Why engineers prefer heat rate
Efficiency gives a share, whereas heat rate gives an amount of fuel. Stand at the plant fence and ask how much fuel energy must come in for each kWh going out. At 7,000 Btu/kWh, a plant burns 7,000 Btu per kWh exported. One kWh equals 3,412 Btu, so 48.7% becomes electricity and the remainder leaves as heat via the condenser, cooling tower and stack.
Both numbers describe the same thing, but heat rate slots straight into fuel accounting. Multiply by output to get fuel burn, then by fuel price to get fuel cost per MWh. Hence “spark spreads” and “dark spreads” are built on heat rate, and utilities file heat rates with regulators.
Conversion runs in both directions across five units and both heating-value bases. The result is then turned into fuel quantity, cost and CO₂ for any plant size and capacity factor you enter.
Equations
η_HHV = η_LHV ÷ (HHV / LHV)
Fuel per MWh = HR (GJ/MWh, LHV) ÷ net calorific value CO₂ per MWh = HR (GJ/MWh, LHV) × emission factor (kg CO₂/GJ) Fuel cost = HR (GJ/MWh, LHV) × fuel price (per GJ)
Ratios of HHV to LHV in use: natural gas 1.108; bituminous coal 1.045; sub-bituminous coal and heavy fuel oil 1.06; lignite and wood 1.09. Calorific values and emission factors come from IPCC 2006 defaults: gas 56.1 kg CO₂/GJ, bituminous coal 94.6, lignite 101.
Same plant, two efficiencies
A single gas turbine may be advertised at 41% in Europe and 37% in a US filing, and both are right. What differs is the heating value: The gross figure, HHV, adds the latent heat of combustion-formed water vapour; the net figure, LHV, omits it. Because that vapour exits through the stack, LHV better reflects what the machine can achieve; IEA and European statistics follow that convention. In contrast, the US EIA and most American utilities report HHV heat rates.
Natural gas is hydrogen-rich, so the gap is wide: 55% on an LHV basis equals only 49.6% on HHV. Coal shows a small gap. Before comparing plants or countries, verify the basis.
Example calculation
Default case: a 400 MW gas combined-cycle plant, 55% net efficiency (LHV), 55% capacity factor, gas at €8/GJ.
- Heat rate: 3,600 ÷ 0.55 = 6,545 kJ/kWh, equal to 6,204 Btu/kWh.
- On the HHV basis efficiency is 55 ÷ 1.108 = 49.6%, giving 6,874 Btu/kWh HHV.
- Each MWh takes in 6.55 GJ of gas, roughly 190 m³ at 34.5 MJ/m³.
- Cost: 6.55 × 8 = €52.4/MWh. Emissions: 6.55 × 56.1 = 367 kg CO₂/MWh.
- Annual totals: 1,927 GWh exported, about 366 million m³ of gas (12.6 PJ) used, 0.71 Mt of CO₂ released.
A coal variant is also built in. Select sub-bituminous coal with the US-style preset of 10,000 Btu/kWh HHV: the plant runs at 34% HHV (36% LHV), consumes about 0.53 t of coal and emits about 0.96 t CO₂ per MWh.
Heat rates by technology
| Technology | LHV net efficiency | kJ/kWh heat rate (LHV) | Btu/kWh, approx. HHV |
|---|---|---|---|
| CCGT, H/J-class, new | 60–63% | 5,700–6,000 | 6,000–6,300 |
| CCGT, F-class | 55–58% | 6,200–6,550 | 6,500–6,900 |
| Aeroderivative turbine, gas | 38–42% | 8,600–9,500 | 9,000–10,000 |
| Open-cycle heavy-duty GT | 34–38% | 9,500–10,600 | 10,000–11,200 |
| Coal, ultra-supercritical | 42–45% | 8,000–8,600 | 8,000–8,500 |
| Coal, subcritical (older units) | 31–36% | 10,000–11,600 | 9,800–11,500 |
| Light-water nuclear reactor | 32–34% | 10,600–11,200 | ≈ 10,400 (EIA convention) |
Fleet averages exceed the best-in-class numbers since plants cycle, run at part load and get old. EIA publishes an annual heat-rate table to cross-check US plants.
What the outputs mean
- Heat rate (HHV) is shown first for US users; the LHV value (hint and table) suits IEA or European data.
- Fuel per MWh is the amount a buyer must purchase, as m³ of gas or kg of coal.
- Fuel cost per MWh equals short-run marginal cost excluding variable O&M and carbon. Compare it with market power prices to judge whether the plant would be dispatched.
- CO₂ per MWh is fixed by heat rate and fuel type, so apart from fuel switching or carbon capture, efficiency is the only lever.
Caveats
A single heat rate is an average, since load, ambient and cooling-water temperature and plant age all shift it. Defaults for calorific value and CO₂ come from the IPCC; coal in particular varies widely, so use your own fuel analysis where possible. Whole-plant economics: LCOE calculator. Tonnes of coal: coal power plant calculator. Turbines at part load: gas turbine fuel consumption calculator.
Method & assumptions
Reciprocal relation: η = 3,600 ÷ heat rate (kJ/kWh) or, in Btu/kWh, η = 3,412.14 ÷ heat rate. A gap separates LHV and HHV efficiencies, bridged by the HHV/LHV ratio of the fuel: ηHHV = ηLHV ÷ (HHV/LHV). Burn per MWh: heat rate (GJ/MWh, LHV) divided by the NCV of the fuel. Emissions per MWh: GJ/MWh multiplied by an emission factor of kg CO₂/GJ (IPCC 2006). Annual numbers rest on net MW × 8,760 h × capacity factor.
Frequently asked questions
Heat rate meaning for a generating station?
Turning a heat rate into an efficiency percentage?
HHV against LHV heat rates?
What counts as a good combined-cycle heat rate?
Typical heat rate of coal-fired stations?
Fuel burned per MWh of output?
Sources & references
- US EIA — Average operating heat rate for selected energy sources (Electric Power Annual, table 8.1)
- IPCC 2006 Guidelines for National GHG Inventories, Vol. 2 Energy, ch. 1 (calorific values and CO₂ factors)
- IEA — Energy Statistics Manual (gross and net calorific values)
- IPCC AR5 WGIII Annex III — Technology-specific cost and performance parameters