Reactive power
Power that cycles between supply and load with no net work done. Magnetic and electric fields depend on it, and so does voltage control.
Voltage and current in an AC circuit rarely peak at the same instant. Reactive power (Q), in volt-amperes reactive (var), is the portion that is stored and returned every cycle by inductive equipment (motors, transformers, overhead lines) or capacitive equipment (cables, capacitor banks). No net energy is consumed. Yet a motor or transformer cannot establish its magnetic field without it, and operators use it to steer voltage across the grid.
In these relations S stands for apparent power (VA), P for active power (W) and φ for the angle separating voltage and current. P divided by S is the power factor.
Grid voltage tracks the reactive balance. A network that absorbs vars sees voltage fall; one that injects them sees it rise. Long cables and lightly loaded lines generate vars, so night-time voltage can climb. Lines under heavy load swallow vars and may head for voltage collapse, which contributed to major blackouts such as France 1978 and North America 2003. Controlling overvoltage was likewise a core question in the inquiry into the 2025 Iberian blackout.
Equipment that supplies vars includes synchronous generators, synchronous condensers, static var compensators (SVCs), STATCOMs, shunt reactors, capacitors, and the inverters of modern wind, solar and battery plants. Europe's RfG grid code obliges new generators to operate within a defined power factor band, commonly about 0.90 to 0.95 lagging to leading. Vars lose their value over distance, so they must be delivered locally; system operators frequently contract them as an ancillary service.
Related terms
All terms →- Power factor
In an AC circuit, active power divided by apparent power: a number from 0 to 1 that shows how well the current does useful work.
- Ancillary services
Products other than bulk energy that grid operators buy to keep the system stable and secure: frequency reserves, voltage support, black start and the like.
- Transmission and distribution losses
Energy lost between generation and customers, partly as heat and partly from non-technical causes such as theft. It is generally stated as a share of energy supplied.
- Grid frequency
How many times per second alternating current reverses on a power system, 50 Hz or 60 Hz; it mirrors the moment-to-moment balance between supply and demand.
- HVDC (High-Voltage Direct Current)
Bulk power transmission using direct current, which loses less energy over long distances and can join grids that are not synchronised.
- Grid-forming inverter
An inverter that defines its own voltage and frequency, behaving like a voltage source; it can hold weak grids steady and provides synthetic inertia.