Air-source heat pump
A heat pump that pulls warm energy out of the outside air to heat rooms and water (air-to-water) or to blow warm air (air-to-air); the leading installed technology.
The evaporator of an air-source heat pump (ASHP) is an outdoor coil with a fan. There are two families. Air-to-air machines, like split or multi-split air conditioners set to heat, warm the room air directly. Air-to-water machines heat a hydronic circuit for radiators, underfloor loops and a hot-water cylinder, so they can take the place of a boiler. Monobloc designs keep every part of the refrigerant circuit outside; split designs run refrigerant lines to an indoor hydraulic module.
Typical SCOP (35 °C, average EU climate): 4.0–5.0
Installed cost (EU/UK, 2024): roughly 8,000–15,000 EUR for a home
Cold weather hurts twice. The temperature gap to bridge widens, and in damp air under roughly 5 °C ice grows on the outdoor coil, so the unit periodically reverses to defrost, spending 5–10% of its energy doing so. Today's inverter-driven cold-climate models still manage a COP of about 2 at -15 °C and keep running to -25 °C or colder, which helps explain why Norway, Sweden and Finland have among the world's highest heat pump counts per household.
Versus ground-source heat pumps an ASHP is cheaper and simpler to fit, though its SCOP is lower and the outdoor unit emits 40–60 dB(A). Results depend on sizing to the design heat loss and on running the heating at low flow temperature.
Related terms
All terms →- Heat pump
Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.
- Ground-source heat pump
A heat pump whose heat source is the ground, reached by buried loops or boreholes; constant soil temperature keeps its seasonal efficiency high.
- COP (Coefficient of Performance)
How much useful heat (or cooling) a heat pump delivers per unit of electricity it uses, at one stated operating point.
- SCOP (Seasonal COP)
Seasonal coefficient of performance (SCOP): a heat pump's average COP over a standard heating season, built from test points weighted by how often each outdoor temperature occurs.
- Heating degree days (HDD)
Tallies how cold and for how many days the outdoor temperature stays under a chosen base, so heating demand can be estimated and compared across years.