SEER
A cooling-efficiency rating (Seasonal Energy Efficiency Ratio): seasonal cooling output over electricity consumed, in BTU/Wh in the US and W/W in the EU.
SEER appears on air conditioner and heat pump labels as the efficiency over a whole cooling season. The US and EU define it differently, so read the unit before comparing two figures.
- EU (EN 14825): W/W, with no dimension, weighted over a standard season of cooling.
- US (AHRI 210/240): BTU removed for each Wh consumed. The 2023 test revision brought in SEER2, with higher external static pressure, and the same machine rates roughly 4–5% lower on it than on the old SEER.
1 W = 3.412 BTU/h, so SEER (W/W) = SEER (BTU/Wh) / 3.412
Example: SEER 16 BTU/Wh ≈ 4.7 W/W
EER is the equivalent at one test point (95 °F / 35 °C outdoors)
In the US, split systems have had federal minimums of 13.4 SEER2 (north) and 14.3 SEER2 (south) since 2023, and premium inverter units exceed 20–25. Europe's A+++ cooling class begins at 8.5 W/W; good inverter splits score 6–9.
Estimate yearly electricity by dividing the season's cooling load by SEER. Load roughly follows cooling degree days. For heating, see SCOP (EU) and HSPF (US).
Related terms
All terms →- SCOP (Seasonal COP)
Seasonal coefficient of performance (SCOP): a heat pump's average COP over a standard heating season, built from test points weighted by how often each outdoor temperature occurs.
- COP (Coefficient of Performance)
How much useful heat (or cooling) a heat pump delivers per unit of electricity it uses, at one stated operating point.
- Cooling degree days (CDD)
A tally of how many degrees, and on how many days, outside air is warmer than a chosen reference temperature; it serves as a proxy for building cooling needs.
- Heat pump
Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.
- BTU (British thermal unit)
Historic heat measure: roughly what it takes to warm 1 lb of water by 1 °F. Exactly, 1 BTU (IT) is 1,055.06 J.