Why it matters
Food plants, chemical works, paper and textile mills, refineries and hospitals all move heat as steam. Its price per tonne is the yardstick energy managers apply: it prices each steam user, tests projects like condensate return or an economiser, and sets one fuel against another or against going electric. The sum is a basic energy balance. Still, the boiler’s workload shifts with pressure, superheat, feedwater temperature and blowdown, so each deserves an input.
You supply steam conditions, fuel and its price, and the boiler’s efficiency. The tool answers with heat and fuel per tonne, cost per tonne, fuel burned per hour, yearly cost and CO₂, and the value of one extra efficiency point and of feedwater 10 °C warmer.
Equations
h_steam = h_g(p) + 2.1 × superheat h_fw = 4.19 × T_feedwater
Fuel per tonne = Q ÷ boiler efficiency ÷ fuel energy content Cost per tonne = fuel × price + water & treatment + CO₂ × carbon price
For saturated steam, h_g and h_f are read from the IAPWS-IF97 tables at absolute pressure (gauge plus 1.013 bar). Common pressures are tabulated under the results.
Walk-through with the presets
Starting point: 10 t/h, gas-fired, saturated steam at 10 bar(g), 90 °C feedwater, 4% blowdown, 88% efficiency, gas at 0.60 per m³ (9.6 kWh per m³ net).
- 10 bar(g) is 11 bar absolute. There, saturated steam has h_g ≈ 2,781 kJ/kg and condenses at 184 °C.
- Water at 90 °C holds 377 kJ/kg, which leaves 2,404 kJ to add per kg. Blowdown contributes 4% × (781 − 377) = 16 kJ/kg more.
- The total is 2.42 GJ per tonne, equal to 672 kWh.
- Efficiency of 0.88 raises that to 764 kWh of fuel, or 79.6 m³ of gas a tonne.
- Gas costs 79.6 × 0.60 = 47.7. Water and treatment at 1.5 bring it to 49.2 per tonne.
- Over 6,000 hours at 10 t/h, 60,000 t of steam cost about 2.95 million a year and emit 9,300 t of CO₂.
In this case each efficiency point is worth about 32,000 a year, while 10 °C of extra feedwater temperature is worth about 52,000. That second number explains why steam audits usually start with condensate return and economisers.
Typical values
| Item | Typical range |
|---|---|
| Heat per tonne (5–20 bar, saturated, 60–105 °C feedwater) | 650–750 kWh |
| Gas per tonne of steam | 70–85 m³ |
| Heavy fuel oil per tonne | 60–75 kg |
| Coal (25 GJ/t) per tonne | 105–125 kg |
| Wood chips (30% moisture) per tonne | 230–280 kg |
| Electricity (electrode boiler) per tonne | 660–760 kWh |
| Boiler efficiency, gas, with economiser | 90–94% (net) |
Where to find savings
- Condensate: returning more of it saves fuel, water and treatment chemicals. A rise of 6 °C in feedwater temperature gives roughly 1% less fuel.
- Economiser: captures stack heat for the feedwater, usually worth 3–5 points of efficiency on a gas boiler.
- Oxygen trim: stops excess air from carrying heat up the flue.
- Blowdown: recover its heat with a flash vessel and exchanger, and let automatic TDS control avoid needless discharge.
- Traps and insulation: a trap failed open or an uninsulated valve wastes steam you have paid for. Compressed air has comparable hidden losses, covered by the compressed air leak calculator.
- Pressure: lower it if the users can accept that; leak and radiation losses ease, though boiler heat barely changes.
Caveats
Everything above is measured at the boiler house outlet. By the time steam reaches a user, distribution losses (often 5–15%), failed traps and condensate that is not returned will have raised the price. Load also matters: low-load on/off cycling can leave a boiler several points below its rated efficiency. Keep fuel energy content and price on the same basis, which here is net calorific value. When the question is district or space heating, the heating cost comparison is the better tool.
Method & assumptions
Each tonne needs heat of (hsteam − hfeedwater) + blowdown × (hf,sat − hfeedwater). Enthalpies of saturated steam are read from IAPWS-IF97 tables at boiler pressure. Dividing heat by boiler efficiency and then by the fuel's energy content gives fuel per tonne. Cost per tonne is then fuel × price + water and treatment + CO₂ × carbon price.
Frequently asked questions
Steam cost per tonne: what goes into it?
How much heat is needed to raise one tonne of steam?
What is the gas consumption of a boiler per tonne of steam?
In what way does condensate return cut steam costs?
Which boiler efficiency figures are reasonable?
Is blowdown a loss of energy?
Sources & references
- IAPWS — Revised Release on the IAPWS Industrial Formulation 1997 (IF97) for water and steam
- US DOE — Improving Steam System Performance: A Sourcebook for Industry
- US DOE — Steam Tip Sheets (feedwater, blowdown, condensate return, economisers)
- IPCC 2006 Guidelines, Vol. 2 Energy — fuel CO₂ emission factors
Embed this calculator
Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.