approximate AC round-trip figures for common technologies:
- Lithium-ion BESS: 85–90%
- Pumped hydro: 70–85%
- Vanadium flow battery: 65–80%
- Diabatic CAES: 40–55%; adiabatic designs target about 60–70%
- Hydrogen (electrolysis plus fuel cell or turbine): roughly 30–45%
Arbitrage profits hinge on this number. Take 85% RTE: the battery needs to sell at no less than 1/0.85, or about 1.18 times, the price it paid before it merely recovers its energy cost, not counting degradation. RTE also enters LCOS. Self-discharge gets its own figure: 1–3% per month for lithium-ion, which is low, but high for thermal stores.
Related terms
All terms →- LCOS (Levelized Cost of Storage)
Lifetime average cost for each MWh a storage asset discharges, covering investment, operation, charging electricity and efficiency losses.
- BESS (Battery Energy Storage System)
A full grid-connected or on-site battery plant: cells, battery management, power electronics, thermal management and control systems.
- Pumped hydro storage
A storage method that pumps water uphill to a reservoir when electricity is cheap or plentiful and sends it back through turbines when demand rises; worldwide, it is the biggest type of grid storage.
- Flow battery
A battery in which energy is kept in liquid electrolytes in outside tanks, so that power (set by the stack) and energy (set by tank size) can be scaled independently.
- Compressed air energy storage (CAES)
Energy storage in which surplus electricity compresses air into caverns or tanks, and the air later drives a turbine to generate power again.
- Long-duration energy storage (LDES)
Storage that can discharge at full rated power for about 8 hours or longer, bridging multi-day lulls and seasonal gaps that 2–4 hour batteries cannot cover.