A grid-tied array can be sized for an average year, because the grid covers any weak December without anyone noticing. With no grid, the question changes. You are no longer asking how many kWh the roof makes in a year. You are asking what the system does on the fifth overcast day in a row, during the darkest week of the year. A flat battery means a tripped inverter and cells that wear out sooner. What follows is the routine professional designers use: a load audit, sizing for the worst month, battery autonomy and a backup plan, with figures you can compare with your own site.
1. Audit what you actually use
Every later number rests on daily energy use in watt-hours. Too high and you overspend; too low and you live in the dark. Write down each appliance, its power and its daily running hours.
| Appliance | Power (W) | Hours/day | Wh/day |
|---|---|---|---|
| LED lighting (8 lamps) | 6 each | 4 | 190 |
| Efficient fridge-freezer (A-class) | — | — | 400–700 |
| Laptop + router + phone charging | 60 | 6 | 360 |
| Water pump (pressurised) | 600 | 0.5 | 300 |
| Washing machine (cold wash) | — | 1 cycle | 400–600 |
| TV (LED, 43”) | 60 | 3 | 180 |
| Inverter standby | 15–40 | 24 | 360–960 |
| Total | ≈ 2,200–3,300 |
Two entries surprise most beginners. One is the inverter itself: a 3–5 kW unit may idle at 20–40 W all day and night, or 0.5–1 kWh daily, up to a quarter of a small cabin’s consumption. Choose a model with low no-load consumption or a search/eco mode. The other is the fridge, which never stops and works harder in a warm room; divide the label’s annual kWh by 365.
Resistive heating elements do not belong on the system: kettles, ovens, hair dryers, immersion heaters, electric room heaters. Six hours of a 2 kW heater is 12 kWh, which an average off-grid home may need two days to use. Rely on gas, wood or a properly sized heat pump. To convert nameplate ratings to daily Wh, use the energy unit converter.
2. Size the panels for the weakest month
Away from the tropics, solar supply swings sharply with the seasons. A south-facing panel in central Europe gathers about 5–8 times as much in June as in December; close to the equator, the ratio is nearly 1. The design month for year-round use is usually December in the northern hemisphere and June in the southern.
Grid-tied plants reach 0.75–0.85. Off-grid ones lose more, since energy cycles through a battery and whatever a full battery cannot absorb on a sunny day is thrown away.
Steep panels favour winter. Tilting at latitude plus 10–20° raises December output and lowers summer yield, which an off-grid home cannot use anyway. For winter-weighted designs, the solar tilt angle calculator suggests an angle. The EU’s PVGIS (JRC) also simulates off-grid operation and states how often the battery would be empty.
Sun hours in the design month (tilted array)
| Location type | Worst-month PSH | Array needed for 3 kWh/day (PR 0.6) |
|---|---|---|
| Northern Europe (UK, Germany, Poland) | 0.8–1.5 | 3.3–6.3 kWp |
| Southern Europe (Spain, Italy, Greece) | 2.5–3.5 | 1.4–2.0 kWp |
| Sub-Saharan Africa, India | 4.0–5.5 | 0.9–1.3 kWp |
| Desert southwest US, Australia | 4.0–5.5 | 0.9–1.3 kWp |
Treat these as ranges; cloud climate, snow and shading at your horizon change them a lot. The northern Europe row explains why homes there often accept a generator in December and January rather than a triple-size array.
3. Battery bank and days of autonomy
Autonomy means how many days the battery can supply the house with zero solar input. It is your cushion for a long overcast spell.
- Days of autonomy: 1–2 where a generator exists or the climate is sunny, 3–5 for isolated homes with no backup.
- Depth of discharge you can use: LFP 80–95%; lead-acid about 50% if you want a decent lifespan.
- Efficiency in and out: LFP 92–96%, lead-acid 75–85%.
- Temperature: lead-acid gives up 10–25% of its capacity near 0 °C, and LFP must not be charged below 0 °C without a heater.
Most new installations now use lithium iron phosphate rather than lead-acid. It costs more per nominal kWh to buy, yet yields far more over its life: 3,000–8,000 deep cycles against a few hundred to about 1,500 for typical lead-acid banks at 50% depth. Counted per delivered kWh, LFP is usually well ahead. The home battery storage guide explains the chemistries.
4. Choosing the inverter and charge controller
Inverter rating. Add the loads that may run simultaneously, then include a 25–50% margin. Check surge capacity as well: well pumps, fridge compressors and power tools can demand 3–6 times their running power at start-up. A pure sine wave unit is needed for modern electronics and motors.
System voltage. A higher voltage cuts current and cable losses. Roughly, use 12 V up to about 1 kW, 24 V up to 2–3 kW and 48 V above. A 3 kW load at 12 V pulls 250 A and needs thumb-thick cable, while at 48 V the current is about 63 A.
Charge controller. An MPPT unit holds the panels at their best operating point and converts surplus voltage into charge current. It also permits long high-voltage series strings, handy when the array is far from the batteries. Give it a current rating of array power ÷ battery voltage plus 25%, and check that the string’s open-circuit voltage on a cold day (rising roughly 0.3%/°C below 25 °C) remains below the controller’s maximum input.
“All-in-one” off-grid units fold the inverter, MPPT controller and generator charger into a single box. Wiring gets simpler, though one fault can then stop the whole system.
Worked example: turning a Czech cabin into a full-time home
Imagine a holiday cabin in the Czech Republic that is to be lived in all year. With efficient appliances and a low-idle inverter, the load audit gives 3.5 kWh/day. December is the design month at about 1.3 peak sun hours on a 60° array (a reasonable PVGIS-type value here; verify for your own site), and PR is 0.6.
| Design element | Calculation | Result |
|---|---|---|
| Array (no generator) | 3.5 ÷ (1.3 × 0.6) | 4.5 kWp |
| Array (with generator for Dec–Jan) | sized on February, PSH ≈ 2.2 | 2.7 kWp → choose 3 kWp |
| Battery (3 days autonomy, LFP) | 3.5 × 3 ÷ (0.9 × 0.95) | 12.3 kWh nominal |
| Battery (1.5 days, with generator) | 3.5 × 1.5 ÷ (0.9 × 0.95) | 6.1 kWh → choose 7–10 kWh |
| Inverter | pump 0.6 kW + kitchen 1.2 kW + misc 0.5 kW, ×1.4 | 3 kW, 48 V |
| Generator | charger 2–3 kW, ~150–300 h/year | 3–4 kVA petrol or LPG |
With a generator, the system costs about half as much and the generator runs maybe 150–300 hours a year, mostly in December and January. In summer, the 3 kWp array makes many times the cabin’s needs and most of it goes unused, unless you add daytime loads that can flex, like a dump-load water heater or an e-bike charger. For month-by-month surplus and deficit at your site, run the off-grid solar calculator.
Backup sources and hybrids
Insisting that solar alone cover every day in a northern climate leads to absurdly big arrays and batteries. The least costly design almost always brings in a second source for the final 5–15% of yearly energy:
- A petrol or LPG generator that the inverter starts automatically. LPG stores without limit and burns more cleanly.
- A small wind turbine, since winter wind often complements solar; worthwhile only on exposed, genuinely windy land (see small wind turbines for homes).
- Micro-hydro: where a stream has enough head, it can run round the clock all winter and beat both. Test the idea with the micro-hydro calculator.
What it costs and how to maintain it
Costs depend on the country and on how much you do yourself. Rough 2024–2026 figures for professional installation in Europe:
| Component | Indicative cost |
|---|---|
| Solar modules + mounting | €400–900 per kWp |
| MPPT controller / hybrid off-grid inverter (3–5 kW) | €1,000–3,000 |
| LFP battery | €300–700 per kWh usable |
| Cabling, protection, earthing, installation | 20–40% of hardware |
Altogether, a 3 kWp, 10 kWh, 3 kW system lands at roughly €8,000–15,000. Maintenance is light: keep panels free of snow and leaves, re-torque battery terminals and fuse holders yearly, apply firmware updates and log the state of charge so a weakening cell group is spotted early.
Off-grid solar worldwide
Off-grid solar is more than a retreat for hobbyists. Per IEA’s SDG7 tracking, about 750 million people had no electricity in the early 2020s, mostly in sub-Saharan Africa, and the IEA and IRENA both see solar home systems and mini-grids as the cheapest way of reaching many of them. The country profiles show access and generation, and a click on the Energy Explorer reveals the solar resource at any location before you design.
Calculators related to this topic
Frequently asked questions
How many panels does an off-grid home need?
What size battery do I need for an off-grid system?
Is it realistic to heat with electricity or a heat pump off-grid?
Does going off-grid save money compared with a grid connection?
Should I buy an MPPT or a PWM charge controller?
Which battery voltage is best for an off-grid system?
Sources & references
- NREL — PVWatts Calculator (solar resource and production modelling)
- European Commission JRC — PVGIS, including the off-grid PV performance tool
- IEA — SDG7 Data and Projections: Access to Electricity
- IRENA — Off-grid Renewable Energy Solutions to Expand Electricity Access
- Sandia National Laboratories — Stand-Alone Photovoltaic Systems: A Handbook of Recommended Design Practices (SAND87-7023)
The figures in this guide are typical ranges taken from the listed sources, and your own values will vary with location, prices and equipment. For estimates specific to your site, use the linked calculators.