Hydro & marine calculator

Micro hydro: how much power, how much energy a year, and which turbine

Turns head and flow into kilowatts, monthly kWh and payback. It accounts for real penstock friction, turbine efficiency at part load, flow through the seasons and a residual (environmental) flow, and proposes a turbine type.

Editable share link Branded PDF report Free · no sign-up

Results

At 60 L/s design flow and 27.5 m net head the plant delivers 10.1 kW electrical, roughly 64,558 kWh over a year (capacity factor 73%). Best match among turbines: Cross-flow (Banki–Michell). Payback takes roughly 5 years.
Electrical output at design flow
10.1kW
Cross-flow (Banki–Michell) · overall η 57% water-to-wire
Annual energy
64,558kWh
177 kWh per day on average
Capacity factor
73.3%
6,420 full-load hours
Net head
27.5m
friction + minor loss 2.54 m (8.5%)
Design flow
60L/s
mean 60 L/s · residual 6 L/s
Hydraulic power (net)
16.2kW
gross 17.7 kW = ρgQH
Penstock velocity
1.91m/s
Re 293,849 · f 0.0149
Year-1 value
€9,684
Payback
4 yr 11 mo
capex 45,248 €
LCOE
0.063€/kWh
IRR 21.3%
CO₂ avoided per year
25.8t
Energy produced and stream flow by month
How well each turbine suits your site (score)

Choosing a turbine (net head, design flow)

TurbineHead range (m)Flow range (m³/s)Peak ηMin. flowFits your site
Cross-flow (Banki–Michell)2–2000.01–1072–80%15%✓ selected
Turgo10–3000.002–1078–85%15%✓
Pelton10–1,8000.001–5080–88%10%✓
Propeller / fixed-blade1.5–300.05–50078–88%70%✓
Francis10–7000.1–1,00084–92%40%—
Kaplan (double-regulated)1.5–400.3–1,00084–91%20%—
Archimedes screw1–100.1–1575–82%20%—

Monthly breakdown

MonthStream flow (L/s)Turbine flow (L/s)LoadPower (kW)Energy (kWh)
Jan8760100%10.17,107
Feb8460100%10.16,419
Mar7860100%10.17,107
Apr635795%9.636,586
May514575%7.755,477
Jun393355%5.683,882
Jul302440%4.072,874
Aug272135%3.532,496
Sep332745%4.63,149
Oct514575%7.755,477
Nov8160100%10.16,878
Dec9660100%10.17,107
  • Enter a long-term average flow. One reading taken in a wet month will greatly overstate the output.
  • Monthly flows follow a generic “Temperate rain-fed (winter high)” profile. Real streams fluctuate from day to day, so a flow-duration curve built from gauge records gives a better figure.
  • Your water authority sets the residual flow you must leave (often Q347, or 5–20% of mean flow). Permits, intake works and the grid connection tend to account for most of a small hydro project's cost.

Why head times flow is not enough

Falling water gives up energy in proportion to its mass and the height of the drop, so a quick estimate looks easy. That is exactly why simple calculators overshoot: they leave out penstock friction, seasonal flow and part-load turbine behaviour. This calculator accounts for all three.

Step What the tool does
1. Flow Takes your measured mean flow, or derives one from catchment area × rainfall × runoff coefficient. A residual (environmental) flow stays in the stream; the rest is shaped month by month by a seasonal pattern (rain-fed, snow-melt, monsoon, Mediterranean or spring-fed).
2. Net head Computes penstock friction with the Darcy–Weisbach equation and a Colebrook friction factor for your pipe’s material and diameter, then adds minor losses at the intake, bends and valves.
3. Turbine Rates Pelton, Turgo, cross-flow, Francis, Kaplan, propeller and Archimedes-screw machines against net head and design flow, and chooses the best fit unless you pick another. Each family has its own peak efficiency, part-load curve and minimum flow: a propeller turbine stops below about 70% of design flow, a Pelton runs on down to 10%.
4. Energy and money Multiplies monthly power × hours × availability, then goes on to payback, LCOE and IRR.

Formulas

P = ρ × g × Q × H_net × η_turbine × η_generator × η_drive

H_net = H_gross − f × (L / D) × v² / 2g − ΣK × v² / 2g Q_turbine,month = min(Q_design, Q_stream,month − Q_residual) E_year = Σ_months P_month × hours × availability

In these equations ρ is 1,000 kg/m³ and g is 9.81 m/s². At micro scale, turbines typically achieve 72–88%, generators 85–92% and the drive plus controls 95–97%, which leaves a water-to-wire efficiency of 55–75%.

Sample site: a farm stream

The presets model a stream averaging 60 L/s over 30 m of gross head, carried by 150 m of 200 mm HDPE pipe, with a temperate (winter-high) flow pattern and 10% of the flow left as residual.

Result Value
Pipe velocity 1.9 m/s
Head lost to friction and minor losses 2.5 m (8.5%), leaving 27.5 m
Best-rated turbine cross-flow (Turgo also suitable), peaking near 72% at micro scale
Power at 60 L/s design flow about 10 kW electrical, 57% water-to-wire
Yearly energy about 64,600 kWh (capacity factor 73%)
Cost at 4,500 €/kW about €45,000
Payback and LCOE at €0.15/kWh about five years; close to €0.06/kWh

Seasons shape output. In winter the turbine gets full flow, yet in late summer the stream carries under 30 L/s and power falls to about a third.

Reading the results

Output How to use it
Electrical power at design flow The nameplate rating to specify.
Annual energy and capacity factor The real worth of the site once seasons, residual flow and downtime are included.
Net head and penstock velocity If losses pass 10–15% or velocity goes above about 3 m/s, test a larger pipe in the penstock calculator.
Turbine suitability chart and table Show each family’s head and flow range; a tick means your site is inside it.
Monthly table Shows which months run at part load, and which fall below the turbine’s minimum flow so that it stops.

Turbine families at a glance

Part-load behaviour Peak efficiency (micro → large) Flow Net head Turbine
excellent, down to 10% flow 80–92% 1 L/s – 50 m³/s 10–1,800 m (best > 50 m) Pelton
very good 78–88% 2 L/s – 10 m³/s 10–300 m Turgo
flat curve, simple and rugged 72–85% 10 L/s – 10 m³/s 2–200 m Cross-flow
poor below ~40% flow 84–94% 0.1–1,000 m³/s 10–700 m Francis
good (double-regulated) 84–93% 0.3–1,000 m³/s 1.5–40 m Kaplan
needs > 70% flow 78–90% 0.05–500 m³/s 1.5–30 m Propeller
good, fish-friendly 75–85% 0.1–15 m³/s 1–10 m Archimedes screw

Tips for a better site

  • Survey at the driest time. Measuring in August with a bucket and stopwatch, a float or salt dilution tells you more than rainfall figures do.
  • Look for head, not length. Relocating the intake uphill often gains more head than the extra pipe loses to friction. Confirm it with the penstock calculator.
  • Pick the design flow deliberately. Design at the mean flow and utilisation stays high. Design at 1.3–1.5× the mean and winter energy rises, but more months run at part load.
  • Consider two units (or a multi-jet Pelton) if flow swings widely, so the dry months still get an efficient machine.
  • Keep the trash rack clean. Overnight, a clogged one can cost you several metres of head.

Limitations

The seasonal flow shapes are templates, not measurements. Gauged data, or the flow-duration curve of a similar gauged catchment, will be much more accurate. Daily variation also means that a monthly model overstates output slightly. If you estimate flow from the catchment, expect only about ±50%. Turbine ranges and efficiencies are published typicals, not a manufacturer’s hill chart. On cost, civil works, permits, fish passage and grid connection often dominate, and they reach the model only via your cost per kW.

Method & assumptions

Power: multiply the three efficiencies ηturbine · ηgenerator · ηdrive by ρ · g · Q · Hnet, with water density ρ = 1,000 kg/m³ and g = 9.81 m/s². Net head starts at the gross head and loses pipe friction (Darcy–Weisbach with a Colebrook friction factor from the pipe roughness) and minor losses (ΣK·v²/2g). For each turbine family, peak efficiency uses typical published values, lower for micro units (<100 kW), and part-load efficiency follows its own curve: Pelton and cross-flow hold steady, Francis drops quickly and propeller machines need >70% of design flow. No turbine runs below its minimum flow. Monthly flow is the mean flow × seasonal factor minus the residual flow, capped at the design flow, and yearly energy = Σ over months of monthly power × hours × availability.

Frequently asked questions

What is the hydro power formula?
The formula is P = ρ × g × Q × H × η, with ρ = water density (1,000 kg/m³), g = gravity (9.81 m/s²), Q = flow (m³/s), H = net head (m) and η = overall efficiency. Small schemes can use P (kW) ≈ 5 to 7 × Q (m³/s) × H (m) as a shortcut; it rests on a water-to-wire efficiency of 50–70%.
How much electricity can a small stream give?
Neither head nor flow can make up for the other. Drop 10 L/s through 50 m and you get about 3 kW electrical; drop the same 10 L/s through 5 m and you get just 0.3 kW. At 100 L/s and a 10 m fall the output is around 5–6 kW. Several homes could live on that, if the water keeps coming all year.
What type of hydro turbine suits my site?
It comes down to head and flow. High head with small flow suits impulse machines, namely a Pelton above about 50 m or a Turgo between roughly 10 and 300 m. For medium heads (3–100 m) and flows that vary, a cross-flow turbine copes well. With low head (under about 10–15 m) and large flow, pick a Kaplan, a propeller turbine or an Archimedes screw. Francis turbines take over the medium heads at larger scales.
Gross head or net head: which one do I use?
Use net head for power. Gross head is simply the vertical drop from the intake water surface to the turbine. Net head is what is left of gross head after penstock friction and losses at intake, bends and valves. A well-designed micro-hydro penstock loses 5–15% of gross head this way.
What should I budget for micro hydro?
Between about 2,000 and more than 10,000 per kW (EUR or USD). The final figure depends on head, civil works, pipeline length and the grid connection. High-head sites cost least per kW, as a small turbine and pipe already deliver the power.
Is a permit needed for micro hydro?
Almost certainly. Expect licences to abstract and impound water, fish-passage provisions and a minimum residual flow left in the stream. Ask your national environment or water agency what applies before spending on equipment.
What yearly energy does a micro hydro plant deliver?
Run-of-river plants produce around the clock. Capacity factors of 40–75% are therefore normal, well beyond what solar or wind manage. At 10 kW, annual output may reach 35,000–65,000 kWh, as long as the stream does not run dry in the dry season.

Sources & references

  1. ESHA — Guide on How to Develop a Small Hydropower Plant (European Small Hydropower Association)
  2. IRENA — Renewable Power Generation Costs in 2023 (hydropower chapter)
  3. Paish, O. (2002). Small hydro power: technology and current status. Renewable and Sustainable Energy Reviews 6(6)
  4. US Department of Energy — Planning a Microhydropower System

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.