Glossary · Grid & markets

Dispatchable generation

Generation that the operator can schedule, ramp up or turn down on demand, whatever the weather.

A dispatchable source is one whose output an operator, at plant or system level, can start, stop, raise or lower on request, inside technical limits. Gas turbines, reservoir hydropower, coal, biomass, geothermal (partly), nuclear (with constraints) and battery or pumped storage with charge left all qualify.

Their agility differs a lot:

  • Reservoir hydro and batteries react within seconds to minutes across almost the whole range.
  • Open-cycle gas turbines take 5 to 15 minutes to start and gain 10 to 20% of capacity per minute.
  • Combined-cycle gas needs 30 to 60 minutes from a hot start and moves 2 to 5% per minute.
  • Hard coal changes 1 to 4% per minute and cannot drop below a 25 to 40% stable load.

(Ranges drawn from IEA and Agora Energiewende flexibility studies.)

Weather-driven variable renewables can be cut back but never pushed beyond what wind or sun allows, so they are non-dispatchable or only partly controllable. The more of them a grid has, the more dispatchable plants are valued for firm output during windless, sunless stretches (Germany calls them "Dunkelflaute") and for ancillary services. How much such plants add to adequacy is captured by capacity credit, typically 80 to 95% for thermal units.

Related terms

All terms →
  • Variable renewable energy (VRE)

    Wind and solar PV power, whose production rises and falls with weather and daylight and cannot be fully scheduled by the operator.

  • Baseload

    Lowest electricity demand seen on a grid across a day, season or year, historically met by plants running nonstop at high output.

  • Load following

    Raising or lowering a power plant's output over minutes to hours so it follows electricity demand or the swings of variable renewable generation.

  • Capacity credit

    Share of a resource's nameplate capacity that planners can rely on during peak demand, used in adequacy studies and capacity markets.

  • Ancillary services

    Products other than bulk energy that grid operators buy to keep the system stable and secure: frequency reserves, voltage support, black start and the like.

  • Combined-cycle gas turbine (CCGT)

    A plant in which a gas turbine's hot exhaust makes steam for a second, steam turbine, giving electrical efficiencies of 55–64%.