Industry & business calculator

What does a tonne of steam cost? Fuel use and CO₂ included

Enter boiler pressure, superheat, feedwater temperature, blowdown and efficiency for a gas, oil, coal, biomass or electric boiler to get the price of a tonne of steam. Also shown: fuel per hour, yearly cost, CO₂ and what condensate return is worth.

Editable share link Branded PDF report Free · no sign-up

Results

Making a tonne of steam at 10 bar(g) takes 672 kWh of heat, equal to 79.6 m³ of fuel with a boiler at 88% efficiency. A tonne therefore costs 49.23 €, and running 10 t/h for 6,000 hours comes to 2,954,099 € per year. Warming the feedwater by a further 10 °C, say through more condensate return, would save about 51,581 € annually.
Cost per tonne of steam
49.23€/t
fuel 47.73 €/t
Heat per tonne
672kWh/t
2.42 GJ/t
Fuel per tonne of steam
79.6m³
Fuel per hour
796m³/h
Boiler heat output
6.72MW
Saturation temperature
184°C
steam enthalpy 2,781 kJ/kg
CO₂ per tonne of steam
154kg
Annual steam cost
3million €
60,000 t of steam per year
Annual CO₂
9,261t
Worth of one extra point of boiler efficiency
€32,181
per year
Value of +10 °C feedwater
€51,581
per year
Steam cost by feedwater temperature (€/t)
Steam cost by boiler efficiency (€/t)

Saturated steam properties

Pressure (bar g)Temperature (°C)h_f (kJ/kg)h_g (kJ/kg)Latent heat (kJ/kg)
099.94182,6752,257
2133.65622,7252,164
4151.96402,7482,108
6165.16972,7622,065
8175.27422,7732,030
101847812,7812,000
15201.28582,7921,934
20214.89202,7991,879
30235.61,0162,8031,787
40251.81,0942,8001,706
  • Saturated-steam properties are interpolated from the IAPWS-IF97 tables. For superheated steam, cp is taken as ≈ 2.1 kJ/kg·K; feedwater enthalpy equals temperature × 4.19 kJ/kg·K.
  • Efficiency and fuel energy have to share one basis (NCV here). Distribution losses, condensate losses and failed steam traps all raise the true cost of steam where it is used.

Why it matters

Food plants, chemical works, paper and textile mills, refineries and hospitals all move heat as steam. Its price per tonne is the yardstick energy managers apply: it prices each steam user, tests projects like condensate return or an economiser, and sets one fuel against another or against going electric. The sum is a basic energy balance. Still, the boiler’s workload shifts with pressure, superheat, feedwater temperature and blowdown, so each deserves an input.

You supply steam conditions, fuel and its price, and the boiler’s efficiency. The tool answers with heat and fuel per tonne, cost per tonne, fuel burned per hour, yearly cost and CO₂, and the value of one extra efficiency point and of feedwater 10 °C warmer.

Equations

Heat per tonne Q = (h_steam − h_fw) + blowdown × (h_f,sat − h_fw) (kJ/kg × 1,000)

h_steam = h_g(p) + 2.1 × superheat h_fw = 4.19 × T_feedwater

Fuel per tonne = Q ÷ boiler efficiency ÷ fuel energy content Cost per tonne = fuel × price + water & treatment + CO₂ × carbon price

For saturated steam, h_g and h_f are read from the IAPWS-IF97 tables at absolute pressure (gauge plus 1.013 bar). Common pressures are tabulated under the results.

Walk-through with the presets

Starting point: 10 t/h, gas-fired, saturated steam at 10 bar(g), 90 °C feedwater, 4% blowdown, 88% efficiency, gas at 0.60 per m³ (9.6 kWh per m³ net).

  1. 10 bar(g) is 11 bar absolute. There, saturated steam has h_g ≈ 2,781 kJ/kg and condenses at 184 °C.
  2. Water at 90 °C holds 377 kJ/kg, which leaves 2,404 kJ to add per kg. Blowdown contributes 4% × (781 − 377) = 16 kJ/kg more.
  3. The total is 2.42 GJ per tonne, equal to 672 kWh.
  4. Efficiency of 0.88 raises that to 764 kWh of fuel, or 79.6 m³ of gas a tonne.
  5. Gas costs 79.6 × 0.60 = 47.7. Water and treatment at 1.5 bring it to 49.2 per tonne.
  6. Over 6,000 hours at 10 t/h, 60,000 t of steam cost about 2.95 million a year and emit 9,300 t of CO₂.

In this case each efficiency point is worth about 32,000 a year, while 10 °C of extra feedwater temperature is worth about 52,000. That second number explains why steam audits usually start with condensate return and economisers.

Typical values

Item Typical range
Heat per tonne (5–20 bar, saturated, 60–105 °C feedwater) 650–750 kWh
Gas per tonne of steam 70–85 m³
Heavy fuel oil per tonne 60–75 kg
Coal (25 GJ/t) per tonne 105–125 kg
Wood chips (30% moisture) per tonne 230–280 kg
Electricity (electrode boiler) per tonne 660–760 kWh
Boiler efficiency, gas, with economiser 90–94% (net)

Where to find savings

  • Condensate: returning more of it saves fuel, water and treatment chemicals. A rise of 6 °C in feedwater temperature gives roughly 1% less fuel.
  • Economiser: captures stack heat for the feedwater, usually worth 3–5 points of efficiency on a gas boiler.
  • Oxygen trim: stops excess air from carrying heat up the flue.
  • Blowdown: recover its heat with a flash vessel and exchanger, and let automatic TDS control avoid needless discharge.
  • Traps and insulation: a trap failed open or an uninsulated valve wastes steam you have paid for. Compressed air has comparable hidden losses, covered by the compressed air leak calculator.
  • Pressure: lower it if the users can accept that; leak and radiation losses ease, though boiler heat barely changes.

Caveats

Everything above is measured at the boiler house outlet. By the time steam reaches a user, distribution losses (often 5–15%), failed traps and condensate that is not returned will have raised the price. Load also matters: low-load on/off cycling can leave a boiler several points below its rated efficiency. Keep fuel energy content and price on the same basis, which here is net calorific value. When the question is district or space heating, the heating cost comparison is the better tool.

Method & assumptions

Each tonne needs heat of (hsteam − hfeedwater) + blowdown × (hf,sat − hfeedwater). Enthalpies of saturated steam are read from IAPWS-IF97 tables at boiler pressure. Dividing heat by boiler efficiency and then by the fuel's energy content gives fuel per tonne. Cost per tonne is then fuel × price + water and treatment + CO₂ × carbon price.

Frequently asked questions

Steam cost per tonne: what goes into it?
Mainly fuel. Picture a boiler at 88% efficiency burning gas to turn 90 °C feedwater into 10 bar steam: that takes about 80 m³ of gas, or 765 kWh, per tonne. If gas is 0.60 per m³, the fuel bill is near 48, and water plus treatment add another 1–3. Per tonne, coal and biomass boilers typically come out cheaper, whereas electrode boilers are normally the most expensive option.
How much heat is needed to raise one tonne of steam?
Between 2.4 and 2.7 GJ (670–750 kWh) for saturated steam at 5–20 bar, assuming feedwater at 60–105 °C. The calculation starts from the total enthalpy of saturated steam, around 2,750–2,800 kJ/kg, and deducts the feedwater's own enthalpy at 4.19 kJ/kg per °C. What is left is the boiler's job.
What is the gas consumption of a boiler per tonne of steam?
Expect 70–85 m³ per tonne. The exact number moves with steam pressure, feedwater temperature and boiler efficiency. For a 10 t/h boiler, that translates to about 700–850 m³ of gas each hour.
In what way does condensate return cut steam costs?
Returned condensate is already treated and typically 80–95 °C. As a rule, fuel use falls about 1% for each 6 °C gained in feedwater temperature. Make-up water, chemical dosing and blowdown shrink as well when more condensate comes back.
Which boiler efficiency figures are reasonable?
On a net calorific basis, modern gas shell boilers deliver 85–89% bare and 90–94% fitted with an economiser; a condensing economiser raises that further. Oil and coal boilers of older design often manage only 75–82%, because stack temperatures are high, excess air is large and radiation losses are significant.
Is blowdown a loss of energy?
Yes, unless the heat is recovered. Blowdown discharges boiler water laden with dissolved solids, preventing scale and foaming. Since it leaves at saturation temperature, that heat goes down the drain without a flash vessel and heat exchanger. Typical rates run from 2% to 8% of steam flow.

Sources & references

  1. IAPWS — Revised Release on the IAPWS Industrial Formulation 1997 (IF97) for water and steam
  2. US DOE — Improving Steam System Performance: A Sourcebook for Industry
  3. US DOE — Steam Tip Sheets (feedwater, blowdown, condensate return, economisers)
  4. IPCC 2006 Guidelines, Vol. 2 Energy — fuel CO₂ emission factors

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.