DC/AC ratio

The inverter loading ratio (ILR): the array's STC nameplate DC capacity relative to the inverter's AC rating.

This ratio compares the module capacity installed with the inverter capacity that serves it. Pair a 1.3 MWp array with a 1.0 MWac inverter and the figure is 1.3.

ILR = PDC,STC (kWp) / PAC,rated (kW)

Designers go above 1 deliberately, since modules almost never output their STC rating: sunlight is below 1,000 W/m² for most hours, cells run hotter than 25 °C, and wiring, dirt and ageing cost further output. A larger array keeps the inverter, transformer and grid link busy for more hours, which raises the AC-based capacity factor but brings some clipping.

Typical values:

  • Residential rooftop: 1.0–1.3, bounded by inverter models and export limits.
  • US utility-scale: new projects have a median of about 1.3 (Lawrence Berkeley National Laboratory, Utility-Scale Solar reports), with fixed-tilt above tracking plants.
  • Grid-limited or PV-plus-storage plants: 1.4–1.6 or more.

As modules become cheaper compared with inverters and grid connection, the best ratio rises. It is higher under cloudy skies and for east-west layouts, where peak output is seldom reached, and lower for single-axis trackers in sunny regions, where output stays close to peak for longer. Since capacity factor may be stated on a DC or an AC basis, a fair comparison between plants needs the DC/AC ratio.

Related terms

All terms →
  • Inverter clipping

    Energy lost when a PV array can produce more DC power than the inverter's AC rating, so the inverter limits output to its maximum.

  • String inverter

    A PV inverter that takes the DC from one or several module strings in series and delivers AC in step with the grid. It usually has multiple MPPT inputs that work independently.

  • Capacity factor

    Actual energy a power plant generates in a period divided by what it would generate at full nameplate capacity throughout that period.

  • Kilowatt-peak (kWp)

    How a PV module or array is rated in DC watts at Standard Test Conditions, and the customary measure of installed solar capacity.

  • String (PV)

    A series connection of PV modules, in which the voltages are added and the current equals that of one module.