Glossary · Grid & markets

Load following

Raising or lowering a power plant's output over minutes to hours so it follows electricity demand or the swings of variable renewable generation.

Load following falls between fast frequency regulation (seconds) and unit commitment (a day ahead). Three numbers describe a plant: ramp rate, minimum stable load and start-up time.

  • OCGT and gas engines ramp 10–25% of capacity a minute, with a 20–50% minimum load and 5–30 minute starts.
  • CCGT ramps 3–8% a minute, has a 30–50% minimum load and restarts hot in under an hour.
  • Hard coal ramps 1.5–6% a minute with a 25–40% minimum; lignite 1–4% a minute with a 35–50% minimum.
  • Nuclear (PWR/BWR) ramps 1–5% a minute between 50% and 100% power, limited late in the fuel cycle by xenon-135 transients.
  • Reservoir hydro and batteries respond almost instantly across their full range.
Required ramp (MW/h) = Δ(demand − wind − solar) / Δt

More variable renewables mean more demand for flexibility. On California's duck curve, the evening ramp tops 20 GW in three hours. In France, nuclear units follow load as a matter of routine, and some cycle every day between roughly 50% and 100%. Constant cycling adds wear, maintenance cost and heat rate; a coal plant at 50% load can lose 2–4 percentage points of efficiency. Storage, demand response and interconnectors are taking over more of this job.

Related terms

All terms →
  • Dispatchable generation

    Generation that the operator can schedule, ramp up or turn down on demand, whatever the weather.

  • Duck curve

    A pattern in grids with much solar: net load sags deeply at midday when PV output peaks, then ramps up sharply as evening approaches.

  • Combined-cycle gas turbine (CCGT)

    A plant in which a gas turbine's hot exhaust makes steam for a second, steam turbine, giving electrical efficiencies of 55–64%.

  • Variable renewable energy (VRE)

    Wind and solar PV power, whose production rises and falls with weather and daylight and cannot be fully scheduled by the operator.

  • Demand response

    Changes in end users' electricity use, prompted by price signals or operator requests, that help balance the grid.

  • Baseload

    Lowest electricity demand seen on a grid across a day, season or year, historically met by plants running nonstop at high output.