Home energy guide

Home Insulation: U-Values, Costs and Payback

Compare loft, wall, floor, window and draught-proofing upgrades by U-value, cost per m² and payback, with step-by-step heat loss examples.

Updated 8 min read 1,728 words

Warmth always moves toward cold, through each wall, roof and floor and through every crack. Insulation reduces that flow; sealing the shell prevents warm air slipping out. Together they fix a building’s energy demand before you pick any boiler or heat pump. The European Commission attributes about 40% of EU final energy use and roughly a third of energy-related emissions to buildings, and most of those standing in 2050 exist already. Below you will find the physics, each measure priced in kWh and euros, and the places where money works hardest.

Basics: conductivity, resistance, U-value

Start with thermal conductivity λ (W/mK), which says how readily a material passes heat. For every layer in a wall or roof you can calculate thermal resistance R = thickness / λ. Sum the layers plus the surface films, invert the total, and you have the U-value; smaller numbers mean better insulation.

R_layer = d / λ U = 1 / (R_si + Σ R_layer + R_se)

Fabric heat loss (W) = Σ (U × A) × ΔT Annual heat loss (kWh) = Σ (U × A) × HDD × 24 / 1,000

HDD = heating degree days (K·day)

Heating degree days are a measure of climate severity. Rough values: 2,000–2,500 for London and Paris, 3,000–3,500 for Berlin, Warsaw or Bucharest, 3,500–4,000 for Stockholm or Toronto and above 4,500 for Helsinki or Minneapolis (base 15.5–18 °C, depending on the source).

U-values by building element

Building part As built, no insulation Late 20th century Current code (N & central Europe) Passive house
Brick wall, solid, 225 mm 1.6–2.1 — 0.15–0.28 ≤0.15
Cavity wall, empty 1.2–1.6 0.5–0.7 (filled) 0.15–0.28 ≤0.15
Roof / loft 2.0–2.5 (none) 0.3–0.6 0.10–0.20 ≤0.12
Solid ground floor 0.7–1.2 0.4–0.7 0.15–0.25 ≤0.15
Single glazing 4.8–5.8 — — —
Older air-filled double glazing 2.8–3.3 2.6–3.0 — —
Low-e double glazing with argon — — 1.1–1.4 —
Triple glazed units — — 0.6–0.9 ≤0.8 (whole window)

Insulation materials compared

Product λ (W/mK) Depth needed for wall U ≈ 0.20 Comment
Mineral wool (glass/rock) 0.032–0.040 160–200 mm Low price, fireproof, lets vapour through
EPS (expanded polystyrene) 0.031–0.038 150–190 mm Widespread on external wall systems
XPS 0.029–0.035 140–170 mm Moisture-resistant, good under floors and at edges
PIR / PUR boards 0.022–0.026 110–130 mm Thin but dearer; check fire regulations
Wood fibre 0.038–0.050 190–250 mm Keeps summer heat out, vapour open
Cellulose (blown) 0.037–0.042 185–210 mm Made from recycled paper; blown into lofts and timber frames
Aerogel blankets 0.013–0.018 65–90 mm Very costly, for cramped details
Vacuum insulated panels 0.004–0.008 25–40 mm Delicate, special uses only

The heat-loss budget

An uninsulated detached house from the 1960s loses its heat roughly as follows: the walls take 25–35%, the roof 20–25%, ventilation and leaks 15–25%, windows and doors 10–20% and the floor 10–15%. In flats, neighbouring homes shield the roof and floor, so those losses are much smaller. Thermal bridges at balconies, lintels and wall–floor junctions add another 5–15% in badly detailed buildings.

Which upgrade gives the best return

The prices below are rough Western European figures for 2024–2026; in Eastern Europe, expect 30–50% less. Savings are calculated for a house on gas at about €0.11/kWh delivered, in a climate of 3,000 HDD.

Upgrade U-value change Cost Typical heat saved Simple payback
Draught-stripping doors, windows and loft hatch — €200–600 1,000–2,500 kWh 2–5 years
Loft top-up, 100 → 300 mm 0.40 → 0.14 €15–30/m² 1,500–2,500 kWh 3–7 years
Loft, from nothing to 300 mm 2.3 → 0.14 €20–35/m² 6,000–14,000 kWh 1–3 years
Cavity wall fill 1.4 → 0.5 €15–30/m² 3,000–7,000 kWh 2–7 years
Hot water tank jacket & pipe lagging — €30–100 300–800 kWh <2 years
Suspended timber floor insulation 0.8 → 0.25 €30–60/m² 1,000–2,000 kWh 8–15 years
External wall insulation (solid walls) 1.8 → 0.25 €120–250/m² 7,000–13,000 kWh 15–35 years
Internal wall insulation 1.8 → 0.30 €80–150/m² 6,000–10,000 kWh 12–30 years
Double → triple glazing 2.8 → 0.8 €500–1,000/m² 1,500–3,000 kWh 30–60 years
Single → modern double glazing 5.0 → 1.2 €400–800/m² 3,000–5,000 kWh 15–30 years

Judged purely by energy savings, walls and windows are poor investments. Yet they are normally tackled during façade repairs or window replacement that was needed anyway, and then only the marginal cost of the better specification counts, so payback shrinks sharply. Comfort improves as well: no cold wall surfaces, draughts or condensation. The insulation savings calculator lets you model your own house.

Example: a loft in Germany

A 1970s bungalow in central Germany has 80 m² of loft floor with 60 mm of old mineral wool (U ≈ 0.55 W/m²K). The climate is 3,300 HDD, and the gas boiler runs at 88% seasonal efficiency with gas at €0.11/kWh.

Before: 0.55 × 80 × 3,300 × 24 / 1,000 = 3,485 kWh heat/year After (300 mm, U = 0.14): 0.14 × 80 × 3,300 × 24 / 1,000 = 887 kWh Saved heat: 2,598 kWh → gas saved: 2,598 / 0.88 = 2,952 kWh → €325/year

Installed at €22/m² (€1,760), the job repays itself in about 5.4 years, then keeps saving for 40+ more. The avoided CO₂ is 2,952 kWh × 0.202 kg/kWh ≈ 0.6 tonnes/year. Replace the boiler with a heat pump (SPF 3.2, €0.30/kWh) and the same loft job saves 812 kWh of electricity, or about €244 a year.

Degree-day estimates run high when a home has strong internal or solar gains. Measured savings usually land at 60–90% of the model, partly because residents spend part of the gain on warmer rooms (the “comfort take-back” or rebound effect).

Airtightness and ventilation

Once the fabric improves, air leakage takes a bigger share of the loss. A blower-door test gives the result as n50, meaning air changes per hour at 50 Pa, or as q50 in m³/h·m². Typical old houses reach n50 = 6–15, codes today ask about 3–5 where there is no mechanical ventilation, and passive houses need ≤0.6.

Ventilation heat loss (W) = 0.33 × n × V × ΔT

n = effective air changes per hour (≈ n50 / 20 for natural infiltration) V = heated volume (m³)

Example: a 400 m³ house improved from n50 = 10 to n50 = 4 sees infiltration fall from about 0.5 to 0.2 ACH, which is worth roughly 0.33 × 0.3 × 400 × 3,300 × 24 / 1,000 ≈ 3,100 kWh/year. Once a house is sealed it still needs fresh air, from trickle vents and extract fans at a minimum, or from mechanical ventilation with heat recovery (MVHR), which gives back 75–90% of the warmth in the exhaust.

Damp, mould and cold bridges

Insulation shifts the dew point within a wall, and mistakes cause condensation, rot and mould. Basic rules:

  • Control vapour on the warm face. Internal insulation goes with either a vapour control layer or a capillary-active, vapour-open product such as calcium silicate or wood fibre. Whichever you pick, no gap may remain behind it.
  • Let solid walls breathe. Old solid masonry frequently calls for lime-based, vapour-open systems.
  • Assess exposure first. On walls hit by driving rain, water may cross the cavity fill; a survey should test for it before you commit.
  • Treat junctions. Wrap insulation around window reveals and floor junctions to avoid cold spots where mould starts.
  • Leave vents alone. Keep air bricks beneath suspended floors and cold-roof vents clear.

How insulation helps a heat pump

The two work well as a pair. If design heat loss falls from 12 kW to 8 kW, a smaller heat pump will do (often €1,500–3,000 cheaper) and radiators can run cooler, which adds 10–20% to seasonal efficiency. You do not have to reach passive-house level; spending €50,000 or more on a deep retrofit buys less per euro than pairing a heat pump with the cheap measures. Try scenarios in the heat pump calculator, and see Heat Pumps Explained for background.

Grants and regulation

Europe has many support schemes. Germany runs the BEG programme and France MaPrimeRénov’; the UK has ECO and the Great British Insulation Scheme, Italy the Ecobonus, and EU states draw on Recovery and Resilience Plan money. EU law adds pressure. Its revised Energy Performance of Buildings Directive (2024) sets cuts in average residential primary energy use of 16% by 2030 and 20–22% by 2035, tackling the worst buildings first. Check what applies where you live on the country pages.

Mistakes that waste money

  • Squashing loft insulation. Mineral wool insulates by holding still air, so pressing it flat under storage boards can halve its performance. Use loft legs to raise the boards, or lay rigid boards over the joists.
  • Leaving gaps. A 5% hole in an insulation layer can push heat loss through that element up by 20–30%, since heat takes the easiest route. Fit batts snugly, stagger joints and seal around pipes and cables.
  • Forgetting the hatch and pipes. An unsealed, uninsulated hatch behaves like a chimney. With a cold loft, pipes and tanks up there then need frost protection.
  • No ventilation plan. Covering trickle vents, air bricks or eaves vents in the name of “keeping heat in” traps moisture. Decide how air will move before you insulate.
  • Overlooking summer overheating. Well-insulated homes with large south or west windows can get too hot. External shading, night ventilation and heavier insulation such as wood fibre or cellulose help.
  • Choosing by λ alone. A slim high-performance board is useful when space is short, but the cheapest route to a target U-value is usually a thicker layer of a cheaper material. Judge options on cost per m² for the target U-value, never on the price of a board.
  • Skipping inspection. Request photos before surfaces are covered and consider thermal imaging afterwards. Sloppy workmanship is the main reason actual savings miss the forecast.

Suggested order of work

  1. Survey. Book an energy audit that includes a blower-door test and cold-day thermal imaging, so leaks and weak spots are found.
  2. Quick and cheap. Draught-proof, insulate the loft, wrap the tank and pipes, and put reflector panels behind radiators on outside walls.
  3. Medium effort. Cavity filling, insulation under timber floors, secondary glazing.
  4. Piggyback on renovations. Time the work with repairs: external insulation with new render, internal insulation with replastering, new windows when the old fail, and good reveal detailing throughout.
  5. Heating last. Choose the heat pump size after the building has been improved.

Summary

Insulation pays for decades and has nothing to wear out. Airtightness and the loft come first, as they often pay back inside five years; walls and windows can wait until they need attention anyway. A quick estimate is U-value change × area × degree days. The insulation savings calculator and the heating cost comparison do it for your own house.

Calculators related to this topic

Frequently asked questions

Which insulation upgrade repays itself first?
Draught-proofing and loft (attic floor) insulation, typically within 2–6 years, with cavity wall fill not far behind. Solid wall insulation and new windows cut a great deal of energy, but each saved kWh costs more, so on energy savings alone they take 15–40 years.
What loft insulation depth is recommended?
The current advice in the UK and much of Europe is roughly 270–300 mm of mineral wool or similar, which delivers a U-value of about 0.15–0.16 W/m²K. Adding 200 mm to an existing 100 mm layer cuts loft heat loss by about two thirds.
What U-value should walls have?
Building codes for new homes in northern and central Europe usually require 0.15–0.28 W/m²K. Plain solid brick sits near 1.5–2.1 W/m²K, which means good insulation removes 80–90% of the heat flowing through it.
Does insulation lead to damp?
It can if the job is poor. Trouble comes from internal insulation lacking a vapour control layer, from blocked vents, and from cavity fill in walls exposed to driving rain, all of which lead to condensation and mould. A competent installer assesses moisture risk and keeps the house ventilated.
Do I need to insulate before fitting a heat pump?
Usually yes, at least with the low-cost measures. A tighter house needs a smaller heat pump, and one running at lower flow temperature works more efficiently. Reaching passive-house level first is not necessary.
Where does a house lose its heat?
In an average uninsulated detached house the floor accounts for 10–15% of losses, windows and doors for 10–20%, ventilation and draughts for 15–25%, the roof for 20–25% and the walls for 25–35%. Building shape and past upgrades shift these shares.

Sources & references

  1. IEA — Energy Efficiency 2024 and Buildings tracking report
  2. EN ISO 6946 — Building components and building elements: thermal resistance and thermal transmittance calculation method
  3. Energy Saving Trust — Home insulation guidance (UK)
  4. JRC — Energy renovation of buildings in the EU (European Commission Joint Research Centre)
  5. Passive House Institute — Building criteria

The figures in this guide are typical ranges taken from the listed sources, and your own values will vary with location, prices and equipment. For estimates specific to your site, use the linked calculators.