Rate of change of frequency (RoCoF)

The speed, in hertz per second, at which grid frequency climbs or drops after a sudden imbalance; the less system inertia, the faster it moves.

A large plant trips, and frequency begins falling. The rate depends on how much generation was lost and on the inertia of the rotating machines connected. If RoCoF is high, protection relays may disconnect embedded generators, which makes things worse. Following the August 2019 blackout, Great Britain relaxed the loss-of-mains settings of small generators, from 0.125 Hz/s to 1 Hz/s.

Where inverter-based solar and wind supply much of the power, operators control RoCoF through synchronous condensers, grid-forming inverters and extremely fast battery response. See grid frequency and balancing.

Related terms

All terms →
  • Inertia (grid)

    Kinetic energy held in synchronously spinning generators and motors, which resists abrupt shifts in grid frequency.

  • Grid frequency

    How many times per second alternating current reverses on a power system, 50 Hz or 60 Hz; it mirrors the moment-to-moment balance between supply and demand.

  • Frequency response

    The automatic shift in generation or demand that halts and then corrects a frequency drift following a sudden mismatch on the grid.

  • Frequency containment reserve (FCR)

    Europe's quickest automatic balancing reserve, which reacts within seconds so that a frequency deviation stops growing.