Heat rate
Fuel energy a thermal plant has to burn per kWh of electricity delivered; it is efficiency turned upside down, typically stated in BTU/kWh or kJ/kWh.
Here efficiency is flipped: the heat rate says how much fuel heat a thermal plant needs for each unit of electricity, so lower numbers are better. US power companies use it routinely, plant performance guarantees quote it, and fuel cost per MWh is calculated straight from it.
Heat rate (BTU/kWh) = 3,412 / η
Example: 6,400 BTU/kWh → 3,412 / 6,400 = 53.3% (HHV)
Fuel cost (USD/MWh) = heat rate (MMBtu/MWh) x fuel price (USD/MMBtu)
Full-load values from the US EIA, HHV basis:
- New CCGT plants reach 6,200–6,800 BTU/kWh, equal to 50–55% HHV or 56–62% LHV
- The US gas combined-cycle fleet averages about 7,500 BTU/kWh
- Open-cycle gas turbines need 9,500–11,500 BTU/kWh
- Coal steam units need 9,500–10,500 BTU/kWh; the fleet averages about 10,000 and supercritical plants about 8,700
- Nuclear stands at about 10,400 BTU/kWh thermal equivalent, or 33% efficiency
A plant at part load, during a start-up or in hot weather will show a higher, worse heat rate. This affects units that ramp up and down to balance variable renewables. A quoted figure should say whether output is gross or net of the plant's own consumption and whether HHV or LHV applies; calorific value covers the difference.
Related terms
All terms →- Calorific value (HHV / LHV)
Heat given off when a fixed amount of fuel burns completely; the higher (gross) value counts the condensation heat of water vapour, the lower (net) value leaves it out.
- Combined-cycle gas turbine (CCGT)
A plant in which a gas turbine's hot exhaust makes steam for a second, steam turbine, giving electrical efficiencies of 55–64%.
- MMBtu
A million British thermal units, equal to 1.05506 GJ or 293.07 kWh, and the common way gas and LNG are priced in the US and across Asia.
- BTU (British thermal unit)
Historic heat measure: roughly what it takes to warm 1 lb of water by 1 °F. Exactly, 1 BTU (IT) is 1,055.06 J.
- Open-cycle gas turbine (OCGT)
A simple-cycle gas turbine venting hot exhaust straight to the air: efficiency is low (33–42%), but it starts quickly and costs little to build, so it mostly serves peaks.
- CHP (Combined Heat and Power)
Producing electricity and usable heat together from a single fuel input, reaching 75–90% total efficiency, compared with about 35–60% for power-only plants.