Cooling degree days (CDD)

A tally of how many degrees, and on how many days, outside air is warmer than a chosen reference temperature; it serves as a proxy for building cooling needs.

Whenever the outdoor mean temperature rises above a chosen base, the excess is booked as cooling degree days (CDD). Bases in use are 18 °C, 21 °C (Eurostat works with a 24 °C threshold and a 21 °C base) and, in the US, 65 °F. The measure is the counterpart of heating degree days.

CDD (daily) = max(0, T_mean - T_base)
Annual CDD = Σ daily CDD
Cooling electricity (kWh) ≈ cooling load (kWh_th) / SEER

Rough yearly totals on an 18 °C base run from under 100 in London and about 500–700 in Madrid to about 1,600 in Houston (roughly 2,900–3,000 °F-days on the US 65 °F base), about 3,500–4,000 in Dubai and above 3,000–3,500 in Chennai and Singapore. Humid places need more cooling than dry-bulb temperature implies, which is why some studies switch to enthalpy- or humidity-adjusted degree days that include the latent (dehumidification) load.

The IEA's Future of Cooling report (2018) found that air conditioning and fans took about 2,000 TWh, roughly 10% of world electricity, and projected a near tripling by 2050 as India, Southeast Asia and Africa get richer and hotter. Because afternoon cooling peaks coincide with solar generation, the strain on peak load is partly offset. Shading and high-SEER equipment shrink demand further.

Related terms

All terms →
  • Heating degree days (HDD)

    Tallies how cold and for how many days the outdoor temperature stays under a chosen base, so heating demand can be estimated and compared across years.

  • SEER

    A cooling-efficiency rating (Seasonal Energy Efficiency Ratio): seasonal cooling output over electricity consumed, in BTU/Wh in the US and W/W in the EU.

  • Peak load

    The highest electricity demand a grid records over a given period; it fixes the capacity the system has to be able to deliver.

  • Heat pump

    Equipment that moves heat from a colder source (air, ground or water) into a warmer space via a refrigeration cycle, giving 2–5 units of heat per unit of electricity used.

  • U-value

    A building element's heat-loss rate: watts passing through each square metre for every kelvin of temperature difference (W/m²K). Smaller values mean better insulation.