Industry & business calculator

Peak kW billing explained: demand charges, load factor and the savings from peak shaving

Breaks a commercial power bill into energy and demand parts, calculates load factor and the all-in price per kWh, applies a ratchet clause, and estimates the saving from cutting the peak with load control or a battery.

Editable share link Branded PDF report Free · no sign-up

Results

Load factor stands at 37%. You pay 6,750 € in demand charges (36% of the bill), so each kWh effectively costs 0.157 € instead of 0.1. Trimming 60 kW off the peak would save 900 € per month.
Effective price
0.157€/kWh
energy rate 0.1 €/kWh
Load factor
37%
average 164 kW vs peak 450 kW
Monthly bill
€18,850
Energy charges
€12,000
Demand charges
€6,750
450 kW billed
Demand share of bill
36%
Saving per month
€900
60 kW less peak
Saving per year
€10,800
Battery needed for this peak shaving
100kWh
60 kW for 1.5 h, 90% usable
Battery payback (demand savings only)
3.2years
battery about 35,000 €
Monthly bill with and without shaving (€)
Effective price against load factor (€/kWh)

Peak shaving options

Peak reduction (kW)New peak (kW)Saving (€/month)Battery (kWh)Saving (€/year)
23428338384,050
45405675758,100
683831,01311312,150
903601,35015016,200
1353152,02522524,300
  • Load factor assumes 730 hours a month. Tariffs vary: some bill the highest 15-minute peak, others 30 or 60 minutes, some only count on-peak hours, and many change by season.
  • Treat the battery size as a first estimate covering one daily peak. If peaks occur on multiple days or last beyond the duration entered, more energy is needed. Income from energy arbitrage or grid services is possible but excluded.

One ten-minute spike sets the month

A home buys kWh. A factory, office or shop buys kWh and also the peak power it reached, in kW or sometimes kVA. The meter averages over 15- or 30-minute windows and keeps the biggest. That one window decides the month’s demand charge.

Why? Cables, transformers and power plants must be built for the peak, however briefly it lasts. Where the peak is short and tall, demand charges can reach a third to two-thirds of the bill. This tool splits a bill into energy, demand and fixed parts, computes load factor and effective price per kWh, and puts a value on a lower peak, battery size included.

Formulas

Load factor LF = monthly kWh ÷ (peak kW × 730 h) Billed demand = max(actual peak, ratchet % × highest peak in last 12 months) Monthly bill = kWh × energy price + billed kW × demand charge + fixed charge Effective price = bill ÷ kWh = energy price + demand charge ÷ (LF × 730)

Peak-shaving saving = (billed kW before − billed kW after) × demand charge Battery energy ≈ kW reduction × peak duration ÷ 0.9 usable

Worked case

Preset: a factory on 120,000 kWh a month, 450 kW peak, 0.10 per kWh, 15 per kW-month, fixed charge 100.

  • LF works out at 120,000 ÷ (450 × 730) = 37%, because the average load of 164 kW is barely over a third of the peak.
  • Energy: 12,000. Demand: 450 × 15 = 6,750, or 36% of the 18,850 total.
  • Divide the total by the energy: 18,850 ÷ 120,000 = 0.157 per kWh, i.e. 57% higher than the energy rate.
  • Take 60 kW off the peak and you keep 900 a month, 10,800 a year.
  • A peak of around 1.5 hours calls for about 100 kWh of battery. At 350 per kWh (about 35,000) the demand savings alone recover it in about 3.2 years.

One preset exposes the ratchet. An EV depot on an 80% ratchet, with a 750 kW peak set earlier, pays for 600 kW whatever happens. Lowering this month’s peak from 600 to 450 kW changes nothing on the bill while the old peak is still in the window.

Benchmarks

Load factor, then demand’s share of the bill at 10–20 per kW-month:

  • 24/7 processes, data centres, cold stores: 70–90%; 15–25%.
  • Three-shift plants: 55–75%; 20–30%.
  • One-shift plants: 30–45%; 30–45%.
  • Offices and schools: 25–40%; 30–50%.
  • EV fast-charging hubs: 5–20%; 50–80%.

Interpreting results

  • Effective price is the true per-kWh cost after demand is spread over energy. Use it, not the energy rate, when valuing efficiency or solar.
  • Load factor below roughly 40% means demand charges dominate and peaks deserve attention.
  • Shaving table: what 5–30% peak cuts are worth. The first few percent usually come from scheduling at little cost, while going deeper takes storage.
  • Battery payback reflects demand savings alone. A battery that also soaks up solar or shifts energy to cheap hours earns more; try the time-of-use savings calculator and LCOS calculator.

How to flatten a peak

  • Pull interval data or fit a logger to learn when it occurs: a Monday start-up, a hot afternoon, a shift change.
  • Stagger compressors, chillers, ovens and furnaces after any shutdown.
  • Shed non-critical loads automatically near a preset limit.
  • If kVA is billed, improve power factor; the power factor correction calculator estimates the saving.
  • Take turns charging EV fleets rather than starting every vehicle together.

Caveats

Real tariffs vary: some bill demand only at peak hours, some change by season, some use coincident-peak charges, a contracted capacity with penalties above it, or kVA. Copy the structure from your own bill and treat the output as an estimate. Battery sizing presumes a single daily peak of the stated length, with no allowance for degradation or round-trip losses beyond the usable-capacity factor.

Method & assumptions

Load factor = monthly kWh ÷ (peak kW × 730 h). The bill has three parts: kWh × energy price, billed kW × demand charge and the fixed charge. Billed kW takes the larger of the actual peak and ratchet % × the highest peak over the last 12 months. Effective price per kWh = bill ÷ kWh = energy price + demand charge ÷ (load factor × 730). Cutting the peak saves billed kW reduction × demand charge, and the battery capacity needed is about kW reduction × peak duration ÷ 0.9 usable.

Frequently asked questions

What does a demand charge pay for?
A line on commercial bills that prices your single highest draw of the month, normally the peak 15- or 30-minute average, at so much per kW (or kVA). It recovers the cost of network and generation capacity built to meet that peak. Almost every commercial and industrial tariff has one, and at sites with short, sharp peaks it can take 30–70% of the bill.
How do I calculate load factor?
Divide the energy used by peak demand times the hours in the period. Picture a plant drawing 120,000 kWh over a month with a 450 kW peak: that is 120,000 ÷ (450 × 730) = 37%. Steady consumption pushes the ratio up and the effective price per kWh down.
How can demand charges be reduced?
Stop large loads starting at the same moment and stagger restarts after shutdowns. Push flexible loads such as pre-cooling, water heating and EV charging away from the peak, let a load controller drop non-critical equipment, or add a battery to shave the peak. Where demand is billed in kVA, a better power factor also helps.
How does a demand ratchet bite?
The contract sets a floor on billed demand, often 50–90% of the highest peak seen in the last 11 or 12 months. A single hot-summer spike therefore keeps bills elevated for a year, and peak shaving shows no benefit until that spike falls out of the window.
Does peak shaving with a battery pay off?
Possibly, when peaks are brief and the charge is steep (above roughly 10–15 per kW-month). To trim 60 kW for 1.5 hours you need around 100 kWh of storage. At 15 per kW-month that saves 10,800 a year, so the battery repays itself in roughly 3–5 years, depending on its price. Peaks that last longer or recur more often require a bigger battery.
Why does each kWh cost more than the energy rate?
Because the demand charge is spread across your consumption. Effective price = energy rate + demand charge ÷ (load factor × 730). At a 37% load factor and 15 per kW-month, that is an extra 0.056 per kWh on top of a 0.10 energy rate.

Sources & references

  1. US DOE / NREL — Identifying potential markets for behind-the-meter battery storage: demand charges
  2. US EIA — Electricity explained: factors affecting electricity prices
  3. OpenEI — U.S. Utility Rate Database (demand charge structures)
  4. IEA — Demand response

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.