Glossary · Solar

String (PV)

A series connection of PV modules, in which the voltages are added and the current equals that of one module.

Wiring modules in series brings voltage up to a level where the inverter is efficient and the cables lose little. The voltage of each module is added along the string, but the current does not change. Take 20 modules, each with a maximum power voltage of 40 V: the string runs close to 800 V. Strings can be paralleled afterwards at a single MPPT input or combiner box.

The number of modules is limited from above and below, and both limits depend on temperature:

Nmax = Vmax,inv / [Voc · (1 + βVoc · (Tmin − 25))]     Nmin = VMPPT,min / [Vmp · (1 + βVmp · (Tcell,max − 25))]

β is the voltage temperature coefficient, around −0.25 to −0.30 %/°C. Cold weather lifts open-circuit voltage above the STC value, so the coldest hour decides the upper limit: 600 V for North American homes, 1,000 V for European homes and commercial sites, 1,500 V for utility plants. Heat lowers voltage, so the hottest day decides the lower limit, which is the inverter's minimum MPPT voltage.

The shared current means the weakest module sets the pace. Shade, dirt or a damaged cell on one module pulls the others down, unless bypass diodes conduct. For this reason, roof sections facing different directions are assigned separate MPPT inputs or fitted with power optimisers or microinverters.

Related terms

All terms →
  • DC/AC ratio

    The inverter loading ratio (ILR): the array's STC nameplate DC capacity relative to the inverter's AC rating.

  • String inverter

    A PV inverter that takes the DC from one or several module strings in series and delivers AC in step with the grid. It usually has multiple MPPT inputs that work independently.

  • Bypass diode

    Diode connected across a section of cells in a PV module so string current can bypass shaded or damaged cells, which averts hot spots.

  • MPPT (Maximum Power Point Tracking)

    Software in an inverter or charge controller that constantly tunes the operating voltage to pull the most power out of a PV array.

  • Temperature coefficient

    How much a PV module's power, voltage or current changes, in percent, for each degree Celsius its cells sit above or below 25 °C.