COP (Coefficient of Performance)
How much useful heat (or cooling) a heat pump delivers per unit of electricity it uses, at one stated operating point.
A COP states how much heat a heat pump or chiller moves for each unit of electricity at one set of test conditions, which makes it an instantaneous efficiency figure. With a COP of 3.5, every kWh of electricity yields 3.5 kWh of heat, and the surroundings supply the other 2.5 kWh. Values above 1 are why COP is not a thermodynamic efficiency and is not written as a percentage.
COP_cooling = Q_C / W (often expressed as EER)
COP_heating = COP_cooling + 1 (ideal cycle, same conditions)
Carnot: COP_H,max = T_H / (T_H - T_C) in kelvin
Source and sink temperatures drive the result. Under EN 14511 a test point such as A7/W35 means outdoor air at 7 °C and water leaving at 35 °C. A modern air-to-water machine typically reaches:
- A7/W35: 4.5–5.2
- A2/W35: 3.5–4.0
- A-7/W35: 2.6–3.0
- A7/W55: 2.8–3.3
Each 1 K cut in flow temperature adds roughly 2–3% to COP. A single point cannot represent a whole winter, so shoppers should look at SCOP or the seasonal performance factor (SPF). For running-cost estimates, try the ground-source heat pump calculator.
Related terms
All terms →- SCOP (Seasonal COP)
Seasonal coefficient of performance (SCOP): a heat pump's average COP over a standard heating season, built from test points weighted by how often each outdoor temperature occurs.
- Heat pump
Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.
- Air-source heat pump
A heat pump that pulls warm energy out of the outside air to heat rooms and water (air-to-water) or to blow warm air (air-to-air); the leading installed technology.
- Ground-source heat pump
A heat pump whose heat source is the ground, reached by buried loops or boreholes; constant soil temperature keeps its seasonal efficiency high.
- SEER
A cooling-efficiency rating (Seasonal Energy Efficiency Ratio): seasonal cooling output over electricity consumed, in BTU/Wh in the US and W/W in the EU.