Reserve margin
How far available or accredited capacity sits above forecast peak demand, given as a percentage of that peak.
Planners use the reserve margin to judge resource adequacy: the cushion of firm capacity above the system's expected peak load.
Nameplate ratings do not go into the formula. Each plant is credited with what it can be relied on to produce at peak, known as its capacity credit. Typical credits: 10 to 30% of nameplate for wind, below 10% for solar at an evening peak, and 85 to 95% for thermal plants after forced outages.
In North America, NERC fixes reference margins by region, usually near 15% where thermal plants dominate, and issues a Long-Term Reliability Assessment every year. The 2024 report found elevated shortfall risk in over half the continent over the coming ten years, driven by plant retirements and new load from data centres and electrification. ERCOT has traditionally operated at about 10 to 15%.
As wind, solar and storage take larger shares, one fixed percentage looks too crude, and probabilistic indicators are replacing it:
- LOLE (loss of load expectation): for example 3 hours per year in Great Britain and France, or "1 day in 10 years" in many US systems.
- EUE (expected unserved energy), in MWh per year.
The European Resource Adequacy Assessment from ENTSO-E applies both across all bidding zones.
Related terms
All terms →- Peak load
The highest electricity demand a grid records over a given period; it fixes the capacity the system has to be able to deliver.
- Capacity credit
Share of a resource's nameplate capacity that planners can rely on during peak demand, used in adequacy studies and capacity markets.
- Capacity market
A scheme that pays resources for standing ready to supply power or cut demand during system stress, on top of payments for energy.
- Dispatchable generation
Generation that the operator can schedule, ramp up or turn down on demand, whatever the weather.
- Demand response
Changes in end users' electricity use, prompted by price signals or operator requests, that help balance the grid.
- Frequency response
The automatic shift in generation or demand that halts and then corrects a frequency drift following a sudden mismatch on the grid.