Power plants & fossil calculator

Heat rate of a power station: from efficiency to Btu/kWh and fuel per MWh

Convert thermal efficiency into heat rate in Btu/kWh, kJ/kWh, kcal/kWh or GJ/MWh (LHV or HHV), or go the other way. Find the coal, gas, oil or biomass burnt per MWh and per year, the fuel bill and the CO₂ released.

Editable share link Branded PDF report Free · no sign-up

Results

Net efficiency of 55% (LHV) is the same as 6,874 Btu/kWh on an HHV basis, or 6,545 kJ/kWh on LHV. For each MWh you feed in 6.55 GJ of fuel, roughly 190 m³ (Natural gas); that costs 52.4 € and releases 0.367 t CO₂.
Heat rate (HHV)
6,874Btu/kWh
6,204 Btu/kWh on an LHV basis
Net efficiency (LHV)
55%
Net efficiency (HHV)
49.6%
Heat rate (LHV)
6,545kJ/kWh
1,563 kcal/kWh
Fuel energy per MWh (LHV)
6.55GJ/MWh
6.87 MMBtu/MWh HHV
Fuel per MWh (Natural gas)
190m³
Fuel cost per MWh
52.4€/MWh
CO₂ per MWh
0.367t
367 g/kWh
Annual generation
1,927GWh
Annual fuel use
365.6million m³
12.61 PJ of fuel
Yearly cost of fuel and carbon
101million €
Annual CO₂
0.71Mt
Heat rate against efficiency (LHV)
Usual net efficiency for each technology (LHV)

Heat rate in every unit

UnitLHV basisHHV basis
Btu/kWh6,2046,874
kJ/kWh6,5457,252
kcal/kWh1,5631,732
GJ/MWh6.5457.252
MMBtu/MWh6.2046.874

Typical technologies

TechnologyEfficiency (LHV)Heat rate (kJ/kWh, LHV)Heat rate (Btu/kWh, LHV)
Old subcritical coal33%10,90910,340
Supercritical coal39%9,2318,749
Ultra-supercritical coal44%8,1827,755
Lignite (modern)40%9,0008,530
Gas engine / recip44%8,1827,755
Aeroderivative OCGT40%9,0008,530
Heavy-duty OCGT37%9,7309,222
CCGT (F-class)57%6,3165,986
CCGT (H/J-class)62%5,8065,503
Oil steam plant36%10,0009,478
Diesel genset38%9,4748,979
Biomass steam30%12,00011,374
Nuclear LWR33%10,90910,340
  • To get the heat rate, divide 3,600 kJ/kWh (or 3,412 Btu/kWh) by the efficiency. Switching between HHV and LHV uses standard ratios per fuel: gas 1.108, bituminous coal 1.045, lignite 1.09, oil 1.06.
  • Default values from IPCC 2006 supply the calorific values and CO₂ factors. Your own fuel analysis will give other figures, most of all for coal and lignite.

Why engineers prefer heat rate

Efficiency gives a share, whereas heat rate gives an amount of fuel. Stand at the plant fence and ask how much fuel energy must come in for each kWh going out. At 7,000 Btu/kWh, a plant burns 7,000 Btu per kWh exported. One kWh equals 3,412 Btu, so 48.7% becomes electricity and the remainder leaves as heat via the condenser, cooling tower and stack.

Both numbers describe the same thing, but heat rate slots straight into fuel accounting. Multiply by output to get fuel burn, then by fuel price to get fuel cost per MWh. Hence “spark spreads” and “dark spreads” are built on heat rate, and utilities file heat rates with regulators.

Conversion runs in both directions across five units and both heating-value bases. The result is then turned into fuel quantity, cost and CO₂ for any plant size and capacity factor you enter.

Equations

Efficiency η = 3,600 ÷ HR (kJ/kWh) = 3,412.14 ÷ HR (Btu/kWh) = 860 ÷ HR (kcal/kWh)

η_HHV = η_LHV ÷ (HHV / LHV)

Fuel per MWh = HR (GJ/MWh, LHV) ÷ net calorific value CO₂ per MWh = HR (GJ/MWh, LHV) × emission factor (kg CO₂/GJ) Fuel cost = HR (GJ/MWh, LHV) × fuel price (per GJ)

Ratios of HHV to LHV in use: natural gas 1.108; bituminous coal 1.045; sub-bituminous coal and heavy fuel oil 1.06; lignite and wood 1.09. Calorific values and emission factors come from IPCC 2006 defaults: gas 56.1 kg CO₂/GJ, bituminous coal 94.6, lignite 101.

Same plant, two efficiencies

A single gas turbine may be advertised at 41% in Europe and 37% in a US filing, and both are right. What differs is the heating value: The gross figure, HHV, adds the latent heat of combustion-formed water vapour; the net figure, LHV, omits it. Because that vapour exits through the stack, LHV better reflects what the machine can achieve; IEA and European statistics follow that convention. In contrast, the US EIA and most American utilities report HHV heat rates.

Natural gas is hydrogen-rich, so the gap is wide: 55% on an LHV basis equals only 49.6% on HHV. Coal shows a small gap. Before comparing plants or countries, verify the basis.

Example calculation

Default case: a 400 MW gas combined-cycle plant, 55% net efficiency (LHV), 55% capacity factor, gas at €8/GJ.

  • Heat rate: 3,600 ÷ 0.55 = 6,545 kJ/kWh, equal to 6,204 Btu/kWh.
  • On the HHV basis efficiency is 55 ÷ 1.108 = 49.6%, giving 6,874 Btu/kWh HHV.
  • Each MWh takes in 6.55 GJ of gas, roughly 190 m³ at 34.5 MJ/m³.
  • Cost: 6.55 × 8 = €52.4/MWh. Emissions: 6.55 × 56.1 = 367 kg CO₂/MWh.
  • Annual totals: 1,927 GWh exported, about 366 million m³ of gas (12.6 PJ) used, 0.71 Mt of CO₂ released.

A coal variant is also built in. Select sub-bituminous coal with the US-style preset of 10,000 Btu/kWh HHV: the plant runs at 34% HHV (36% LHV), consumes about 0.53 t of coal and emits about 0.96 t CO₂ per MWh.

Heat rates by technology

Technology LHV net efficiency kJ/kWh heat rate (LHV) Btu/kWh, approx. HHV
CCGT, H/J-class, new 60–63% 5,700–6,000 6,000–6,300
CCGT, F-class 55–58% 6,200–6,550 6,500–6,900
Aeroderivative turbine, gas 38–42% 8,600–9,500 9,000–10,000
Open-cycle heavy-duty GT 34–38% 9,500–10,600 10,000–11,200
Coal, ultra-supercritical 42–45% 8,000–8,600 8,000–8,500
Coal, subcritical (older units) 31–36% 10,000–11,600 9,800–11,500
Light-water nuclear reactor 32–34% 10,600–11,200 ≈ 10,400 (EIA convention)

Fleet averages exceed the best-in-class numbers since plants cycle, run at part load and get old. EIA publishes an annual heat-rate table to cross-check US plants.

What the outputs mean

  • Heat rate (HHV) is shown first for US users; the LHV value (hint and table) suits IEA or European data.
  • Fuel per MWh is the amount a buyer must purchase, as m³ of gas or kg of coal.
  • Fuel cost per MWh equals short-run marginal cost excluding variable O&M and carbon. Compare it with market power prices to judge whether the plant would be dispatched.
  • CO₂ per MWh is fixed by heat rate and fuel type, so apart from fuel switching or carbon capture, efficiency is the only lever.

Caveats

A single heat rate is an average, since load, ambient and cooling-water temperature and plant age all shift it. Defaults for calorific value and CO₂ come from the IPCC; coal in particular varies widely, so use your own fuel analysis where possible. Whole-plant economics: LCOE calculator. Tonnes of coal: coal power plant calculator. Turbines at part load: gas turbine fuel consumption calculator.

Method & assumptions

Reciprocal relation: η = 3,600 ÷ heat rate (kJ/kWh) or, in Btu/kWh, η = 3,412.14 ÷ heat rate. A gap separates LHV and HHV efficiencies, bridged by the HHV/LHV ratio of the fuel: ηHHV = ηLHV ÷ (HHV/LHV). Burn per MWh: heat rate (GJ/MWh, LHV) divided by the NCV of the fuel. Emissions per MWh: GJ/MWh multiplied by an emission factor of kg CO₂/GJ (IPCC 2006). Annual numbers rest on net MW × 8,760 h × capacity factor.

Frequently asked questions

Heat rate meaning for a generating station?
Heat rate states how much fuel energy goes in per kWh exported (Btu/kWh or kJ/kWh), the reciprocal view of efficiency. A 7,000 Btu/kWh plant converts 3,412 ÷ 7,000 = 48.7% to electricity. The lower the figure, the better.
Turning a heat rate into an efficiency percentage?
Compute 3,412 ÷ (Btu/kWh) or 3,600 ÷ (kJ/kWh): 10,000 Btu/kWh is 34.1%, 6,500 kJ/kWh is 55.4%. One plant gives two numbers depending on whether the higher (HHV) or lower (LHV) heating value is used, so find out which applies.
HHV against LHV heat rates?
HHV credits the energy freed when flue-gas water vapour condenses; LHV ignores it. Stations rarely capture that latent heat, which is why IEA and European statistics adopt LHV and US EIA data adopts HHV. Natural gas reads about 10.8% higher on HHV, bituminous coal about 4–5% higher.
What counts as a good combined-cycle heat rate?
At full load, new H- and J-class plants achieve 60–63% LHV, i.e. 5,700–6,000 kJ/kWh (LHV) or roughly 6,000–6,300 Btu/kWh HHV. The US fleet of gas combined cycles averages near 7,500 Btu/kWh HHV, dragged up by older units, part-load running and starts.
Typical heat rate of coal-fired stations?
Older subcritical units burn 9,500–11,000 Btu/kWh HHV, an efficiency of 31–36%. Supercritical machines manage about 8,700–9,200 Btu/kWh. Top ultra-supercritical plants get to around 8,000 Btu/kWh, i.e. 42–45% LHV.
Fuel burned per MWh of output?
Heat rate (GJ/MWh) over calorific value gives fuel quantity. A 55%-efficient gas plant needs 6.55 GJ per MWh, about 190 m³ of natural gas, while a 38%-efficient coal plant needs 9.5 GJ per MWh, about 370 kg of bituminous coal at 25.8 GJ/t.

Sources & references

  1. US EIA — Average operating heat rate for selected energy sources (Electric Power Annual, table 8.1)
  2. IPCC 2006 Guidelines for National GHG Inventories, Vol. 2 Energy, ch. 1 (calorific values and CO₂ factors)
  3. IEA — Energy Statistics Manual (gross and net calorific values)
  4. IPCC AR5 WGIII Annex III — Technology-specific cost and performance parameters

Embed this calculator

Free for bloggers, installers, schools and NGOs. Copy the snippet below and it stays current by itself.