Glossary · Grid & markets

Capacity factor

Actual energy a power plant generates in a period divided by what it would generate at full nameplate capacity throughout that period.

Capacity factor is the go-to indicator of how hard a generating asset works. It suits every technology from nuclear reactors to rooftop solar and is normally an annual figure.

CF = Eactual / (Prated × 8,760 h)

Worked case: a 100 MW wind farm delivering 350 GWh over a year gives CF = 350,000 / (100 × 8,760) = 40%. Re-stated in hours the result is the plant's full-load hours, 3,504 h.

Annual ranges by technology (sources: IRENA Renewable Power Generation Costs, NREL ATB, EIA):

  • Nuclear: 80–93%, with the US fleet over 90% in recent years (EIA)
  • Geothermal: 70–90%
  • Hydropower: 30–60%, depending greatly on water availability and on how the plant is dispatched
  • Onshore wind: 25–45%; globally, new projects average about 36–39% (weighted)
  • Offshore wind: 35–50% in recent North Sea projects
  • Utility solar PV: 10–30%, i.e. about 11–13% for fixed-tilt arrays in central Europe and 25–30% for single-axis trackers in deserts
  • Gas peakers (OCGT): frequently below 15%, because of economics instead of technical limits

The metric blends the resource with what the plant is used for. A dispatchable unit with a low value is typically run just when prices spike; for variable renewables the number mainly captures weather, curtailment and design choices such as the DC/AC ratio. Since it forms the denominator in LCOE, a halved capacity factor roughly doubles the capital share of each MWh's cost.

Related terms

All terms →
  • Full-load hours

    Annual energy output expressed as the number of hours a plant would have to run at full rated power to produce it; equal to capacity factor times 8,760.

  • LCOE (Levelized Cost of Electricity)

    The flat price per MWh that would repay every lifetime cost of a power plant, once costs and output are both discounted to present value.

  • Capacity credit

    Share of a resource's nameplate capacity that planners can rely on during peak demand, used in adequacy studies and capacity markets.

  • Curtailment

    Output that a wind or solar plant could have delivered but is ordered, or elects, not to, owing to network limits, market conditions or system-security needs.

  • Load factor

    Average demand divided by peak demand over a period; it shows how evenly a customer or a power system uses electricity.

  • Specific yield

    Yearly energy a PV system produces per unit of installed capacity, in kWh/kWp per year. It reflects both the solar resource and how well the system performs.