Heating degree days (HDD)

Tallies how cold and for how many days the outdoor temperature stays under a chosen base, so heating demand can be estimated and compared across years.

For each day, heating degree days record how many degrees the outdoor temperature sits under a base value, the point where a building no longer needs heating; the daily figures are then summed. Base temperatures reflect internal and solar heat gains. Typical bases: 15.5 °C in the UK, 18 °C internationally, 65 °F in the US (about 18.3 °C), and Eurostat's approach, an 18 °C base with a 15 °C heating threshold.

HDD (daily) = max(0, T_base - T_mean)
Annual HDD = Σ daily HDD
Heat demand (kWh) ≈ H (W/K) x HDD x 24 / 1000
Example: H = 200 W/K, 3,000 K·days: 200 x 3,000 x 24 / 1000 = 14,400 kWh

In the formula, H is the heat loss coefficient of the building, combining fabric and ventilation losses. Annual totals at an 18 °C base are about 2,700–3,000 for London, 3,200 for Berlin, 3,000 for Bucharest, 4,400 for Helsinki, 1,800 for Madrid and over 7,000 for Fairbanks.

Typical jobs: weather-normalising consumption from one year to the next, checking progress against targets, sizing heating plant, and forecasting gas demand. The method is approximate, because internal gains in actual buildings shift with temperature and occupancy; an hourly simulation does better. With warming, global HDD is decreasing and cooling degree days are increasing. Better U-values mean less heat demand for every degree day.

Related terms

All terms →
  • Cooling degree days (CDD)

    A tally of how many degrees, and on how many days, outside air is warmer than a chosen reference temperature; it serves as a proxy for building cooling needs.

  • U-value

    A building element's heat-loss rate: watts passing through each square metre for every kelvin of temperature difference (W/m²K). Smaller values mean better insulation.

  • Heat pump

    Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.

  • Energy Performance Certificate (EPC)

    A standardised grade, usually A to G, for a building's calculated energy performance; the EU and UK demand one when a property is sold or let.

  • SCOP (Seasonal COP)

    Seasonal coefficient of performance (SCOP): a heat pump's average COP over a standard heating season, built from test points weighted by how often each outdoor temperature occurs.