What a poor power factor costs you
Magnetising current does no work, yet motors, transformers and fluorescent ballasts all need it, and it shuttles back and forth in the wiring. This reactive part (kVAr) loads each cable, switchboard and transformer on the path from generator to machine. Power factor (PF) compares useful kW with apparent kVA, as a fraction. Take PF 0.78: the line carries 28% more current than a resistive load of equal kW would need.
There are three ways a utility can bill for it:
- Peak demand measured in kVA rather than kW.
- Reactive energy (kVArh), once consumption passes a free allowance.
- A penalty surcharge if the monthly PF dips under a set limit, often 0.85 or 0.9.
A capacitor bank installed at the plant makes the reactive power on the spot, which keeps it away from the meter.
Equations
C per phase (delta) = Q_c ÷ (3 × 2πf × V_LL²) C per phase (star) = 3 × C_delta
S = P ÷ PF I = S ÷ (√3 × V_LL) Loss reduction = 1 − (PF1 ÷ PF2)²
A lookup table sits under the results. It lists the multiplier in kVAr per kW (tan φ1 − tan φ2) for common starting and target power factors, as capacitor catalogues do.
Example: a factory at PF 0.78
Start with a plant at 250 kW average and PF 0.78, 400 V, 50 Hz. Its monthly bill carries 12 per kVA of maximum demand.
| Quantity | Working | Result |
|---|---|---|
| Capacitor size | tan φ1 = 0.802, tan φ2 (PF 0.95) = 0.329, so 250 × 0.473 | 118 kVAr; next standard size is a 125 kVAr automatic bank |
| Delta capacitance | 118,400 ÷ (3 × 314.2 × 400²) | 785 µF per phase |
| Apparent power | 321 kVA down to 263 kVA | 57 kVA freed on the supply transformer |
| Current | 463 A down to 380 A | 83 A less |
| Demand charge | 57.4 kVA × 12 | 688 a month saved |
| Loss saving | 33% cut, 2% network losses, 0.15/kWh, 400 hours | about 98 a month |
| Payback | bank at 30 per kVAr costs 3,750 | about five months |
The two other presets bill differently. The first uses a reactive-energy tariff that allows tan φ = 0.4 free (a PF of about 0.93, a common European rule) and charges 500 kW at PF 0.82 for about 60,000 kVArh a month. The last applies a 1.5% surcharge on the bill for each 0.01 below PF 0.85, a scheme used by several Asian utilities, including TNB in Malaysia for many customer classes.
Power factors of common loads
| Load | Typical PF |
|---|---|
| Induction motor, full load | 0.80–0.90 |
| Induction motor, 50% load | 0.65–0.80 |
| Induction motor, idling | 0.10–0.30 |
| Welding transformer | 0.40–0.60 |
| Variable-speed drive (input) | 0.92–0.97 displacement, lower true PF with harmonics |
| LED lighting with good driver | 0.90–0.98 |
| Resistive heating | 1.0 |
Oversized, lightly loaded motors are the chief cause of poor PF in plants, so fitting motor size to the load helps as much as capacitors do. The motor energy savings calculator is the place for that.
Reading the results
- Capacitor required: the reactive power, in kVAr, that your average load calls for. The automatic bank you buy needs steps covering your lightest and heaviest load.
- Current after: the relief for cables and switchgear, which at times is enough to put off a transformer upgrade. Test it in the transformer sizing calculator.
- Tariff saving: set wholly by your billing method. If your bill has no kVA, kVArh or PF item, only the saving from lower losses is left.
- Simple payback: often below two years when you are charged for reactive power.
Model limits
The tool treats your plant as one average load. In practice load changes through the day, and the reactive charge follows integrated kVArh or peak kVA across the billing period. There is no harmonic model: where drives and inverters are many, plain capacitors may resonate, and the fix is a detuned bank or an active filter. Follow IEC 60831 or the local code for capacitor voltage rating, discharge resistors and protection. A plain kVA to kW conversion is quicker in kVA to kW.
Method & assumptions
Start from the reactive power to remove: Qc = P × (tan φ1 − tan φ2), with φ = arccos(PF). A delta-connected three-phase bank needs C = Qc ÷ (3 × 2πf × VLL²) per phase, and wiring the same bank in star calls for three times that capacitance. Line current is I = P ÷ (√3 × V × PF). Since losses track I², the saving in losses is 1 − (PF1/PF2)². What you save on the tariff then follows the billing method you choose.
Frequently asked questions
How do I find the kVAr needed to correct power factor?
How can I convert kVAr into microfarads?
Will power factor correction lower my power bill?
Which power factor is the right target?
By how much does correction reduce current?
At what point is a detuned capacitor bank required?
Sources & references
- IEC 60831-1 — Shunt power capacitors of the self-healing type for AC systems up to 1,000 V
- IEEE Std 1036 — Guide for the Application of Shunt Power Capacitors
- US DOE — Reducing Power Factor Cost (Motor Systems Tip Sheet #8)
- Schneider Electric — Electrical Installation Guide, chapter L: Power factor correction